ABB Industrial Connections & Solutions: Meaning and Drive Wiring
If you searched for ABB industrial connections & solutions, you probably need to make the electrical connections on an ABB product. This guide clears up the name first. Then it walks you through wiring the ABB drives we stock, the ACS255 and ACS180, with safety steps, checks after each stage and common mistakes.
On this page
- What “ABB Industrial Connections & Solutions” means and where drives fit
- What you need before making ABB industrial connections
- Safety first for ABB industrial connections: isolate, lock out and prove dead
- Step 1: Mount the drive and prepare the enclosure
- Step 2: Ground the drive and plan cable routing
- Step 3: Connect the input power cable
- Step 4: Connect the motor cable (and brake resistor if used)
- Step 5: Wire the control terminals
- Step 6: Final checks, power-up and first run
- Common mistakes in ABB industrial connections
- When to call for ABB industrial connections repair or help
- Where to find ABB manuals and parts for ABB industrial connections
- Frequently asked questions
What “ABB Industrial Connections & Solutions” means and where drives fit
What is ABB Industrial Connections & Solutions?
Industrial Connections & Solutions LLC is a US subsidiary of ABB. Its short name is Industrial C&S LLC. In addition, ABB’s US privacy filing lists the company as a covered entity next to ABB Inc. and ABB Installation Products Inc.
The name also shows up as an ordering and vendor entity. ABB’s OEM transition guide says some products moved to the Industrial Connections & Solutions “empower” platform, and customers set up Industrial Connections & Solutions LLC as a vendor. This tied to the integration of GE Industrial Solutions into ABB’s Electrification Products division.
A Tennessee economic development announcement says the company’s McNairy County facility makes and distributes busway and bus plug systems, among other electrical products. So think switchgear, busway and similar products when you see ABB industrial connections & solutions on a quote or an order.
Is ABB Industrial Connections & Solutions the same as ABB Drives?
No. The name refers to a legal and ordering entity, not a drive series. Drives such as the ACS255 and ACS180 are documented in ABB’s drives manual library, not in switchgear catalogs. We found nothing saying that ABB Industrial Connections & Solutions LLC makes or sells these drives.
For drive connections, use the drive’s own user’s manual or hardware manual. Also read the type code on the drive label before you use any wiring data. For example, ACS255-01U-02A3-1+B063 is a 0.5 hp, 2.3 A drive for 1-phase 110-115 V input.
What you need before making ABB industrial connections
What do I need before making ABB industrial connections on a drive?
First, gather your documents. Next, collect parts and tools. Then confirm the supply matches the drive.

- Documents: the drive’s manual, the motor nameplate, the site electrical drawings and your local code requirements.
- Parts: input fuses or a breaker, shielded motor cable, cable glands or conduit fittings, ring or ferrule terminals, and a brake resistor if you need one.
- Tools: a torque screwdriver that reads small values, a voltage tester, a multimeter, wire strippers, and a drill and hole saw or punch for gland holes.
Do not size fuses, breakers or cables from memory. Instead, use the fuse and cable table in the manual for your exact type code, and follow your local code.
Which input voltage and phase does the drive need?
Check input voltage and phase before you buy parts. Our 0.5 hp ACS255 range covers 110-120 V 1-phase, 208-240 V 1-phase or 3-phase, and 400-480 V 3-phase. As a result, the type code tells you which supply the drive accepts.
Where do I find fuse, cable and torque values for my exact drive?
Each manual lists these values by type code or frame. For the ACS255, find your type code, such as the 0.5 hp 115 V unit, in the fuse and cable table of the user’s manual that matches your voltage. For the ACS180, look up your frame, R1 to R4, in the hardware manual. It gives terminal torque, wire sizes and input fuse ratings for each frame.
We do not list those numbers here. They change by frame, type code and local code, so a copied value can be wrong for your drive. If you cannot find your type code in the table, contact us with the label details.
Safety first for ABB industrial connections: isolate, lock out and prove dead
What safety steps come before ABB industrial connections?
Lock out the supply and wait for the drive to discharge before you open it. Dangerous voltage can stay at L1, L2, L3, U, V, W, + and BR even when the motor is stopped. Externally supplied control circuits can also stay live when mains is off, so do not work on control cables while any power is applied.
Never connect mains power to the output terminals U, V, W. Also make sure the system is grounded before you apply power. Finally, do not enable automatic fault reset where a restart could be dangerous.
How do I prove a drive is de-energized?
Follow the ACS180 check, which works well for any drive:
- First, test your tester on a known live source.
- Next, check for zero voltage between input terminals L1, L2, L3 and PE.
- Then measure zero voltage between output terminals T1/U, T2/V, T3/W and PE.
- After that, verify zero voltage between DC terminals UDC+ and UDC- and PE.
- Finally, test your tester on the known source again.
Step 1: Mount the drive and prepare the enclosure
How much clearance does an ACS255 IP66 drive need?
Leave 7.87 in (200 mm) above and below the drive. Leave 0.39 in (10 mm) at each side. You can mount drives side by side with 0 spacing between them.

Also check the enclosure rating. The ACS255 is IP20 or IP66, depending on the model. IP20 units must go in a suitable enclosure.
The type-code suffix B063 means IP66 indoor, and B068 means IP66 outdoor. However, the same manual says the drives are intended for indoor use only. As a result, confirm outdoor mounting conditions with ABB before you install a B068 drive in the weather.
Is the ACS255 +B063 version still available?
ABB announced that +B068 replaces +B063 as the standard IP66 ACS255. So if you are replacing a +B063 drive, ask us about the +B068 version. Confirm availability with us before you plan the job, because it can change.
Also compare the manual and the label on the new drive with your old one. The type code suffix is part of what you match.
What gland or hole size does an ACS255 frame 1 need?
The frame 1 moulded hole is 0.866 in (22 mm) and fits a PG13.5 or M20 gland. Frame 2 and 3 holes are 1.11 in (28.2 mm) for PG21 or M25 glands. A frame 1 drilled hole for flexible conduit is 1.125 in (28 mm).
Check after this stage: the drive is secure, the clearances are kept, the seals are intact and the glands match the holes. A wrong gland defeats the IP66/NEMA 4X rating.
Step 2: Ground the drive and plan cable routing
How should I ground an ABB drive?
Connect the ground terminal of each drive individually and directly to the site ground bus bar. Do not loop ground connections from one drive to another or to other equipment.
On the ACS180, IEC/EN 61800-5-1 requires two PE conductors for a fixed connection if the grounding conductor is under 10 mm2 Cu or 16 mm2 Al. In addition, the cable shield can serve as the second conductor.
When should I remove the ACS180 EMC screw or VAR screw?
The EMC screw connects the internal EMC filter to ground. The VAR screw connects the surge varistor to ground. On supplies that are not solidly grounded, such as an IT (ungrounded) system or a corner-grounded delta, these screws can let ground current flow where it should not. In those cases, the hardware manual tells you to remove them.
For a TT supply, do not guess. Check the grounding-system table in the ACS180 hardware manual for your frame. Also confirm your supply type with the site electrician before you change either screw.
How far apart should power and control cables be in ABB industrial connections?
Route power and control cables separately, and do not run them in parallel. The ACS255 600 V manual says to keep control cabling at least 4 in from power cabling. Where the cables must cross, cross them at an angle as near to 90 degrees as possible.
Check after this stage: ground continuity is confirmed and the cable paths are planned.
Step 3: Connect the input power cable
How do I connect single-phase or three-phase input power?
First, fit the input fuses or breaker, plus any line choke or filter the manual recommends. Then wire the input.

- ACS255, 1-phase: connect L1/L and L2/N.
- ACS255, 3-phase: wire L1, L2, L3.
- ACS180: attach L1, L2, L3, ground the shield under the clamp and land each PE conductor on the PE terminal.
Input phase sequence does not matter on the ACS255. Instead, motor direction comes from the motor lead order or the drive’s reverse function.
What torque do ABB drive terminals need?
Torque depends on the manual for your variant. For ACS255 frame 1-3 IP66 (115-480 V) units, the maximum is 0.5 Nm (4.5 lb-in) on control terminals and 1 Nm (9 lb-in) on power terminals.
The ACS255 600 V manual lists different values, so do not mix them. For the ACS180, check the hardware manual for the torque values of your frame.
Check after this stage: no loose strands, terminals torqued, protective earth connected, and no voltage at the output terminals.
Step 4: Connect the motor cable (and brake resistor if used)
How do I connect the motor and the cable shield?
Use a shielded 3- or 4-core cable. ABB recommends a symmetrical shielded VFD cable for the ACS180 motor cable. Connect the leads to U, V, W (T1/U, T2/V, T3/W on the ACS180).
Next, terminate the screen at both ends. On an ACS255 IP66, connect it to the internal ground clamp, and use an EMC gland or clamp at the motor. On the ACS180, ground it at the drive clamp.
Also check the motor terminal box for star or delta. The setting must match the drive output voltage and the nameplate.
What is the maximum motor cable length?
The limit differs by drive, frame and EMC requirement. Use the maximum motor cable length in the manual for your type code. A longer cable can cause overcurrent trips and can break the EMC rating, so do not stretch the limit.
How do I connect a brake resistor to an ACS180?
Run a shielded brake resistor cable to R- and UDC+. Then tighten the R- and UDC+ screws even if no cables are connected.
How do I size a brake resistor?
You need a resistor with the right resistance and enough power rating. The resistance must not fall below the minimum the drive allows. The power rating depends on how much the load regenerates and how often it brakes.
Use the brake resistor data in the manual for your drive. If you cannot tell how much braking the load needs, send us the motor size and duty cycle and we will help you choose.
Check after this stage: motor wiring matches the nameplate and shield terminations are made. Run an insulation test only as ABB’s instructions describe, with the drive disconnected.
Step 5: Wire the control terminals
How do I wire start/stop and a speed pot on an ACS255?
The ACS255 ships in factory default, set to terminal control. Connect a control switch between terminals 1 and 2. Keep the contact open, which leaves the drive disabled. Closing it enables the drive, and opening terminal 2 stops it.

For a speed pot, connect a pot of 1 kΩ minimum to 10 kΩ maximum between terminals 5 and 7. Put the wiper on terminal 6. Models with the +F278 option already have the pot, FWD-OFF-REV switch and disconnect built in.
The +24 V control output is rated 100 mA, and control terminals take a maximum of 0.5 Nm (4.5 lb-in) on the 115-480 V manual. In addition, parameter 1103 set to 1 allows keypad control in the forward direction only.
You can also add options. The optional REMOTE PANEL gets power through the RJ45 connection. Likewise, the relay output card plugs into the terminal connector with its row of 11 pins, and its second relay output is on terminals 8 and 9. Finally, make sure the terminals are tight.
Does the relay output card fit every ACS255 variant?
No. ABB says the RCRO-01 relay output card is not compatible with the +B058 NEMA 4X variant. Check the suffix on your type code before you order the card.
How is STO wired on the ACS255?
ABB’s catalog lists safe torque off (STO) as a 600 V-only feature on the ACS255. As a result, the 115-480 V variants do not have it. Do not plan a safety circuit around STO on those drives.
If you have a 600 V unit, wire STO exactly as the 600 V ACS255 user’s manual shows. Safety circuits need the exact terminals and checks from that manual, so we do not repeat them here.
What are the ACS180 default I/O connections and where is STO?
The ACS180 default I/O follows the ABB standard macro, so use the default I/O diagram in the hardware manual. For other macros, see the firmware manual 3AXD50000467860. Safe torque off (STO) is only on the ACS180-04S. In addition, the drive has an embedded EIA-485 fieldbus connection, and DI5 does not support NPN.
Also note that ACS180 drives sold in North America have a plastic EMC screw. A metal screw ships in the box to connect the internal EMC filter.
Check after this stage: use a meter to confirm the enable contact is open and the wiring matches the drawing.
Step 6: Final checks, power-up and first run
What should I check before the first power-up?
- First, refit the terminal covers and gland seals.
- Next, confirm no tools or wire strands remain inside.
- Then compare the supply voltage with the nameplate.
- Finally, apply power with the enable switch open.
After that, enter the motor nameplate data (voltage, current, frequency, speed) as the manual directs. Close the enable switch and run at low speed.
How do I check motor direction after wiring?
Watch the shaft as the motor starts. If it turns the wrong way, switch off and lock out the power. Then swap two motor leads, or use the drive’s reverse function instead.
What do first-power-up trips mean on the ACS255 and ACS180?
Look up the exact fault code in your manual. Meanwhile, these checks cover the most common trips. Always lock out the power before you touch any wiring.
- Ground fault: current is leaking to ground. Check the motor cable and motor for damaged insulation, wet glands and a shield touching a live lead. Disconnect the motor and try again to see if the drive or the motor is at fault.
- Short circuit: two outputs are touching, or a winding has failed. Check U, V, W for a short at the drive terminals, in the cable and at the motor. Also look for stray wire strands.
- Overcurrent: the motor draws more than the drive allows. Check that the nameplate data is right, the load is not jammed and the ramp time is not too short. Also check that the drive is sized for the motor.
If the trip returns with the motor disconnected, stop and call us. The drive may be damaged.
Check after this stage: no faults, motor current within the rating, and no strange heat, noise or smell.
Common mistakes in ABB industrial connections
What mistakes cause drive wiring problems?
- Connecting mains to U, V, W.
- Looping grounds, or ending shields with pigtails instead of the clamp.
- Running control and power cables in parallel or in the same cable.
- Using the wrong torque, or over-tightening small control terminals.
- Choosing the wrong gland or hole on an IP66 enclosure.
- Mounting an IP20 unit outside an enclosure.
- Mixing manuals, since the 115-480 V and 600 V ACS255 manuals have different torque values.
- Leaving the EMC or VAR screw in place on an ungrounded or corner-grounded supply.
- Treating Industrial Connections & Solutions product pages as drive documentation.
When to call for ABB industrial connections repair or help
When should I send a drive for repair?
Call us if the drive trips on a ground fault or short circuit at first power-up. Also call if you see damage, burnt terminals or a burnt smell, or if faults repeat after you verify the wiring.
In addition, ask for help if the type code on the label does not match the manual you have. Our repair shop can test and repair ABB drives.
Where to find ABB manuals and parts for ABB industrial connections
Where do I find the right manual for an ABB drive?
Go to ABB’s library and search for your drive. These are the documents for the drives in this guide:

- The ACS255 user’s manual for 0.5-10 hp, 115-480 V.
- For 600 V variants, a separate ACS255 user’s manual.
- A micro drives catalog covering the ACS255.
- Also, the ACS255 Remote Panel user guide and the relay output option card guide.
- Finally, the ACS180 hardware manual.
Where do I find ABB Industrial Connections & Solutions products?
For connection products, busway and switchgear from the Industrial Connections & Solutions side, see ABB’s US Electrification products page. To match a replacement drive, use the SKU and type code of the drive you are replacing.
Frequently asked questions
What is ABB Industrial Connections & Solutions?
ABB Industrial Connections & Solutions is a US ABB subsidiary, Industrial Connections & Solutions LLC, with the short name Industrial C&S LLC. As part of ABB’s electrification business, the company appears as an ordering and vendor entity for products such as switchgear and busway. However, it is not a drive model line.
Where do I find wiring instructions for an ABB drive?
Use the drive’s own manual from ABB’s library, such as the ACS255 user’s manual or the ACS180 hardware manual. The electrical installation chapters cover power, motor and control terminals, torque and grounding.
What torque do ABB ACS255 terminals need?
For ACS255 frame 1-3 IP66 (115-480 V) units, the manual gives a maximum of 0.5 Nm (4.5 lb-in) on control terminals and 1 Nm (9 lb-in) on power terminals. However, the 600 V manual lists different values, so use the manual for your variant.
Can I connect mains power to the U, V, W terminals?
No. ABB’s ACS255 manual says never to connect mains to the output terminals U, V, W. Input goes to L1/L2/L3, or to L1/L and L2/N on single-phase.
Does phase order matter on the drive input?
No. The ACS255 manual says input phase sequence is not important. Instead, the motor lead order or the drive’s reverse function sets motor direction.
Do I need shielded motor cable?
Yes, ABB recommends symmetrical shielded VFD cable for the ACS180 motor cable. For best results, terminate the screen at the drive clamp and at the motor with an EMC gland or clamp, as the ACS255 manual describes.
The name abb industrial connections & solutions points to an ABB US entity for products like switchgear and busway, while your drive wiring comes from the drive’s own manual. Follow the steps in order, check after each stage, and torque every terminal to the value for your variant. If you need help, a quote or a repair, contact Precision Electric or browse our ABB drives.