SMV Parameter Setup & High Frequency Output
Setting up SMV Drive Parameters
1. Enter the “edit parameter mode” by:
a. With the drive powered up the display should read “Stop”.
b. Press the M key once. The drive will flash “PASS” then display “0000”
c. Using the arrow keys change the display to read the default password “0225”
d. Press the M key once. You can now use the arrow keys to navigate to the parameter you want to change.
Changing the SMV to high frequency mode above 120hz:
1. Enter the “edit parameter mode”
2. Navigate to parameter P103 (Maximum Frequency Output)
3. Press the M key once.
4. Use the arrow keys to change the maximum frequency to the desired value. The range of adjustment is 7.5 hz to 500 hz. When changing this parameter to a value higher than 120 hz you must stop first at 120 hz. The drive will flash “Hi Fr”. Release the button for one second. Press the key again to proceed to the desired value higher than 120 hz.
5. Press the M key once. The maximum frequency is now set to the desired value.