Often times those using a Variable Frequency Drive (
VFD) may find themselves needing to connect a higher horsepower
VFD to a
single phase input power source. Since most higher horsepower
VFDs only accept
three phase input as a power source, they are left with little options or alternatives. Don’t fret, there is a solution.
If you are using a Variable Frequency Drive (
VFD) rated for
three phase input and the only power source you have available to you is
single phase input, then you can
derate the Variable Frequency Drive (
VFD) to accept the
single phase input power source. You can almost always use a VFD rated for
three phase input with a
single phase input power source. Of course, if it is available, try to use a
single phase input rated VFD if your power source is single phase.
When only a
three phase input VFD is available, it is acceptable and common practice to
derate the
VFDto work with a
single phase input power source. Variable Frequency Drive (
VFD) availability and installation procedures may vary from one manufacturer to another.
Before you
derate your
VFD, it is most important to ensure the
VFD you are using is properly suited for your application. The following are some basic guidlines to help you in determining whether or not your Variable Frequency Drive (
VFD) is suitable for your application:
- Gather motor nameplate data including horsepower (HP), current (Amps), motor voltage, input line voltage and power source phase.
- Determine which type of VFD your application will require. The type will fall under the category of either Volts per Hertz (V/Hz), closed-loop vector, or open-loop vector (Sensorless Vector).
The internal components of the
three phase input Variable Frequency Drive (
VFD) is rated for the appropriate current expected when
three phase input power is applied. When using
single phase inputinstead, the line side current from the single phase is always higher. To “
derate“ is the process of ensuring that these component are rated for the higher current that will flow from the
single phase input instead of the
three phase input.
You can
derate a
VFD by:
- Determining the Horsepower of the Motor the VFD will be connected too, then
- Choosing VFD with a Horsepower higher than the Horsepower of the motor to compensate for the additional input current from the single phase power source.
The simplest formula used for these types of applications is:
VFD Input Current > Motor Current Rating * 1.73
The
VFD input current must be equal to or greater than the Motor Current Rating * 1.73.
When installing most
three phase input Variable Frequency Drives (
VFDs) on an application where
single phase input power is used, you will almost always connect the input line leads to L1 and L2 of the
VFD. L3 will be left open with nothing connected. Consult with the
VFD manufacturer or knowledgeable integrator to be sure.
Example Application to
Derate a
Three Phase Input Variable Frequency Drive (
VFD) to work with a
Single Phase Input power source:
An application has a 230 VAC
single phase input power source and needs to connect it to a conveyor that has a Variable Frequency Drive (
VFD) connected to a 10 Horsepower 230 VAC 3 phase induction motor. Let us assume it has been determined that this application will operate well with a simple Volts per Hertz (V/Hz)
VFD. The issue is, since there are no
VFD manufacturers that offer a 10 Horsepower (HP)
single phase input Variable Frequency Drive (VFD), we will need to
derate a
VFD with a
three phase input for
single phase input. Most manufactuers of
VFDs only offer products up to 3 Horsepower (HP) for
single phase input,
three phase output; some products such as AC Tech SCF series do offer standard
single phase input,
three phase output products available up to 5 Horsepower (HP) range.
The 10 Horsepower (HP) AC motor nameplate reveals that the motor is rated for approximately 27 amps at 230 VAC. We must use the equation above:
- VFD Input Current > Motor Current Rating * 1.73
- VFD Input Current > 27 Amps * 1.73
- VFD Input Current > 46.71
Now it has been determined this application will need a 230 VAC 3 phase Volts per Hertz (V/Hz) Variable Frequency Drive (
VFD) with an input current rated at or above 47.0 amps.
Our company’s
VFD of choice is the AC Technology/Lenze SMVector (SMV) product. Although this
VFD is open-loop vector capable and this application only requires a standard Volts per Hertz (V/Hz)
VFD, the AC Tech SMVector (SMV)
VFD is a great alternative to any manufacturer of Volts per Hertz (V/Hz) products because the SMV is often the same price or cheaper as any other Volts per Hertz (V/Hz) product and can operate in either Volts per Hertz (V/Hz) mode or open-loop vector. These
VFDs are also available in both Nema 1 and Nema 4x enclosures.
Looking into the product catalog, we find an SMV model fitting the requirements available rated at 15 Horsepower (HP) that has a 230 VAC
three phase input rated for 48 input amps.