Eaton DG1 Guide: Specs, Catalog Numbers and Model Selection

Illustrated Eaton DG1 drive mounted inside an open control cabinet, wired by cables to an electric motor on a workbench.

If you are shopping for an eaton dg1, you need to know which model fits your motor and what to check before you order. This guide explains the series, decodes the catalog numbers and compares the drive with other Eaton options. You will also see the mistakes buyers make most often.

On this page

What the Eaton PowerXL DG1 is

What is the Eaton DG1?

The Eaton PowerXL DG1 is a general-purpose variable frequency drive (VFD). A VFD controls motor speed by changing the frequency and voltage it sends to the motor. Eaton’s catalog page lists it as “PowerXL DG1 general purpose variable frequency drives.”

Illustration of a wall-mounted orange drive unit, an electric motor, a coiled cable, and tools on a pegboard.
Keep output leads short and separated from control wiring between drive and load.

Eaton’s brochure calls the DG1 series the next generation of the PowerXL family. It features a patented energy-saving algorithm, high short-circuit ratings and a sturdy design. As a result, you can use it on pumps, fans, conveyors and similar loads.

Key features include:

  • Active Energy Control, Eaton’s energy-saving software
  • Dual overload ratings (constant torque and variable torque)
  • An integrated DC choke and EMC filter
  • A real-time clock for calendar and PLC-style functions
  • Ethernet and RS-485 ports, plus expansion slots
  • A graphical LCD keypad on many models

Is the Eaton PowerXL DG1 VFD the same as the Eaton Power XL DG1?

Yes. “Eaton DG1,” “Eaton PowerXL DG1,” “Eaton Power XL DG1” and “DG1 VFD” all name the same product line. However, people spell it different ways, but the drives are the same. In fact, Eaton’s own documents use “PowerXL DG1.”

Eaton DG1 specifications at a glance

What voltage and horsepower ranges do Eaton DG1 drives cover?

Eaton’s design guide lists these ranges for eaton dg1 drives:

  • 208 V: 0.75 to 100 hp
  • 230 V: 0.75 to 125 hp
  • 480 V: 1 to 1000 hp
  • 230 V single-phase: 1 to 30 hp

The line also includes 525 to 600 V models. However, older Eaton documents show different maximums, such as 250 hp in a 2012 overview. For that reason, use the design guide and current manuals for the range.

Does the DG1 have a built-in brake chopper, EMC filter and DC choke?

The EMC filter and DC choke are built in. The design guide lists a 5% DC link choke with input surge protection. It also lists EMI/RFI filters as standard on all drives, meeting EMC Category C2.

However, the brake chopper is less simple. Eaton lists it as standard on frames 0 to 3. Also, its SKU pages mark FB models with a brake chopper, while an FN example (DG1-35062FN-C54C) shows “No brake chopper.” So check the SKU page for your exact part.

What communications does the DG1 support?

The Eaton DG1 variable frequency drive supports EtherNet, RS-485, BACnet MS/TP, and Modbus TCP and RTU. Eaton lists 2 expansion slots even on the small frame-1 DG1-327D8FB-C21C (2 hp). As a result, you can connect to building automation systems and PLC networks without a separate gateway for the common protocols.

Other key specs and warranty

On the 400 V class, input is 380 to 500 V (-15%, +10%) at 50 or 60 Hz. Output frequency runs from 0 to 400 Hz. In addition, control modes are Frequency, Speed, Open-loop speed and Open-loop torque.

Eaton’s overview lists an operating range of -10 °C to 50 °C, or up to 60 °C with derating. It also lists a 100 kAIC short-circuit rating. However, that document is older, so confirm both figures in the current manual.

What is the warranty on a DG1? Eaton’s SKU page lists 24 months from shipment as standard. With Eaton certified startup, it extends to 36 months, covering parts, labor and travel.

How to read an Eaton DG1 catalog number

What does the Eaton DG1 catalog number mean?

Take DG1-34140FN-C54C as an example. Each part tells you something about the drive.

Isometric illustration of a navy electrical enclosure with an open front showing gray terminal blocks and wires, mounted on
Cover off, the connector strip sits ready for field wiring at the bench.
  • DG1: the series.
  • 3: three-phase input.
  • 4: the voltage class. A 2 means 230 V, a 4 means 400 V and a 5 means 600 V.
  • 140: the output amps. This is the constant torque current.
  • F (first suffix letter): the filter and choke. F means an internal EMC filter and DC choke. D means choke only, E means EMC filter only, and N means neither.
  • B or N (second suffix letter): the brake. B means a brake chopper. N means no brake chopper.
  • C (before the enclosure digits): coated circuit boards.
  • 54: the enclosure code. 00 is IP00, 20 is IP20, 21 is IP21/Type 1 and 54 is IP54/Type 12.
  • C (final letter): a graphical LCD display. N means no display.

Eaton’s application manual spells out this code, so you can read the brake letter straight from the catalog number. Still, confirm the brake chopper on the exact SKU page. Also note that small amp codes use a “D” for the decimal point. For example, 4D8 means 4.8 A.

The amp figure is the constant torque current. However, a drive one size up may carry the same load under a variable torque rating. In addition, Eaton’s installation manual lists the same ratings in both hp and kW tables.

Eaton DG1 models and ratings we stock

What DG1 models and ratings does Precision Electric stock?

We list 12 Eaton PowerXL DG1 part numbers. They cover 1, 10, 100 and 125 hp, each in NEMA 1 (C21C) and NEMA 12 (C54C). The table shows the listed horsepower and amps.

HorsepowerInput voltageAmpsNEMA 1 (C21C)NEMA 12 (C54C)
1 hp208–240 V4.8 ADG1-324D8FB-C21CDG1-324D8FB-C54C
1 hp400–480 V2.2 ADG1-342D2FB-C21CDG1-342D2FB-C54C
10 hp208–240 V31 ADG1-32031FB-C21CDG1-32031FB-C54C
10 hp400–480 V16 ADG1-34016FB-C21CDG1-34016FB-C54C
100 hp400–480 V140 ADG1-34140FN-C21CDG1-34140FN-C54C
125 hp400–480 V170 ADG1-34170FN-C21CDG1-34170FN-C54C

The 100 hp and 125 hp parts: read the ratings carefully

Eaton rates the DG1-34140FN at 75 kW / 100 hp / 140 A at constant torque (CT). At variable torque (VT), the same drive is 90 kW / 125 hp / 170 A. So the model carries both a 100 hp and a 125 hp rating, depending on the load.

The DG1-34170FN works the same way. It is 90 kW / 125 hp / 170 A at CT and 110 kW / 150 hp / 205 A at VT. For this reason, do not treat the two models as interchangeable. Instead, pick by load type and motor amps.

Frame size, weight and lifting

Both large parts are listed as frame size 6 (FR6) and they are heavy. Eaton lists the C54C 100 hp drive (DG1-34140FN-C54C) at 70.6 kg (about 155.6 lb) and 340.7 × 888.5 × 288 mm. The C21C 125 hp drive is listed at 44 × 20 × 18 in. Because of this size, plan your lifting gear and mounting space before it arrives.

By comparison, the 10 hp 480 V DG1-34016FB-C21C is listed at 26.45 lb and 21 × 14.3 × 10 in, as frame size 3 on its SKU page. However, frame sizes differ between sources. For example, a third-party table places 7.5 to 15 hp at FR2. So always check the Eaton SKU page for the frame, weight and size of your exact part.

NEMA 1 (IP21) vs NEMA 12 (IP54): choosing the enclosure

What is the difference between a NEMA 1 and a NEMA 12 DG1?

C21C is IP21/Type 1, which suits general indoor use. C54C is IP54/Type 12, which suits dusty areas or places with dripping liquid. For example, pick Type 12 if the drive sits on a plant floor with dust or drips.

Grey vented enclosure beside an orange sealed Eaton DG1 enclosure with gasketed door, with a broom and spill below.
Louvered slots on the left unit let air flow, which suits ventilated indoor panels.

However, one detail matters. A Type 12 drive keeps its rating only with the keypad or the keypad hole plug fitted. So if you remove the keypad, install the plug (DXG-KEY-N12PLUG).

Also note the clearance rule. The installation manual lists Type 12 drives with 0 mm minimum side clearances A and B. Before you lay out the panel, check the manual’s clearance table.

Can I convert a DG1 from Type 1 to Type 12?

Yes. Eaton sells a Type 12/IP54 option kit that converts a Type 1/IP21 drive. The kit includes a cover, fan and grommets. However, the keypad or hole plug rule still applies after conversion.

Also, do not confuse the drive enclosure with Eaton’s separate enclosed packages. Eaton’s PowerXL DG1 and SVX Enclosed Drives installation manual (IL040060EN) covers those. It lists Type 1, 12, 3R and Type 1 filtered and gasketed.

Choosing an Eaton DG1 for your motor and application

What is the difference between CT and VT ratings on a DG1?

The eaton dg1 has two overload ratings. Constant torque (CT) is the high overload rating, at 150% (IH). Variable torque (VT) is the low overload rating, at 110% (IL). In addition, Eaton lists 200% for starting.

Use CT for loads that need strong starting torque, such as conveyors, mixers and crushers. Use VT for centrifugal pumps and fans, where torque rises with speed. Because of this, a VT rating gives you more output current from the same drive, so it can drive a bigger motor.

How do I choose the right DG1 for my motor?

Follow these steps:

  1. First, read the motor nameplate full-load amps. Size from amps, not just hp.
  2. Next, decide whether the load is CT or VT.
  3. Then match the drive’s current rating for that load type to the motor amps.
  4. Match the line voltage class: 208–240 V, 380–500 V or 525–600 V. Also check your supply tolerance.
  5. Choose the enclosure: Type 1 or Type 12.
  6. Check the brake chopper. If the load regenerates or needs fast stopping with a braking resistor, you need one.
  7. Finally, check the communications. Ethernet, BACnet and Modbus ports suit building automation and PLC networks.

For example, a 480 V motor that draws 150 A on a fan could suit the DG1-34140FN at its VT rating of 170 A. However, a conveyor drawing the same current would need the CT rating, which makes the 140 A drive too small.

How do I size a braking resistor, and what if I need braking on an FN model?

A braking resistor burns off the energy a motor sends back while it slows a heavy load. Only models with a brake chopper (the B in FB) can use one directly. To size it, gather the load inertia, the stop time you need and how often you stop. Then pick a resistor from the Eaton manual that meets the drive’s minimum resistance and has enough power rating for that duty. Never use a resistor below the minimum ohm value.

An FN model has no brake chopper, so you have a few choices:

  • Order an FB model instead, if one exists for your rating.
  • Add an external brake chopper unit on the DC bus, if the drive’s manual supports it.
  • Use a longer deceleration time, so the load does not regenerate as much.
  • Use a regenerative drive or unit for loads that regenerate often.

If you are not sure which fits, send us your motor amps, load type and stop time.

Eaton DG1 vs other Eaton drives

How does the DG1 compare with the DC1, DA1, DX1 and SVX9000?

Eaton’s brochure places the Eaton DG1 series general purpose drive next to the DB1, DE1, DC1, DA1 and the High Performance DX1. Here is how the main ones differ.

Four white-and-navy drive units of varying sizes sit on a metal storage shelf, with one orange-fronted unit in the center.
A wrench rests on the shelf beside the smallest unit, suggesting quick service access.
  • DG1: the general-purpose drive for roughly 1 hp and up. It has Ethernet on board.
  • DC1 and DA1: compact OEM drives for smaller ratings. Both give 150% torque during overload. The DC1 gives 175% at start, and the DA1 gives 200% in sensorless vector control.
  • DX1: the high-performance drive. It extends the functional spectrum for applications with the highest safety requirements.
  • SVX9000: the older platform.

An older Eaton training overview grouped DE1, DC1, DA1 and M-Max at 0.25 to 30 hp. It grouped DG1 and SVX at the higher ratings. However, that document is dated, so use it only for the general idea.

Can a DG1 replace an SVX9000?

Often it can serve the same job, but it is not a direct drop-in. Mounting dimensions and weights differ. A distributor’s SV9-to-SVX-to-DG1 comparison shows this. For example, SVX FR4 is 5.00 in wide and 11.00 lb, while DG1 FR1 is 6.02 in wide and 14.33 lb.

Therefore, check the footprint and mounting holes in the Eaton manual before you promise a swap. If the holes do not line up, plan for a new mounting plate or panel changes.

Installing and starting up an Eaton DG1

How do I install and wire a DG1?

First, start with the Installation Manual MN040002EN. It covers mounting, line and motor wiring, I/O wiring and EMC installation. Also, frame 7 and 8 drives have their own FR7 & FR8 Installation Manual, MN040040EN.

Next, mount the drive using the template on the carton. Small frames can mount vertically or horizontally. However, heavy frames need a hook or hoist.

The manual also limits how often you switch the input voltage on. The maximum is one time per minute in normal operation. As a result, do not use the input contactor to start and stop the motor.

The manual warns that the drive can be dangerous after you disconnect it from supply, because it stores charge. For this reason, read the manual fully before you install, operate or service the drive.

What fuses and wire do I need for a DG1?

Field-installed conductors must be copper rated at 75 °C, according to the drive label data in the manual. For fuses, use Class T or Class J. For example, one distributor lists a 60 A fuse for an FR3 unit. However, fuse size depends on the exact part, so confirm it in the manual.

How do I set up and start a DG1?

Parameter setup is in the Application Manual MN040004EN. The drive also has a quick start wizard on the keypad that walks you through the basics. In addition, Eaton lists a WebUI setup guide. First, enter the motor nameplate data, then choose the control mode and run a test.

Common mistakes and when to get help

What mistakes do buyers make when ordering a DG1?

  • Ordering by hp alone, without checking CT versus VT and motor amps.
  • Choosing a Type 1 drive for a dusty or washdown area.
  • Removing the keypad on a Type 12 unit without fitting the plug.
  • Ordering an FN model where you need a brake resistor.
  • Assuming the frame size from hp. Frames differ across voltage classes and sources.
  • Assuming a DG1 fits an SVX9000’s footprint without checking dimensions.

When should I send a DG1 for repair?

Send the drive in if you see repeated fault codes, DC bus problems or a failed board. Also call us for any issue that involves opening the drive. Do not work inside it yourself. Because stored charge can stay in the drive after you remove power, the manual warns against it.

Where to buy Eaton DG1 drives, find manuals and get repairs

Where can I download DG1 manuals?

Get them from Eaton. These are the documents to download:

Isometric illustration of a workbench with a navy and orange unit, stacked manuals, a toolbox, pen, and notepad, plus motors
Printed pages held with a rubber band sit right beside the drive.
  • The Eaton PowerXL DG1 catalog page, which links the Application Manual MN040004EN and both installation manuals
  • The Installation Manual MN040002EN
  • The FR7 & FR8 Installation Manual MN040040EN
  • The Design Guide DG040001EB
  • The brochure BR040010EN
  • The Enclosed Drives Installation Manual IL040060EN
  • The product page for your exact SKU, such as DG1-34140FN-C54C, DG1-34170FN-C21C or DG1-34016FB-C21C

What does a DG1 cost and how do I order one?

Eaton’s SKU pages do not list prices. To get a quote, send us the exact catalog number, such as DG1-34170FN-C54C. Also tell us your motor amps and load type, so we can help you check the CT or VT match. In addition, Precision Electric stocks the listed DG1 part numbers and repairs drives too.

Frequently asked questions

What is the Eaton DG1?

The Eaton PowerXL DG1 is a general-purpose variable frequency drive. The range covers 208/230 V up to 125 hp and 480 V from 1 to 1000 hp. It has dual CT/VT overload ratings, an integrated DC choke and EMC filter, and Active Energy Control. Communications include Ethernet, RS-485, BACnet and Modbus.

What is the difference between NEMA 1 (C21C) and NEMA 12 (C54C) DG1 drives?

C21C is IP21/Type 1 for general indoor use. C54C is IP54/Type 12 for dusty or dripping environments. However, a Type 12 drive keeps its rating only with the keypad or the keypad hole plug fitted.

Is the DG1-34140FN rated 100 hp or 125 hp?

Both. Eaton rates it 75 kW / 100 hp / 140 A at constant torque (high overload). It is 90 kW / 125 hp / 170 A at variable torque (low overload). So pick based on your load type and motor amps.

Does the DG1 have a brake chopper?

Eaton lists a brake chopper as standard on frames 0 to 3. Its SKU pages mark FB models with a brake chopper, and an FN example (DG1-35062FN) is listed with none. For that reason, check the SKU page for the exact part.

Which Eaton drive should I choose: DG1, DA1 or SVX9000?

The DG1 is Eaton’s general-purpose drive for roughly 1 hp and up. The DC1 and DA1 are compact OEM drives for smaller ratings. The SVX9000 is the older platform, so check the mounting footprint before you treat a DG1 as a swap.

The eaton dg1 covers a wide range of motors, but the right model depends on your load type, motor amps, enclosure and braking needs. Check these points against the Eaton SKU page before you order. If you want a quote, help matching a drive to your motor, or a repair, contact Precision Electric and we will help.