AC Tech SCF Series: Models, Ratings, I/O and Replacement Guide
If you have an AC Tech SCF series drive on a machine, you need to know what it is, how to read its label, and what to do when it fails. This guide covers the models, ratings, I/O, options, setup points and replacement path in one place. It also separates what Lenze documents from what resellers say.
On this page
- What the AC Tech SCF series is
- AC Tech SCF series model numbers and how to read them
- AC Tech SCF series ratings by voltage class
- Features and I/O of the AC Tech SCF series
- EPM, keypad, software and options for the AC Tech SCF series
- Where each SCF size fits
- Installing and wiring an AC Tech SCF series drive
- Setting up and programming the AC Tech SCF series
- Common AC Tech SCF series faults and when to repair
- SCF is discontinued: what replaces it
- i510 and i550 protec drives that replace the SCF
- AC Tech SCF series vs SMVector vs i510/i550: comparison
- Cost, lead time and where to get parts and manuals
- Frequently asked questions
What the AC Tech SCF series is
What is the AC Tech SCF series?
The AC Tech SCF series is a family of compact “sub-micro” frequency inverters from Lenze / AC Tech. First, these drives use V/f control (a fixed voltage-to-frequency ratio) to run three-phase induction motors. They also come in IP20 panel-mount form, so you mount them inside an enclosure.
The Lenze SCF drive fits tight panel layouts where the process still needs full I/O. The model prefix is SF. In addition, the manual covers the SF200Y, SF200, SF400 and SF500 classes. Output is always three-phase.
Is the AC Tech SCF series discontinued?
Yes. Resellers list SCF models as discontinued by the manufacturer, and Lenze shows the series under “previous products” on its site. As a result, you will find new-old-stock, used or repaired units, not current production. The replacement section below covers what to buy instead.
AC Tech SCF series model numbers and how to read them
How do I read an SCF model number such as SF210Y?
The manual gives SF210Y as its example. Here is how the code breaks down:

- SF means SCF series.
- The digit 2 means the 208/240 Vac class.
- Next, 10 means 1 HP.
- Finally, Y means single- or three-phase input.
The voltage classes are SF2xx for 208/240 V, SF4xx for 400/480 V and SF5xx for 480/590 V. However, watch the SF510. It is the 1 HP 480/590 V unit, not a 5 HP model.
How do SF200 and SF200Y differ in the AC Tech SCF series?
The Y suffix tells you the input phase. The SF200Y models (SF203Y through SF250Y) take 208/240 Vac single- or three-phase input. In contrast, the plain SF200 models need three-phase input. Both work at 208-240 Vac (+10%, -15%) and 48 to 62 Hz.
The AC Tech SF200 series also has variants. For example, these include a through-hole mount, a PI set-point option and a high-frequency option for output up to 1000 Hz.
AC Tech SCF series ratings by voltage class
What HP and voltage ratings does the AC Tech SCF series come in?
Precision’s product pages and the Lenze datasheet describe 1/4 to 30 HP (0.18 to 22 kW). However, one reseller datasheet says 25 HP, so confirm the top size against the manual and the drive nameplate. Also, sources disagree on a 120 V single-phase option. The Lenze datasheet lists single-phase 208 or 240 VAC only.
The Lenze datasheet lists three-phase input at 208, 240, 400, 480 or 590 VAC. It also lists 50 or 60 Hz supply (+10/-15%) and output of 0 to 240 Hz, with operation to 1000 Hz as an option.
What are the output amps for each SCF model?
This table shows the 208/240 V Y-series models. The higher amp figure is for 208 V input and the lower is for 240 V.
| Model | HP | kW | Output amps (208/240 V) | Frame |
|---|---|---|---|---|
| SF203Y | 0.25 | 0.18 | 1.6 / 1.4 | A1 |
| SF205Y | 0.5 | 0.37 | 2.5 / 2.2 | A1 |
| SF210Y | 1 | 0.75 | 4.8 / 4.2 | A2 |
| SF215Y | 1.5 | 1.1 | 6.9 / 6.0 | B1 |
| SF220Y | 2 | 1.5 | 7.8 / 6.8 | B2 |
| SF230Y | 3 | 2.2 | 11.0 / 9.6 | B2 |
| SF250Y | 5 | 3.7 | 17.5 / 15.2 | C1 |
The same footnote rule applies to the other classes. In the SF4xx class, the higher current is for 400 V and the lower for 480 V. Likewise, the SF5xx higher figure is for 480 V and the lower for 590 V. As for larger models, our listings show the SF2150 (15 HP, 208-240 VAC three-phase) at 42.0 A and the SF450 (5 HP, 400-480 VAC) at 7.6 A.
In the manual, STD means a standard unit and THRU means a through-hole mount unit. For the remaining sizes, check the manual’s rating tables.
What overload capacity does the SCF drive have?
The manual lists 150% overload for 60 seconds and 180% for 30 seconds. In addition, other published specs include:
- Carrier frequency of 4 to 10 kHz, fully rated to 6 kHz.
- Efficiency up to 98%.
- Operating temperature of 0 to 50 °C, derated 2.5% per °C above 50.
- Storage temperature of -20 to 70 °C.
- Humidity under 95%, non-condensing.
- Altitude to 3300 ft, then derate 5% per additional 3300 ft.
Features and I/O of the AC Tech SCF series
What I/O does the AC Tech SCF VFD have?
The full-feature AC Tech SCF VFD has 18 isolated control terminals. They break down as follows:

- Five logic inputs: one dedicated stop, one dedicated start and three programmable. They are active low (NPN).
- Two open-collector logic outputs.
- Also, two analog inputs: one 0-10 VDC and one 4-20 mA.
- Two analog outputs, as well.
- Finally, a 12 VDC, 50 mA supply.
The drive also offers 8 preset speeds, jog, DC injection braking and a fault history of the last 8 faults. In addition, a 3-digit LED display and buttons let you program it at the drive face.
Does the SCF support Modbus?
Yes. The drive has 2-wire RS485 Modbus RTU. The SCF Modbus Communications Reference Guide (32 pages) covers control, status monitoring and parameter programming. It also lists registers, the watchdog timer and quick-start steps.
The drive has a built-in motor overload too. Because it is UL approved for solid-state overload protection, a single motor needs no separate overload relay. Its adjustable thermal overload circuit guards against excess current. Finally, the drive is UL/cUL listed, carries CE (EMC when suitably filtered) and has a two-year warranty.
EPM, keypad, software and options for the AC Tech SCF series
What is the EPM and how do I copy SCF settings?
The EPM is the electronic programming module. It stores the drive’s program. With the EPM programmer, you can copy a program to another module in about 2 seconds. As a result, cloning settings to a spare drive is quick.
You can also program through the drive face, the remote keypad, or a PC with TechLink software.
How do I clone or restore settings step by step?
First, remove power from the drive and wait for the internal capacitors to discharge. Next, pull the EPM from its socket. Then either copy it with the EPM Programmer, or seat the copied EPM in the spare drive. Finally, make sure the module sits firmly before you power up.
The exact button steps on the EPM Programmer and the TechLink screens are in their own instructions, so follow those. Also, we do not list OEM default values here. Check the parameter tables in the installation manual instead.
What options exist for the SCF drive?
AC Tech lists these options for the SCF sub-micro drive:
- Remote keypad (844-200): full-function, NEMA 4X when mounted properly, usable up to 100 feet away.
- DIN rail kit: for rail mounting.
- Through-hole mount: puts the heat sink outside the enclosure.
- Dynamic braking kit: for faster stops.
The remote keypad connects over RS485 and allows operation and programming. Radwell describes the 844-200 as having a segment display. The backlit LCD, plain-language programming and parameter copy belong to the battery-powered EPM Programmer, not the keypad. In addition, the keypad has Start/Stop and Forward/Reverse keys. A signal on terminal 13A or 13C can then toggle between remote keypad and terminal strip control.
What cable does the remote keypad need at 100 feet?
The cable supplied with the keypad is only good to about 8 feet in low-noise areas. For longer runs, up to the 100 foot limit, you need a better cable. Because the link is RS485, a shielded twisted-pair cable is the usual choice, and you should keep it away from motor and power wiring. For the exact cable type, check the remote keypad instructions or call us.
Where each SCF size fits
What applications is the AC Tech SCF series good for?
The SCF suits three-phase motor jobs that need reversing, soft start or variable speed. For example, it can run up to 4 times the motor’s rated RPM, and the high-frequency option supports up to 1000 Hz. It also works well for panel retrofits and for DIN-rail or through-hole layouts.
Pick the voltage class by your supply:
- 208/240 V for machines fed by single-phase power, up to 5 HP with the Y models.
- 400/480 V for common industrial three-phase supplies.
- Finally, 480/590 V for 575 V systems.
Remember that the SCF is a V/f drive. So do not treat it as a sensorless-vector or servo drive.
What enclosure does the SCF need?
Most SCF drives are IP20, so they must go inside a protective enclosure such as a NEMA 1 or NEMA 12 panel. Next, mount them vertically for convection cooling. However, the drive body is not NEMA 4X or washdown rated. Only the remote keypad (mounted properly) and the through-hole option with the heat sink outside can reach NEMA 4X.
Installing and wiring an AC Tech SCF series drive
How do I install and wire an SCF drive?
First, mount the drive vertically in a clean, dry, vibration-free spot. Next, check that the supply voltage matches the nameplate. Then use the manual’s fuse and wire tables and your local code. Do not rely on memory for fuse or wire sizes.

Keep these points in mind:
- Keep ambient temperature within 0 to 50 °C, and derate above that.
- Also derate for altitude above 3300 ft.
- Use wire rated at least 75 °C.
- Keep carrier frequency at 6 kHz or below for full rating. At 8 or 10 kHz, the ambient rating drops.
- Finally, check the wiring diagrams in the manual before you power up.
If a drive sat unused for a long time, its storage capacitors may need attention. In that case, follow the manual’s guidance before you apply full power.
When does an SCF drive need a line reactor?
Add an isolation transformer or a 2-3% line reactor when the supply transformer is more than 10 times the drive’s input kVA. Because a large transformer can pass high fault current and line spikes to the drive, this step matters. The reactor limits both.
Setting up and programming the AC Tech SCF series
How do I program the SCF and use the remote keypad?
First, choose the control source: the drive keypad, the terminal strip, the remote keypad or Modbus. Then set the parameters from the quick reference manual, which covers the terminal strip and parameter menu. Because the quick reference is only 2 pages, you can keep a copy near the panel.
Parameter changes made while the drive runs may not take effect until it stops. So if a change seems ignored, stop the drive and check again. For remote keypad use, wire a switch to terminal 13A or 13C to toggle between keypad and terminal control.
Common AC Tech SCF series faults and when to repair
Where do I find SCF fault messages?
The installation manual has a display messages section that lists each fault code with its cause and fix. Start there. Then run through the usual checks:

- Input voltage within +10/-15% of the nameplate.
- Carrier frequency and ambient temperature, for derating.
- Motor and control wiring.
- Finally, an EPM that sits firmly in its socket.
When should I repair an SCF instead of replacing it?
Repair makes sense when the drive will not power up, or trips again and again after you verify wiring and settings. Because the series is discontinued, repair keeps a working machine running without a redesign. In addition, Precision repairs the series.
SCF is discontinued: what replaces it
What replaces the AC Tech SCF series?
Resellers point to SMVector units as SCF replacements. For example, Radwell lists the SF510 with replacement ESV751N06TXB. However, the SMVector began in 2006 and is now in phase-out. As a result, Lenze is migrating customers to the i510 protec and i550 protec, which are certified to UL 61800-5-1.
No Lenze page we found gives a direct SCF-to-i510/i550 cross-reference. Lenze documents only SMVector to i510/i550. So match by HP, voltage, phase and current, and do not assume.
Lenze and Wolf Automation also give these cautions:
- The i510/i550 can share mounting holes with many SMVector units, but wiring and programming changed.
- Motor wiring differs from the SMVector, so check the wiring diagram first.
- Control terminals are push-in spring type.
- Finally, choose the i550 for dynamic braking.
Can I reuse my SCF EPM in an i510 or i550?
No. Lenze says EPM memory modules are not interchangeable between the SMVector and the i510/i550. However, Lenze offers a migration service. Send your wiring diagram, the EPM and the new part number, and they create a parameter list, wiring diagram and program file.
i510 and i550 protec drives that replace the SCF
Which i510 or i550 model do I choose for my SCF?
The i510 is the simpler drive. Our stocked i510 units have basic I/O, or CANopen and Modbus-RTU. In contrast, the i550 adds application I/O, CANopen or EtherCAT, and an optional STO (safe torque off) module.

Our stock is all 0.33 HP. The i510 units take 208-240 VAC single-phase input and are rated 1.7 A. Meanwhile, the i550 units take 120 V or 230-240 V single-phase input. Output is single-phase or three-phase 240 V, depending on the model.
- If you need braking, STO or EtherCAT, choose the i550.
- However, if you need simple speed control and Modbus, choose the i510.
- In our listings, “STO Module Included” or “No STO” tells you the safety option. Also, the I/O wording tells you basic, CANopen/Modbus-RTU or EtherCAT.
These are small-frame units. As a result, they do not cover every SCF size, so larger replacements need a catalog check or a call.
AC Tech SCF series vs SMVector vs i510/i550: comparison
How does the SCF compare with the SMVector and i510/i550?
| Feature | SCF | SMVector | i510/i550 protec |
|---|---|---|---|
| Enclosure | IP20 | NEMA 1 and NEMA 4X models | IP20 in our stock |
| Control | V/f only | See Lenze literature | See Lenze literature |
| Control terminals | Screw | Screw | Spring, fixed |
| Memory | EPM | EPM | Not interchangeable with EPM |
| Comms | RS485 Modbus | See Lenze literature | i510: Modbus, CANopen; i550: CANopen, EtherCAT |
| Braking | Dynamic braking kit | See Lenze literature | i550 for dynamic braking |
| Status | Discontinued | In phase-out | Current line |
The i550 also has a dedicated PTC input. In addition, Lenze says size is similar between the SMVector and the new drives.
Cost, lead time and where to get parts and manuals
How much does an AC Tech SCF series drive cost?
Prices for discontinued SCF units vary widely and stock changes. Other retailers show list prices in the thousands for large models, but those are not our prices. So for current pricing, check the Precision product page or contact us. Our SCF listings carry a two-year manufacturer warranty, and we also offer repair.
Where do I download the SCF manual and Modbus guide?
Our SCF Series Manual page links the manual. In addition, the Lenze Americas site carries more literature, and Lenze lists the SCF under previous products. Manualslib also hosts three documents:
- The Installation and Operation Manual (68 pages).
- The remote keypad instructions (2 pages) and quick reference (2 pages).
- Finally, the Modbus Communications Reference Guide (32 pages).
The manual covers dimensions, the model code, specs, ratings, fusing, wiring diagrams, programming and display messages. Its appendices also cover through-hole mounting and PI set-point control.
Frequently asked questions
What is the AC Tech SCF series?
It is a family of IP20 sub-micro V/f frequency inverters from Lenze / AC Tech. They drive three-phase induction motors from 1/4 to 30 HP. In addition, the I/O includes 5 logic inputs, 2 logic outputs, 2 analog inputs, 2 analog outputs and RS485 Modbus.
Is the AC Tech SCF series still made?
No. Resellers list SCF models as discontinued by the manufacturer. As a result, Lenze’s migration path for its older small drives goes through the SMVector and now the i510 protec and i550 protec.
What replaces an SCF drive?
Match by HP, voltage, phase and amps. Resellers point to SMVector units, such as ESV751N06TXB for the SF510, and Lenze is moving SMVector users to the i510/i550 protec. However, EPMs are not interchangeable, the terminals are push-in, and braking needs the i550. Motor wiring also differs from the SMVector, so check the wiring diagram before powering up.
Can an SCF run on single-phase input?
Yes, for the SF200Y models (SF203Y through SF250Y). They are rated for 208/240 Vac single- or three-phase input. However, the plain SF200 models need three-phase input. Output is always three-phase.
Does the SCF need a separate overload relay?
Not for a single motor. The SCF is UL approved for solid-state motor overload protection with an adjustable thermal overload circuit.
Where can I download the SCF manual?
Our SCF Series Manual page links the manual, and the Lenze Americas site carries more literature. Manualslib also hosts the installation manual, the quick reference and the Modbus reference guide.
The AC Tech SCF series is a capable, compact drive, but it is now a legacy product. So know your model code, verify the ratings in the manual, and match any replacement by HP, voltage, phase and current. If you need a repair, a replacement drive or help choosing between the i510 and i550, contact Precision Electric or browse our drives.