ACS580 Guide: Variants, Part Numbers and Horsepower Ratings

ABB ACS580 VFD mounted in an open cabinet, wired by cable to an electric motor, with a fan and ducting nearby.

The acs580 is ABB’s general purpose AC drive, and picking the right model from a long part number list is not always easy. This guide explains the family, decodes the ACS580-01 part number, and matches common horsepower ratings to the drives we stock. You will also learn how it compares with other ABB drives and what to check before you order.

On this page

What the ABB ACS580 is

What is the ABB ACS580 drive?

The ABB ACS580 is a general purpose drive family rated 0.75 to 500 kW. It controls the speed of AC motors, so it works as a variable frequency drive (VFD). In addition, ABB calls it part of its “all-compatible” platform, which means it shares tools and options with related drives.

The ACS580 also shares a base platform with the ACH580 for HVAC and the ACQ580 for water. In North America, the ACS580-01 covers 1 to 350 hp at 480 V, 1 to 100 hp at 230 V and 2 to 250 hp at 575 V.

Which loads and industries is it designed for?

This ACS580 general purpose drive suits pumps, fans, conveyors, compressors, mixers and similar loads. For example, ABB lists food and beverage, agriculture, automotive, and rubber and plastics among its industries. Because it uses vector control, it gives high starting torque at low speed.

Which standard features are included?

Every ABB ACS580 VFD ships with a useful feature set. First, here is what ABB’s catalog lists:

  • A built-in choke to reduce harmonics
  • EMC level C2 for the first environment
  • Safe Torque Off (STO), described as SIL 3
  • The ACS-AP-S assistant control panel
  • Support for high-efficiency, PM and SynRM motors
  • An integrated braking chopper up to 30 hp
  • Coated boards for harsh conditions
  • An external +24 V supply, optional on frames R1 to R5

ACS580 variants: -01, -04, -07 and -0P

What do the -01, -04, -07 and -0P variants mean?

The two digits after the series name tell you how the drive is built. As a result, each ABB ACS580 drive variant fits a different job.

Isometric drawing of three small wall-mounted drives with fans, cabled to a taller floor cabinet with an orange fan.
Curved grey conduit loops drop from each smaller unit into the large enclosure’s side.
  • ACS580-01: wall-mounted. It is IP21 / UL Type 1 as standard and IP55 / UL Type 12 with +B056. ABB’s latest catalog (Rev R, 2026) lists it from 0.75 up to 355 kW. Earlier catalog editions and the hardware manual, which covers up to R9, give 250 kW (350 hp).
  • ACS580-04: a drive module for 250 to 500 kW. It is IP00 as standard, with IP20 (UL Type 1) optional.
  • ACS580-07: cabinet-built, 30 to 500 kW. It is IP21 as standard, with IP42 or IP54 (UL Type 12) options.
  • ACS580-0P: a packaged drive with a disconnect, in a UL Type 12 enclosure.

Every drive in our listings is an ACS580-01. However, we cover the -0P in its own guide, so we will not repeat it here.

ACS580-01 part numbers explained

What does -01 mean and what frame sizes does it come in?

The ACS580-01 is the wall-mounted drive. It comes in frame sizes R1 to R9. In addition, earlier manual revisions also cover R0, and the R9e frame has its own installation instructions. To find your frame, check the type label and the hardware manual.

How do I read a part number?

Take ACS580-01-124A-4+B056 as an example. Next, read it in pieces:

  1. ACS580: the series.
  2. -01: the wall-mounted variant.
  3. 124A: the current code, in amps.
  4. -4: the voltage code.
  5. +B056: an option code, here the IP55 / UL Type 12 enclosure.

Which supply voltages are supported?

The voltage code tells you the supply range. A 2 means 208 to 240 V, a 4 means 380 to 480 V, and a 6 means 525 to 600 V. However, our -6 listings show 540 to 600 V input, so confirm the voltage on the nameplate or in the catalog before you order.

What do the option codes mean?

The hardware manual lists these option codes:

  • +B056: IP55 / UL Type 12
  • +B063: IP66
  • +B066: UL Type 4X
  • +C135: flange mounting
  • +C193: sun shield, used only with +B063 or +B066
  • +F278: main switch disconnector
  • +F316: disconnector plus EMC C1 filter
  • +E223: EMC C1 filter

Note that the +F278, +F316 and +E223 options are available only on IP55 (+B056) drives. Also, in our listings, “NEMA 1” means UL Type 1 / IP21. Likewise, “NEMA 12” means +B056 / IP55.

ACS580-01 ratings by horsepower and voltage

What is the difference between normal duty and heavy duty ratings?

Each drive has two ratings. At normal (light) duty, the drive can run a larger motor. At heavy duty, however, it runs a smaller motor with more overload room. For example, ABB’s US catalog lists the ACS580-01-273A-2 at 100 hp light duty (273 A) and 75 hp heavy duty (211 A).

Orange variable frequency drive mounted on a DIN rail, wired to two electric motors, with a clamp meter and coiled cable
Leads fan out from the housing’s base, one bundle heading to each unit.

Which model do I need for a 10, 100 or 125 hp motor?

This table shows the models we stock. For the NEMA 12 version, add +B056 to the part number.

Motor hpSupply voltageOutput ampsBase part number
10208–240 V30.8 AACS580-01-031A-2
10400–480 V14 AACS580-01-014A-4
10540–600 V11 AACS580-01-011A-6
100208–240 V273 AACS580-01-273A-2
100400–480 V124 AACS580-01-124A-4
100540–600 V99 AACS580-01-099A-6 (NEMA 1 only)
125400–480 V156 AACS580-01-156A-4

ABB’s catalog lists the 031A-2 as frame R2 and the 273A-2 as frame R8. For other models, you can look up the frame in the catalog or hardware manual.

How do I size the drive to the motor?

Do not size by horsepower alone. Instead, compare the drive’s current with the motor’s full-load amps on the nameplate. Then check the duty: variable torque, or heavy duty for constant-torque loads.

How do altitude, ambient temperature and switching frequency derate the output current?

Derating means the drive can give less output current than its rating. First, high ambient temperature cuts the current once the air around the drive passes about 40 °C (104 °F). Next, altitude above about 1,000 m (3,300 ft) cuts it because thin air cools less well. Also, a higher switching frequency cuts it because the drive makes more heat. The exact percentages differ by type and frame, so use the derating tables in the hardware manual for your drive.

Where each enclosure and variant fits

NEMA 1 versus NEMA 12 (+B056): what is the difference?

A NEMA 1 drive (IP21 / UL Type 1) fits clean, conditioned electrical rooms or the inside of a panel. A NEMA 12 drive (IP55 / UL Type 12, option +B056) is built for dust, moisture and vibration. As a result, it can hang on a wall in the plant, and it has a footprint similar to the Type 1 drive. Also, in North America, a hood comes with +B056.

Exact dimensions, weights and side-by-side mounting clearances differ for each frame and enclosure. Therefore, take them from the dimension tables in the hardware manual for your frame before you plan the layout.

When do I need something else?

For washdown or outdoor use, look at IP66 (+B063) or UL Type 4X (+B066), with the sun shield outdoors. However, if you want a disconnect or bypass built in, look at the -0P or -07. Finally, above 250 kW, the -04 module or -07 cabinet is the route.

What “ACS580 panel” means: control panel versus panel-built drives

What is an ACS580 panel?

People use the phrase “acs580 panel” in two ways. First, it can mean the control panel, the keypad on the front. The ACS-AP-S assistant control panel is standard and supports 16 languages. In addition, options are the Industrial assistant panel (+J425) and a Bluetooth panel (+J429) that connects to a mobile app. With the CDPI-01 panel adapter, one assistant panel can manage up to 32 drives.

Isometric illustration of an open navy and grey enclosure beside an orange drive module, a ribbon cable, and a small grey
Cabinet door swung wide, with mounting feet bolted to a flat base plate.

What is the difference between the ACS580-01 and the ACS580-07 or -0P?

Second, an ACS580 panel can mean a panel-built drive. The -07 is a cabinet-built drive, and the -0P is a packaged drive with a disconnect. In addition, the -0P is also offered with a circuit breaker disconnect and a two-contactor bypass. These suit you if you want a ready-to-wire enclosure instead of building your own.

What if I build my own panel?

The ABB catalog lists recommended input fuses (gG and UL Class T), heat loss, cooling airflow and noise level for each type. For example, the ACS580-01-089A-4 is frame R4 with 100 A gG and 110 A UL Class T fuses. Therefore, always take values from the row for your exact type.

ACS580 compared with ACH580, ACQ580, ACS880 and the ACS550

How does the ACS580 compare with the ACH580, ACQ580 and ACS880?

These points come from third-party comparisons, not ABB, so confirm them in ABB’s catalogs. First, the ACH580 shares a base platform but adds native BACnet, HVAC macros and multi-pump logic. Next, the ACQ580 targets pump protection in water and wastewater. Finally, the ACS880 is the industrial platform, with options such as regeneration, an embedded PLC, liquid cooling and higher power.

NeedBest fit
Pumps, fans, conveyors, compressorsACS580
Building HVAC with BACnetACH580
Water and wastewater pumpsACQ580
Regeneration, embedded PLC, higher powerACS880

The ACS580 uses vector and scalar control. However, for heavy-duty or hoist loads, choose the ACS880 or talk with an applications engineer.

Can an ACS580 replace an ACS550?

Yes. ABB’s replacement guide maps ACS550-U1 types to ACS580-01 types, but the current code often changes. For example, ACS550-U1-012A-4 maps to ACS580-01-012A-4, while ACS550-U1-012A-2 maps to ACS580-01-10A6-2 and 248A-2 maps to 273A-2. Always check the guide’s table for your exact type. Likewise, the old +B055 (Type 12, IP54) maps to +B056 (Type 12, IP55).

Installing and commissioning an ACS580

How do I wire and set up an ACS580?

Read the hardware manual for your frame before you wire. Then follow it and local code (NEC / UL) for fusing and conductors. In UL installations, use copper conductors only. However, under IEC, aluminum is allowed only for input power cabling on 230 V drives of frames R5 to R8. Also, the catalog lists motor cables up to 1,000 ft (300 m).

Open blue cabinet with an orange drive unit mounted inside, beside a workbench holding wire spools, pliers, cutters
Metal conduit lengths sit on the table, ready for bending before any terminations.

For setup, use the assistant control panel. Because its primary settings menu and start-up assistants walk you through the basics, you do not need to know every parameter up front.

What are the EMC filter settings for IT or ungrounded supplies?

The drive has an internal EMC filter that is connected at the factory. On an IT (ungrounded) supply, this filter can cause problems, so you disconnect it. To do so, first lock out and wait for the DC link to discharge. Then remove the screws marked for the EMC filter, as the hardware manual shows for your frame. Note that with the filter disconnected, the drive no longer meets its stated EMC category. Also, cable-length limits depend on the EMC setting, so check the manual for your frame.

How do I wire and test the STO circuit?

Wire both STO channels to the STO connector on the control board, using the terminals the hardware manual shows. Both channels must open together to stop the motor safely. Next, run the validation test in the manual, and repeat it after any wiring or parameter change. If the check fails, for example the drive still runs with one channel open, treat the circuit as unsafe. Do not use it. Instead, find the wiring or relay fault and test again, or call us.

Which braking resistor do I need?

Sizing depends on how much energy the load returns and how often it brakes. First, find the braking power and duty cycle for your load. Next, pick a resistor that handles that energy and is not below the minimum resistance in the hardware manual for your type. In addition, the catalog states that the chopper is built in up to 30 hp. As a rule, that covers the smaller frames, R1 to R3. For larger frames, confirm in the catalog whether you need to add a chopper.

What do common fault codes mean, and how do I reset them?

The panel shows a fault or warning code, and the event logger in Drive Composer records it. Here are four common codes:

  • 2310: overcurrent. Check for a short circuit, a motor or cable fault, or a ramp that is too fast.
  • 3210: DC link overvoltage. Check for fast deceleration or a missing braking resistor.
  • 3220: DC link undervoltage. Check for a supply dip or a lost phase.
  • 4310: excess temperature. Check for blocked airflow, a dead fan or high ambient heat.

First fix the cause. Then press the reset key on the panel, or reset through the control source. Because the list is long, use the fault tracing table in the firmware manual for any other code. If a fault keeps returning, call us.

Which software and tools work with it?

Drive Composer entry is free from ABB. It gives access to parameters, the event logger and basic monitoring. In addition, Drive Composer pro adds data loggers, fast monitoring, control diagrams, safety configuration, macro script and multi-drive work. For the current version, check the ABB Library.

To connect a PC, install the panel USB driver and plug into the USB port on the assistant control panel. However, you cannot use the panel while it is connected to a PC. Also, the drive supports F-series fieldbus adapters.

Which fieldbus adapters fit the ACS580?

Modbus RTU is built in. For other networks, you add a plug-in adapter. Here are the common ones:

  • FPBA: PROFIBUS DP
  • FENA: Ethernet adapters, such as EtherNet/IP, Modbus TCP and PROFINET IO
  • FDNA: DeviceNet
  • FCAN: CANopen
  • FECA: EtherCAT

Adapter models and revisions change, so confirm the exact one in the ABB catalog before you order.

What to check before ordering an ACS580

What should I check before ordering an ACS580?

First, run through this list:

  1. Motor nameplate voltage, full-load amps and hp
  2. Supply voltage and phase
  3. Duty: variable torque or heavy duty
  4. Location: dusty or wet areas need +B056
  5. Frame size and mounting space
  6. Options such as a fieldbus adapter or Bluetooth panel
  7. Fuses and disconnect

What are common selection mistakes?

Unfortunately, the same errors come up again and again:

  • Sizing by hp only
  • Buying a Type 1 drive for a dusty location
  • Picking the wrong voltage code
  • Forgetting that “NEMA 12” means adding +B056
  • Ignoring heavy-duty ratings on constant-torque loads
  • Assuming the ACS580 handles hoists or regeneration

When should I call for repair or application help?

Call if you see repeated faults or a failed STO check. Also call if you do not know the drive you are replacing, or if the old model is obsolete. In that case, send the nameplate and the drive’s type label, and we can match it to a part number.

Documents, software and support

Where do I download manuals, catalogs and software?

Everything is in the ABB Library. To start, search for these documents there:

ACS580 drive in a cabinet with a laptop, binders, and glasses on a workbench, connected to a motor.
Orange frequency converter mounted inside the enclosure, with wiring running out to the equipment.
  • The ABB ACS580 catalog
  • The ACS580-01 wall-mounted drive documents
  • The ACS580-01 hardware manual for frames R1 to R9
  • The quick installation guide and firmware manual
  • Drive Composer in the ABB Drive Composer software downloads
  • The ACS-AP-I/S assistant control panel documents and USB driver
  • The ABB ACS550 to ACS580 replacement guide (US)

In addition, the ABB Library lists an ABB Virtual Drive add-on for offline setup of ACS580 drives.

Frequently asked questions

What is the ABB ACS580?

It is ABB’s general purpose AC drive family, rated 0.75 to 500 kW. It is built for pumps, fans, conveyors, compressors and similar loads. In particular, the wall-mounted version is the ACS580-01.

What does ACS580-01 mean?

The -01 is the wall-mounted variant, in frames R1 to R9. It is IP21 / UL Type 1 as standard and IP55 / UL Type 12 with the +B056 option. In addition, the other variants are -04 (module), -07 (cabinet-built) and -0P (packaged with a disconnect).

What does +B056 mean on a part number?

+B056 is ABB’s option code for the IP55 (UL / NEMA Type 12) enclosure. Without it, however, the ACS580-01 is IP21 (UL / NEMA Type 1).

What is the difference between the ACS580 and the ACS880?

The ACS580 is the general purpose drive for variable-torque and standard industrial loads. In contrast, the ACS880 is the industrial platform, with features such as regenerative options, an embedded PLC and higher power. Before choosing, check ABB’s catalogs.

How do I configure the drive?

Use the standard assistant control panel and its primary settings and start-up assistants. For PC-based setup, connect to the panel’s USB port with the free Drive Composer entry tool. In addition, Drive Composer pro adds more features.

Does it come with a control panel?

Yes. The ACS-AP-S assistant control panel is included as standard. Also, a Bluetooth panel (+J429) is an option.

The ABB ACS580 covers most pump, fan and conveyor jobs, and the part number tells you the voltage, current and enclosure. First, match the drive to the motor nameplate, then pick Type 1 or +B056 for the room it will live in. If you need help choosing, want a quote, or have a drive that needs repair, contact Precision Electric or browse our ACS580-01 drives.