Drives Repair Guide: Diagnose Faults, Repair or Replace
Drives repair starts the moment a VFD, inverter or DC drive trips and your line stops. This guide takes you from the first fault code to a running drive. You will learn how to isolate the drive safely, read the fault, find the likely cause, choose between repair and replacement, and prevent the next failure.
On this page
- What drives repair covers: AC, DC, frequency drives and inverters
- Safety first: isolate and verify before you touch a drive
- Repair or replace: how to decide
- Why drives fail: causes, symptoms and first checks
- What are the most common reasons a drive fails?
- Heat, fans and dirty heatsinks: why does my drive trip on overtemperature?
- DC bus capacitors: how long do they last, and when should they be replaced?
- Power section failures: rectifier, IGBTs and gate drives
- Overvoltage and regeneration: why does my drive trip on overvoltage when it decelerates?
- Loose connections and control wiring: can loose wires cause erratic drive behavior?
- Control board, power supply and parameter problems
- The drives repair process step by step
- Frequency drive repair: how AC drives repair works
- DC drives repair: thyristor converters and the SIMOREG 6RA70
- Siemens drive repair: SINAMICS, MICROMASTER and SIMOREG
- Preventive maintenance that avoids drives repair
- How to get a drive repaired: what to send and what to expect
- Common drives repair mistakes
- When to call a repair shop or field service
- Frequently asked questions
What drives repair covers: AC, DC, frequency drives and inverters
What is drives repair, and which drives does it cover?
Drives repair means finding and fixing faults in the electronic drives that control motor speed and torque. People use many names for these drives. A VFD (variable frequency drive), frequency drive, inverter, adjustable speed drive and AC drive all describe the same kind of device. Older documents sometimes write it as A.C. drive.
So VFD repair, inverter repair, variable speed drive repair and adjustable frequency drive repair all name the same job. In addition, drives repair covers DC drives, which run DC motors and use a different power section.
What is the difference between AC and DC drive repair?
An AC drive first rectifies incoming AC power into DC. That DC sits on the DC bus, a bank of capacitors that stores energy. Then the inverter section switches the DC back into AC at the frequency and voltage the motor needs. As a result, AC drive repair focuses on the rectifier, bus capacitors, IGBTs (fast power transistors) and control boards.
A DC drive works differently. It uses SCRs, also called thyristors, to turn AC directly into controlled DC. The drive feeds two motor circuits: the armature, which makes torque, and the field, which builds the magnetic field. So DC drives repair centers on thyristor modules, firing boards, fuses, field supplies and feedback devices.
Can one shop handle AC & DC drive repair?
Yes. One shop and one process can handle AC & DC drive repair, as long as the technicians know where each type tends to fail. The safety steps, bench tests and run tests follow the same logic for both. For a deeper look, see our post on AC and DC drive repair.
What a drives repair job includes
A full drives repair looks at more than the one part that failed. A typical job covers these areas:
- Power section: input rectifier, DC bus, IGBTs or thyristors, and gate drive boards
- Control board and keypad: the logic, display and communication parts
- Internal control power supply: the circuit that powers the boards and display
- Cooling: fans, heatsinks and filters
- DC bus capacitors: testing and replacement when worn
- Firmware and parameters: backup, update and restore
Also, a good shop checks the motor, cable and application. Many drive faults start outside the drive, so a repair that ignores them can fail again.
Safety first: isolate and verify before you touch a drive
Safe drives repair starts before any cover comes off. Rockwell states that only qualified people who know adjustable frequency AC drives and the connected machinery should install, start up or maintain them. If you are not trained for high-energy work, stop here and call a qualified person. Next, lock out and tag out every AC and DC source per NFPA 70E, as the PowerFlex 750-Series safety manual directs.

How long do I wait before working on a drive after power is off?
The DC bus capacitors stay charged after you remove power. Because the wait depends on the drive, use the discharge time printed on your drive’s own warning label. For example, Rockwell’s PowerFlex 750-Series service documents say to wait 5 minutes. Siemens G120C instructions say to wait until the time on the warning labels has passed.
However, no single wait time fits every drive. Never treat a dark keypad as proof of safety. The bus can still hold hazardous voltage after the display goes out.
Do larger frames and other brands need a longer wait?
Yes, they can. Rockwell says to wait 15 minutes, not 5, on PowerFlex 750 frame 8 to 15 regenerative units. Larger drives hold more stored energy, so their labels often list longer times. This table shows how to find the right time.
| Drive | Wait time |
|---|---|
| PowerFlex 750-Series, standard service documents | 5 minutes |
| PowerFlex 750 frames 8 to 15, regenerative units | 15 minutes |
| Siemens G120C | Time on the warning label |
| ABB, Eaton, Yaskawa, Danfoss and others | Time on the warning label and in the manual; it can change with drive size |
Because times differ by frame size, read the label on the exact drive in front of you. Then confirm zero volts with a meter anyway.
How do I check that the DC bus is discharged?
After the wait, measure the bus with a meter rated for the DC bus voltage. On a 480 V drive, the bus runs at several hundred volts DC, so a low-rated meter is not safe. The PowerFlex 750-Series user manual lists three checks at the power terminal block:
- Between +DC and -DC
- From +DC to chassis
- Last, from -DC to chassis
All three readings must be zero. Some PowerFlex 750 power modules also have DC+ and DC- test-point sockets on the front for this check. In addition, Siemens G120C instructions say to confirm no voltage between any power connections, and between power connections and the protective earth conductor.
What arc-flash and PPE rules apply to working on a drive?
Arc-flash rules come from NFPA 70E. The goal is an electrically safe work condition, which means isolating, locking out and proving zero volts. Checking for zero volts is itself a risk, because you are near parts that could still be live. So wear the PPE that your facility’s risk assessment calls for.
No single PPE category fits every drive. Incident energy depends on the supply, the protective device and the working distance. Use the arc-flash label on the equipment or your site’s incident energy study. NFPA 70E groups PPE into categories 1 to 4, with minimum arc ratings of 4, 8, 25 and 40 cal/cm². Never work on energized parts without an energized work permit and a trained person.
Other hazards to control
- Static: Rockwell warns that drive boards are ESD-sensitive, meaning static can damage them. Use a grounded wrist strap and static-safe bags.
- Cable shields: Siemens warns that unconnected shields can carry hazardous touch voltage through capacitive coupling. Connect shields and unused conductors, such as brake cores, to grounded housing at one end at least.
- Moving motors: A spinning motor can feed voltage back into the drive. Make sure the motor cannot move.
- Other sources: Look for external control power, bypass circuits and shared DC bus links.
Repair or replace: how to decide
The repair-or-replace choice is the first big decision in drives repair. No single rule fits every case. Instead, weigh the factors in this table against your own line.
| Factor | Leans toward repair | Leans toward replace |
|---|---|---|
| Age and obsolescence | Current model with parts available | Discontinued model with scarce parts |
| Like-for-like replacement | No direct replacement; a new drive means rewiring or reprogramming | A drop-in replacement exists |
| Extent of damage | Fan, capacitor, power supply or control board fault | Severe power section damage across many parts |
| Downtime cost | Repair time fits your schedule, or you have a spare or loaner | Line is down now with no spare |
| Legacy setup | Machine built around this drive and its settings | Upgrade already planned and budgeted |
| Repeat failures | First failure with a clear cause | Same drive fails again and again |
Should I repair or replace a failed drive?
Start with a diagnosis. When our technicians find a short in the power section on the bench, they take the drive apart, find the cause and quote the repair. If the repair costs too much, we offer a replacement instead. That way, you decide with real numbers for your drive.
Is there a rule of thumb for when repair costs too much?
Many buyers use a simple rule. If the repair quote nears half the price of a comparable new drive, start to lean toward replacement. This is only a guide, not a fixed rule. Also count downtime, rewiring, reprogramming and whether the old drive is obsolete. Then compare both options on total cost, not just the quote.
Keep a spare for critical drives
Many plants keep spare drives or modules for critical lines. A spare lets you swap and restart while the failed unit goes out for drives repair. As a result, repair time stops setting your downtime.
Why drives fail: causes, symptoms and first checks
A drive fault is not always a drive failure. In fact, many calls for drives repair start with a trip caused somewhere else. So check these four things before you pull the drive:

- The fault code and fault history
- The input power: all phases present and at the right voltage
- The motor and motor cable
- The control wiring and speed reference
What are the most common reasons a drive fails?
The most common causes are heat, aging DC bus capacitors, power section damage from shorts and ground faults, and regeneration on fast stops. Loose connections and control power problems round out the list. The sections below cover each one with its symptoms and first checks.
Heat, fans and dirty heatsinks: why does my drive trip on overtemperature?
Heat is a leading cause of drives repair. A failed fan, a clogged filter or a hot cabinet raises the drive’s internal temperature. That extra heat also ages the capacitors faster.
For example, Siemens lists these causes for G120 fault F00004, inverter overtemperature:
- Inverter overloaded
- Ventilation inadequate
- Pulse frequency too high
- Ambient temperature too high
- Fan not working
So check the load cycle, clean the filters and confirm the fan spins. Siemens also says to check that the motor power in p0307 matches the inverter power in r0206.
Fan life is hard to pin down. Third-party sources quote anything from 3 to 5 years up to 50,000 to 100,000 hours. Because these figures conflict, use the replacement interval in your drive’s manual.
DC bus capacitors: how long do they last, and when should they be replaced?
Capacitors show up often in VFD repair. The electrolytic capacitors on the DC bus lose capacitance and gain internal resistance, called ESR, as they age. As a result, bus ripple rises and the power devices work harder. Wear often gives no warning during normal running, so a drive can seem fine until it trips.
Third-party guides say capacitor life roughly halves for every 10 °C above its rated temperature. They quote replacement intervals from about 5 to 7 years up to 10 to 12 years. So follow the manufacturer’s guidance and factor in how hot your drive actually runs. Watch for these signs of worn capacitors:
- DC bus or undervoltage trips under load
- Blown input fuses
- Display flicker
- Bulging tops, leaking electrolyte or discoloration
One capacitor supplier’s guide treats capacitance below 80% of rated, or ESR above twice nominal, as end of life. Replacement parts must match the original capacitance, voltage rating and ESR class. Also, a drive stored for a long time may need its capacitors reformed at reduced voltage. Voltage steps and hold times differ by maker, so follow the method in your drive’s manual or ask the maker.
Power section failures: rectifier, IGBTs and gate drives
Power section shorts show up as overcurrent or short-circuit trips, blown fuses or ground faults. Often the root cause sits in the motor or cable, such as a shorted winding or damaged insulation.
Because applying power to a shorted section causes more damage, our technicians test the input and output power sections with a meter first. These diode and IGBT tests run with the drive dead. If they find a short, the drive comes apart for diagnosis.
Before you reconnect a repaired drive, insulation-test (megger) or inspect the motor and cable. Otherwise, the same fault can destroy the repaired drive.
Overvoltage and regeneration: why does my drive trip on overvoltage when it decelerates?
When a motor slows down fast, it acts like a generator. Energy flows back into the DC bus and raises its voltage. Siemens G120 fault documentation names two causes: fast ramp-downs and a motor driven by an active load, such as a lowering hoist.
So the fix is often a setup change, not a hardware repair. Siemens advises longer ramp times for high-inertia loads, or a braking resistor if you cannot lengthen the ramp. Check the deceleration time and braking settings before you send the drive out for drives repair.
Loose connections and control wiring: can loose wires cause erratic drive behavior?
Yes. Heat cycles and vibration loosen terminals over time. A bad connection can arc, and arcing leads to nuisance faults and damage.
In our experience, arcing at the input can cause nuisance overvoltage faults, blown input fuses or damaged protective parts. At the output, it can cause overcurrent faults or damage the power components. Loose start/stop wires can make the drive start and stop on its own. A loose speed reference wire can make the speed swing, which risks scrap, machine damage or injury.
ABB lists “verify tightness of connections” in its NFPA 70B-based preventive maintenance scope. Torque terminals to the maker’s spec. In our experience, reusing torque hardware or tightening an already tight connection can ruin it.
Control board, power supply and parameter problems
A drive with no display usually has a failed internal control power supply. Finding that fault takes disassembly and diagnosis on the bench.
Software faults are another source. For example, Siemens G120 fault F01000 is an internal software error that needs a POWER ON to clear. The list manual’s remedies include reading the fault buffer (r0945), a POWER ON for all components, a firmware upgrade, a call to the Siemens hotline, or replacing the Control Unit.
Corrupt or mismatched parameter files also cause faults. So back up the parameters before any reset or firmware change during drives repair.
The drives repair process step by step
Here is the sequence our shop follows on every drives repair. Each step builds on the last, so a drive never gets full power before it passes the earlier tests.
- Intake: Record the nameplate, fault history and application details.
- Visual check: Inspect for heat damage, debris, swollen capacitors and loose connections.
- Dead tests: Meter-test the input and output power sections with no power applied.
- Short repair: If a short shows up, disassemble the drive, find the cause and quote the repair.
- Slow power-up: Raise the input voltage gradually to rated level while checking current and output frequency.
- Control power check: If the display stays dark, diagnose the internal control power supply.
- Run test: Back up the parameters, reset to defaults and run a jog test with a template program. Use closed loop if the drive has an encoder.
- Final test: Run a motor or load test and confirm output voltage and current.
How are drives tested on the bench before power is applied?
Every drives repair at our shop starts with meter tests on the input rectifier and the output IGBTs. These checks find shorted or open devices while the drive is dead. If the readings look healthy, the technician powers up slowly and watches the current. This slow start limits damage if a hidden fault remains.
How do I meter-test the rectifier and IGBTs?
First, isolate the drive, confirm zero bus voltage and disconnect the input and motor wires. Then set your meter to diode test. Each rectifier and IGBT output leg has a diode path you can read, as in the steps below.
- Put the red lead on +DC and the black lead on each input terminal (R, S, T). Expect a forward drop, often around 0.3 to 0.7 V.
- Reverse the leads. Expect an open reading, shown as OL.
- Put the black lead on -DC and the red lead on each input terminal. Expect a similar forward drop.
- Repeat the same checks on the output terminals (U, V, W) against +DC and -DC.
Now compare the readings. All three phases should match closely. A device reading near 0 V in both directions is shorted. A device reading OL in both directions is open. Exact numbers vary by drive, so use your drive’s service manual if you have it.
However, a meter cannot fully prove an IGBT. It checks the diode path, not the gate or switching. So passing these tests only clears the drive for the next steps, like a slow power-up.
What does a motor run test show?
The run test proves the drive can turn a motor under control. The best backup method depends on the brand, so our technicians back up the stored program first. Then they reset to factory defaults through the keypad and set up a basic start, stop and jog application. If the motor will not run, they check the output voltages and currents going to the motor.
How do I back up and restore drive parameters?
The tool depends on the brand. For Rockwell drives, upload the parameters to a file with DriveExecutive or Connected Components Workbench, depending on the drive family. For ABB, use the control panel to copy parameters, or use ABB’s PC tool such as DriveWindow on older drives. Siemens drives can use the operator panel, a memory card or STARTER.
After a repair, restore the file and check that it loaded without errors. Also compare the firmware version and any option cards with the original drive. A different firmware version or an unrecognized option card can cause faults or stop a file from loading. Check the maker’s manual for compatibility before you restore.
What happens if the drive tests good but the machine still faults?
Sometimes the drive passes every bench test. In that case, the cause likely sits elsewhere: PLC communications, faulty I/O, bad wiring or bad cabling. Next, we talk with you about the application to narrow it down. No single method fits this step, because every machine is different.
When is a field service technician needed?
If the drive tests good and you cannot find the fault elsewhere on the machine, a field service technician can come on site. A trained tech troubleshoots the drive, PLC and the rest of the control system. The goal is to find the cause and a fix as fast as possible.
Frequency drive repair: how AC drives repair works
Is frequency drive repair the same as VFD or inverter repair?
Yes. Frequency drive repair, VFD repair and inverter repair all name the same job on the same kind of drive. The process stays the same for each: safe isolation, power section tests, bench power-up and a motor run test.
What is A.C. drive repair and how does it work?
A.C. drive repair, usually written AC drive repair, means fixing the four main sections of a VFD. First, the rectifier turns AC into DC. Next, the DC bus stores that energy in capacitors. Then the inverter switches the DC into variable-frequency AC for the motor. Finally, the control section runs the logic, keypad and communications.
Each section has typical failures, so the symptom tells you where to look first. Use this table as a starting point.
| Symptom | Likely section or cause | First check |
|---|---|---|
| Overcurrent at start | Output stage, motor or cable | Insulation-test motor and cable; check acceleration time |
| Overvoltage on decel | Regeneration onto the DC bus | Deceleration time; braking resistor |
| Undervoltage | Input power or bus capacitors | Measure all incoming phases; inspect capacitors |
| Overtemperature | Fans, filters, heatsink, ambient | Clean filters; confirm fan runs; check cabinet temperature |
| Ground fault | Motor or cable insulation | Insulation test with the drive disconnected |
| Blown input fuses | Rectifier, bus capacitors or input wiring | Meter-test the rectifier with power off |
| No display | Internal control power supply | Bench diagnosis |
Check the supply side too
The power feeding the drive matters as much as the drive itself. For example, the Siemens CU240 getting-started document requires a supply short-circuit ratio of at least 100. That ratio compares the strength of the supply with the size of the drive. Also, phase loss, low voltage or poor upstream connections can make a healthy drive trip.
What do common fault codes mean on other brands?
Most brands use similar faults with different codes. This table shows common examples. Codes and wording vary by model and firmware, so confirm each one in your drive’s fault list.
| Fault | Rockwell PowerFlex 750 | ABB (ACS880) | Yaskawa | Danfoss VLT |
|---|---|---|---|---|
| Overcurrent | F12 HW OverCurrent | 2310 | oC | Alarm 13 |
| Ground fault | F13 Ground Fault | 2330 earth leakage | GF | Alarm 14 |
| DC bus overvoltage | F5 OverVoltage | 3210 | ov | Alarm 7 |
| DC bus undervoltage | F4 UnderVoltage | 3220 | Uv1 | Alarm 8 |
| Overtemperature | Check the fault list for your frame | Check the fault list | oH | Alarm 29 |
For Eaton drives and for other faults, look up the code in the maker’s manual for your exact model. In every case, the cause is the same as the Siemens examples above: check the motor, cable, input power, ramp times and cooling first.
Brand-specific guides
For details on single brands, see our guides on Rockwell PowerFlex, ABB, Eaton and AC Tech drives repair. Each one covers that maker’s faults and service quirks. You can find Rockwell manuals in the Rockwell Automation Literature Library, including the PowerFlex 750-Series spare parts and service installation instructions.
DC drives repair: thyristor converters and the SIMOREG 6RA70
DC drives have SCR or thyristor power sections and firing boards that time the thyristors. They also have separate armature and field supplies, feedback devices, contactors and fuses. The safety rule stays the same. Siemens SIMOREG 6RA70 instructions say to disconnect and lock out the AC supply before visual checks or maintenance, because both the converter and the motor carry hazardous voltage until then.

How is a DC drive repaired, and what do I check on a SIMOREG 6RA70?
The SIMOREG DC-MASTER 6RA70 makes a good example. Its operating instructions cover converters from 6 kW to 2500 kW. The maintenance chapter covers software updates and replacement of fans and PCBs. It also covers thyristor module replacement on converters up to 1200 A, and fuse and thyristor assembly replacement on larger units.
You can download the SIMOREG DC-MASTER 6RA70 Operating Instructions from Siemens Industry Online Support. Then the repair follows the same pattern as an AC drive: isolate, test the power section dead, power up with care and run the motor. The same manual lists the 6RA70 fault codes and their causes, so look up each code there.
How do I test SCRs and firing boards?
First, isolate the drive, lock it out and disconnect the thyristor leads or busbars so nothing else affects the reading. Then check each SCR with your meter.
- Anode to cathode: A good SCR reads open in both directions. A reading near zero means a shorted device.
- Gate to cathode: A good SCR usually shows a low resistance, often tens of ohms. An open reading means a damaged gate.
- Firing board: Check the gate leads, connectors and pulse transformer wiring. Look for burned parts or cracked solder joints.
Because values vary by module, compare all the SCRs in the same bridge. One that reads very differently is the suspect. Replace thyristors as a set when the maker advises it.
How do I diagnose a lost field?
A lost field can make a DC motor lose torque or run away, so treat it as serious. With power off, check the field fuses first. Next, measure field winding resistance and look for an open circuit. Then, with power on and safe working practice, confirm the field supply outputs the expected voltage. Finally, check the field-loss setting in the drive, since most drives trip on low field current to protect the motor.
How do I find a tach or encoder fault?
Speed feedback faults cause overspeed trips, speed swings or a motor that will not hold speed. For a tachometer, check the wiring, the polarity and that its voltage rises steadily with speed. For an encoder, check its supply voltage, the signal wiring and the shield connection. Then compare the feedback reading with the actual motor speed. A mismatch points to a bad feedback device or loose wiring.
Check the motor and feedback before blaming the drive
Many DC drive faults start in the motor or its feedback. So check these first:
- Motor brushes and commutator for wear, sparking or burn marks
- Field supply and field winding
- Tachometer or encoder feedback and its wiring
- Armature wiring and connections
Repair like-for-like or move to an AC drive?
Some plants repair a DC drive like-for-like because the motor, machine and controls were built around it. Others move to an AC drive and motor when parts get scarce or the machine needs an upgrade anyway. Both are valid options. So talk through the motor, the load and your downtime window with your repair shop.
Siemens drive repair: SINAMICS, MICROMASTER and SIMOREG
Siemens drive repair follows the same process as any other drives repair, with a few Siemens-specific tools. Some people search for seimens drive repair, a common misspelling, but the job is the same. Our shop works on SINAMICS drives such as the G120 and G120C. We also work on older MICROMASTER drives and SIMOREG DC Master drives.
How does Siemens drive repair work?
First, isolate the drive using the steps in its manual. The SINAMICS G120C Operating Instructions say to wait for the labelled discharge time and check for no voltage between power connections and protective earth. They also say to make sure the motor cannot move. For the G120 with CU240E/CU240S, the getting-started document says to wait at least 5 minutes. Then read the fault, test the power section and follow the bench process above.
Where do I find Siemens fault codes and how do I read them?
On a G120 Control Unit, a fault shuts down the inverter and lights the SF LED. The drive will not restart until you fix the cause. You can read the fault number on the operator panel, in STARTER software or on a higher-level controller. These parameters hold the details:
- r0947: the fault code number
- r0945: the fault buffer
- r0949: the fault value
Many faults need an acknowledgment, and some need a POWER ON. Look up each code in the list manual for your own Control Unit, such as the SINAMICS G120 CU240B/E-2 List Manual. You can download these manuals from Siemens Industry Online Support. Meanings can differ between Control Units, so do not rely on a list from another model.
Common Siemens faults and what the list manual says
| Fault | Causes from the Siemens list | Remedies from the Siemens list |
|---|---|---|
| F00004 inverter overtemperature | Overload, poor ventilation, high pulse frequency, high ambient temperature, fan not working | Check load cycle and fan; confirm motor power (p0307) matches inverter power (r0206) |
| Overvoltage on deceleration | Fast ramp-down or a motor driven by an active load | Longer ramp times for high-inertia loads, or a braking resistor |
| F01000 internal software error | Internal software fault | Read fault buffer (r0945), POWER ON, firmware upgrade, call the hotline, replace the Control Unit |
How do I reset a Siemens drive to factory settings, and what should I back up first?
On G120 drives with the CU240 Control Unit, the getting-started document gives the reset as P0010 = 30, then P0970 = 1. Other Siemens families use different steps, so confirm the sequence in your own manual. Before any reset, back up the parameters to the operator panel, a memory card or STARTER. Otherwise, the reset wipes your application settings and the machine will not run until you rebuild them.
Preventive maintenance that avoids drives repair
Good maintenance cuts the need for drives repair and shortens the repairs you still need. It also lowers repair cost, because worn fans and capacitors get replaced before they take out the power section.

What preventive maintenance reduces drive repairs, and what does NFPA 70B say?
NFPA 70B became the Standard for Electrical Equipment Maintenance with an effective date of January 16, 2023, set by the NFPA Standards Council. Before that, it was only a recommended practice. It covers preventive maintenance for electrical, electronic and communication systems in industrial plants and other buildings. It also forms part of the electrical safety cycle with NFPA 70 and NFPA 70E.
However, NFPA 70B does not replace manufacturer instructions. So start with the PM tasks in your drive’s manual, then build your 70B program around them. The ESFI overview of NFPA 70B gives a plain summary if you are new to the standard.
Example maintenance intervals by equipment condition
Eaton’s white paper on 2023 NFPA 70B lists example intervals by equipment condition. Equipment in Condition 1 is in the best shape, and Condition 3 is the worst.
| Task | Best (Condition 1) | Middle (Condition 2) | Worst (Condition 3) |
|---|---|---|---|
| Infrared thermography, all equipment | 12 months | 12 months | 6 months |
| Motor control equipment, visual inspection | 60 months | 36 months | 12 months |
These are examples, not fixed rules for drives. Your scope depends on the condition of your equipment and the maker’s instructions. Also, ABB’s NFPA 70B preventive maintenance services document lists connection tightness checks and a drives PM service.
A practical drive PM checklist
- Clean heatsinks and replace or wash filters
- Check that every fan spins freely and moves air
- Torque power and control terminals to the maker’s spec
- Look for bulging, leaking or discolored capacitors
- Trend DC bus voltage and ripple if the drive logs them
- Take thermal images under load
- Keep the cabinet cool, clean and dry
- Record drive running hours for fan and capacitor planning
Store spare drives correctly
Keep spares for critical drives, and store them clean, dry and within the maker’s temperature range. Because capacitors age on the shelf, check the manual for reforming steps before you install a long-stored spare.
How to get a drive repaired: what to send and what to expect
What should I send to a drive repair shop?
Good information speeds up diagnosis. Send these items with the drive:
- Full nameplate data and catalog number
- Firmware version and any option cards
- The fault code and fault history
- What happened just before the failure
- A parameter backup, if the drive can still communicate
- Application details: motor data, load type and control method
How much does drives repair cost and how long does it take?
Cost and turnaround depend on the drive model, its size, the damage and parts supply. For example, a fan or capacitor job differs a lot from a burned power section. We do not post set price ranges, because a fair number needs a look at your drive. So the shop evaluates the drive first, then quotes the cost and lead time for your unit.
What to expect after you send the drive
- Evaluation and diagnosis of the cause
- A quote with cost and lead time
- A repair, or a replacement offer if repair costs too much
- Bench and motor run testing
- Return with the shop’s warranty; ask about terms when you get your quote
Packing and shipping tips
- Remove loose option cards if the shop advises it
- Pack boards and the drive in static-safe bags
- Use firm padding so the drive cannot shift in the box
- Tag the drive with the fault code and your contact details
For details on shipping drives to us from anywhere in the country, see our nationwide drive repair post and our brand pages.
Common drives repair mistakes
These mistakes cause injuries, extra damage or repeat failures. Avoid them on every job.

- Opening the drive before you verify zero volts on the DC bus
- Re-applying power to a drive that has a short
- Resetting to factory defaults without a parameter backup
- Installing a capacitor with the wrong voltage rating or class
- Over-tightening connections or reusing hardware the maker says to replace
- Ignoring the motor, cable, ramp times and load as causes of repeat faults
- Treating every trip as a drive problem when the cause is a loose wire, PLC communications or I/O
When to call a repair shop or field service
When should I call a repair shop or a field service technician?
Call a shop for drives repair when you see any of these triggers:
- A shorted power section
- Repeated trips after you have checked power, motor, cable and wiring
- No display
- An obsolete drive or one with no manual
- No one on site qualified for high-energy work
If the drive tests good on the bench, the next step is application-level troubleshooting. In that case, a field service visit often finds the cause faster than more bench time.
Frequently asked questions
How long should I wait before opening a drive after removing power?
Use the discharge time on the drive’s own warning label. For example, Rockwell’s PowerFlex 750-Series documents specify 5 minutes, and 15 minutes for frame 8 to 15 regenerative units. Then measure the DC bus with a correctly rated meter and confirm zero volts before you touch anything.
Is frequency drive repair the same as VFD or inverter repair?
Yes. Frequency drive, VFD, AC drive and inverter all describe an electronic drive that controls AC motor speed. The repair process is the same: safe isolation, power section tests, bench power-up and a motor run test.
Can the same shop repair both AC and DC drives?
Yes, but the failure points differ. AC drives mostly fail in the DC bus capacitors, fans, IGBT power stage and control power supply. DC drives, such as the Siemens SIMOREG 6RA70, have thyristor modules, fuses, PCBs and fans to replace.
Where do I find fault codes for a Siemens drive?
Siemens fault numbers show on the operator panel or in STARTER. On the G120, parameter r0947 holds the fault code number and r0945 holds the fault buffer. The Siemens list manual for your Control Unit gives the cause and remedy for each fault. You can download the manuals from Siemens Industry Online Support.
Should I repair or replace a failed drive?
It depends on the damage, the drive’s age, parts supply, downtime cost and whether a like-for-like replacement exists. A shop diagnoses the cause and quotes the repair. If the repair costs too much, the shop offers a replacement.
Safe, lasting drives repair comes down to a few habits: isolate and verify zero volts, read the fault, test the power section dead, and check the motor and application. Good preventive maintenance then keeps the next failure away. Contact Precision Electric for help with a faulting drive, or for a repair or replacement quote.