What Are Harmonics? Causes, Effects and Fixes for Your Plant

Isometric illustration of a open navy electrical cabinet showing a drive unit, circuit breakers, and a sine wave with

Hot neutrals, warm transformers and nuisance drive trips often lead to one question: what are harmonics, and are they hurting your plant? This guide answers that question from the plant floor up. You will learn the definition, the frequency tables, the causes, the damage, how to confirm a problem and which fixes to try first.

On this page

What are harmonics? Definition and meaning

So, what are harmonics? Harmonics are sinusoidal voltages or currents at whole-number multiples of the fundamental frequency, which is 50 or 60 Hz on most power systems. That one sentence is the short answer to “define harmonic,” to “harmonics meaning” and to “what is a harmonics” when someone types it into a search box. A harmonic is one extra sine wave, riding on top of the main one, at two, three, five or more times the base frequency.

IEEE 519-2022 gives the formal version. It defines harmonics as components of order greater than one in the Fourier series of a periodic quantity. In plain words, you can break any repeating, distorted wave into a fundamental plus a set of pure sine waves. Each of those extra sine waves is a harmonic.

Seeing the idea in plain terms

Picture a clean 60 Hz current wave. Now add a smaller 300 Hz wave on top of it, then a smaller 420 Hz wave. The sum is a lumpy, flat-topped or double-humped wave. That lumpy wave is what a meter or scope shows you, and the pure sine waves inside it are the harmonics.

This is why people say electrical harmonics are “distortion.” The word harmonic distortion describes how far the real wave drifts from a clean sine wave. The more harmonic content, the more the wave looks bent out of shape.

Why do harmonics appear at all?

The usual cause is a nonlinear load. A nonlinear load draws current that does not follow the voltage wave in a smooth way. The simplest example is a diode. It lets current flow in only one direction, so the current wave comes out chopped, not sinusoidal.

Many modern loads act like diodes at their input. Drives, power supplies, LED lighting and battery chargers all fit this pattern. As a result, current harmonics are now normal in almost every building and plant.

Harmonic order and harmonics frequency (50 Hz and 60 Hz tables)

The rule for harmonics frequency is simple. Harmonic frequency equals the harmonic order times the fundamental frequency. The 5th harmonic on a 60 Hz system is 5 × 60, or 300 Hz. The same order on a 50 Hz system is 250 Hz.

Row of gears on a workbench, largest orange gear at left decreasing in size to small white gear at right, with tape measure
Only the first wheel is colored, so the eye starts there.
Harmonic orderFrequency on 60 HzFrequency on 50 Hz
2nd120 Hz100 Hz
3rd180 Hz150 Hz
5th300 Hz250 Hz
7th420 Hz350 Hz
11th660 Hz550 Hz
13th780 Hz650 Hz

Be careful when you read a spectrum on a meter. A peak at 300 Hz is the 5th harmonic on a 60 Hz system, but it is the 6th on a 50 Hz system. Always check the fundamental first, then count orders from there.

How high do harmonics go?

In general, higher orders carry less amplitude. The 5th and 7th are usually the big ones from drives, and the 25th is usually small. However, small does not mean harmless, because high-frequency content can still heat parts and upset electronics.

IEEE 519-2022 evaluates harmonics up to the 50th order. So when a utility letter or spec cites that standard, you should expect measurements across that whole range, not just the 5th and 7th.

Types of harmonics

Not every harmonic behaves the same way. You can sort power system harmonics in three useful ways: by whether the order is odd, even or a multiple of three, by phase sequence, and by whether the order is a whole number at all. Each view explains a different kind of damage.

Odd, even and triplen harmonics

Odd harmonics dominate in power systems. That is because the positive and negative half-cycles of the current wave are usually symmetrical. When both halves match, the even harmonics cancel, so the 2nd, 4th and 6th normally do not appear in large amounts.

Triplens are the odd multiples of three: the 3rd, 9th and 15th. They get their own name because they behave differently in three-phase systems. They matter most for neutral conductors and transformers, which the effects section covers below.

Even harmonics still show up in some cases, such as with half-wave rectifiers or unbalanced loads. IEEE 519 sets limits for them, and the 2022 edition handles even harmonics differently from the 2014 edition. If you work to a contract that names an edition, check which one it cites before you compare readings to limits.

Harmonic sequence: positive, negative and zero

Harmonics also have a phase sequence. In a balanced three-phase system, the pattern repeats in a set way:

  • Positive sequence: the fundamental, 4th, 7th and so on.
  • Negative sequence: the 2nd, 5th, 8th and so on.
  • Zero sequence: the 3rd, 6th, 9th and so on.

For motors, the meaning is easy to remember. Positive-sequence harmonics try to turn the rotor forward. Negative-sequence harmonics try to turn it backward. Zero-sequence harmonics produce no useful torque and only add heat.

This is why the 5th is a common motor-heating harmonic. It is negative sequence, so it fights the rotation, and drives produce it in large amounts. The motor wastes that energy as heat.

Interharmonics and high-order harmonics

Interharmonics are components at frequencies that are not whole-number multiples of the fundamental. Many loads that make harmonics also make interharmonics. Arc furnaces, welders and some variable-speed drives are common sources.

Note that TDD and THD in IEEE 519-2022 exclude interharmonics. So a clean THD number does not prove the wave is free of them. In addition, harmonics at 1.5 kHz and above, which means the 25th order and higher on 60 Hz, are getting more attention as power electronics spread.

What causes harmonics in a plant?

Every answer to what are harmonics leads back to the same cause: loads that draw current in pulses. The load takes current only during part of each cycle, so the wave is no longer a sine wave. Here are the most common sources you will find in a plant:

Isometric illustration of a workbench with power equipment connected by dark, gray, and blue cables to a wall-mounted
Bundled cable runs from the bench units converge on the enclosure at right.
  • Variable frequency drives with a diode or rectifier front end.
  • DC drives and soft starters.
  • Switch-mode power supplies in computers, PLC power supplies and controls.
  • LED and electronic-ballast lighting.
  • Uninterruptible power supplies and battery chargers.
  • Welders and arc furnaces.

Linear loads such as resistance heaters and plain incandescent lamps do not make harmonics. A motor running straight across the line makes very little. The trouble starts when the share of electronic load grows.

Why a six-pulse drive makes 5th and 7th harmonics

A standard drive has a six-pulse rectifier. It has six diodes, and each phase conducts twice per cycle. That makes six current pulses per cycle on the DC bus.

The result follows a pattern. A six-pulse rectifier produces harmonics at orders of 6k ± 1, where k is 1, 2, 3 and so on. That gives the 5th and 7th, then the 11th and 13th, then the 17th and 19th. The 5th and 7th are the largest, and each higher pair is smaller.

This pattern is useful on the floor. If your spectrum shows big 5th and 7th peaks and little 3rd, a six-pulse drive is the likely source. If the 3rd is large instead, look for single-phase loads such as computers and lighting.

How harmonic current becomes voltage distortion

Harmonic current starts at the load, but your other equipment feels harmonic voltage. The link between them is Ohm’s law at each harmonic frequency: Vh = Ih × Zh. Here Vh is the voltage drop at harmonic order h, Ih is the harmonic current, and Zh is the system impedance at that frequency.

The harmonic current flows back through the source impedance, such as the transformer and the cables. That impedance makes a small voltage drop at each harmonic frequency. Those drops add to the clean supply voltage, so the voltage wave at your panel is distorted too.

Why source impedance matters

Source impedance is mostly inductive, so it rises with frequency. At the 5th harmonic, the impedance is about five times larger than at the fundamental. The same harmonic current therefore makes a bigger voltage drop at higher orders.

A weak source, such as a small transformer or a long feeder, has high impedance. The same drive will create more voltage distortion there than on a stiff source. For that reason, two plants with identical drives can have very different voltage harmonics.

The point of common coupling

The point of common coupling, or PCC, is where your system meets the utility and other customers. IEEE 519 sets limits at this point. It limits the current harmonics you may send out and the voltage harmonics the utility should deliver.

Inside the plant, you can see worse distortion than at the PCC. Equipment on a shared bus with a large drive will see more voltage harmonics than the utility meter does. So measure where your sensitive loads connect, not only at the service entrance.

Voltage harmonics versus current harmonics

Current harmonics come from your loads. Voltage harmonics come from those currents flowing through impedance. Fixing the current at the source usually lowers both. Fixing the voltage alone, for example with a filter that holds the bus voltage, often leaves the extra current in the wiring.

What do harmonics do to equipment?

With power system harmonics, the main damage is extra heat. Each harmonic adds current or voltage that does no useful work. The part carries it anyway, so it runs hotter and ages faster. Below, each type of equipment is covered in turn.

Isometric illustration of an orange transformer, blue electric motor, and control cabinets showing power harmonics affecting
Dark rust streaks on the casing suggest this unit has run warm for years.

Transformers

Harmonic currents raise losses in transformer windings and cores. Eddy-current loss grows quickly with frequency, so high-order harmonics cause heat out of proportion to their size. A transformer can run hot even when its RMS current looks fine for its nameplate.

Triplen currents add another problem. In a delta winding, zero-sequence currents circulate inside the delta and heat it. A K-rated transformer is built to handle this extra heating, so ask about one when your load is mostly electronic.

What is a K-factor rating, and how do you calculate K-factor?

K-factor is a number that tells you how much harmonic heating a load causes in a transformer. A pure linear load has a K-factor of 1. The more high-order current the load draws, the higher the number.

To calculate it, express each harmonic current as a fraction of the total RMS current. Then square each fraction, multiply it by the square of its harmonic order, and add the results. Because the order is squared, high harmonics weigh heavily.

Standard K-rated transformers come in steps such as K-4, K-13 and K-20. K-4 suits light to moderate harmonic loads, K-13 suits heavier ones, and K-20 suits very heavy ones. Pick a rating at or above your calculated or measured K-factor.

How do you derate a standard transformer?

IEEE C57.110 gives the method to derate a standard transformer for nonlinear load. It limits the load current so total losses, including the extra eddy-current loss, stay within what the transformer handles on a clean sine wave. You need the transformer’s eddy-current loss data from the manufacturer, plus a measured harmonic spectrum, to run the numbers.

Are harmonic-mitigating transformers an alternative?

Yes. A K-rated unit only survives the heat, but a harmonic-mitigating transformer also reduces harmonics. Special winding arrangements, such as zig-zag windings, cancel triplen currents and some higher orders inside the transformer. As a result, less harmonic current reaches the source. These units suit panels that feed many single-phase electronic loads.

Neutral conductors

In a three-phase, four-wire system with single-phase loads, triplen harmonics do not cancel in the neutral. Instead, they add together. Neutral current can therefore reach or exceed phase current, even when the phases are balanced.

This is a classic cause of a hot neutral in an office, a data room or a plant with many power supplies. A neutral sized at the same rating as a phase conductor can overheat. In an older building with a reduced neutral, the risk is greater.

How do you size a neutral for harmonics?

Start with the code. NEC 220.61 normally allows a demand reduction on a large feeder neutral. However, that reduction does not apply to the part of the load that is nonlinear. So count the full neutral current from electronic loads.

In practice, many designers specify a 200% neutral for panels and feeders that serve mostly electronic loads. In bad cases, neutral current can reach about 1.7 times phase current. A 200% neutral leaves room for that.

IEC 60364-5-52 takes a different route. It uses the third-harmonic content of the phase current to pick a reduction factor for the cable:

Third harmonic in phase currentSize the cable onReduction factor
Up to 15%Phase current1.0
15% to 33%Phase current0.86
33% to 45%Neutral current0.86
Above 45%Neutral current1.0

As a field rule, not a code limit, act when neutral current nears the neutral conductor’s ampacity or runs higher than the phase current. Then upsize the neutral, run a separate neutral for each phase, or cut the triplens at the source.

Motors

Harmonic voltage makes extra losses in a motor’s stator and rotor. Negative-sequence harmonics such as the 5th also create torque that opposes rotation. The motor runs warmer, and in some cases you can feel torque pulsation or hear extra noise.

Over time, extra heat shortens insulation life. A motor that keeps failing early on a drive-heavy bus is worth checking for voltage distortion, not only for a bad drive output.

NEMA harmonic voltage factor and motor derating

NEMA MG 1 uses the harmonic voltage factor, or HVF, to rate this effect. You find it by dividing each harmonic voltage (as a fraction of rated voltage) by its order, then squaring it, adding the results and taking the square root. Triplens are left out, so you count the 5th, 7th, 11th, 13th and so on.

NEMA MG 1 says a general-purpose motor should run at rated load when HVF is 0.03 or less. Above that, derate the motor using the curve in MG 1, or move the harmonics off the bus.

What do PWM drive outputs do to motors?

Drive-output effects differ from line-side harmonics. A drive’s PWM output makes fast voltage pulses, and these cause two main problems.

  • Reflected wave: on a long cable, the pulse bounces at the motor and can nearly double. Peak voltage at the motor terminals can then far exceed the DC bus voltage and stress the winding insulation.
  • Bearing currents: the pulses create common-mode voltage on the shaft. That voltage can discharge through the bearings and leave fluting or pitting.

NEMA MG 1 Part 31 covers inverter-duty motors rated 600 V or less. They must withstand peaks up to 1600 V with a rise time of at least 0.1 microsecond. To protect other motors, shorten the cable, add a dV/dt or sine filter, use a shaft grounding ring or insulated bearing, and ground the system well.

Capacitor banks and resonance

Capacitor banks are the most common victim. A capacitor’s impedance falls as frequency rises, so it soaks up harmonic current. Worse, the capacitor and the system inductance can form a parallel resonance at some frequency.

If that resonant frequency lands near a harmonic that a drive makes, such as the 5th or 7th, the current and voltage can multiply. The result is blown fuses, bulging capacitors and failed banks. You can estimate the resonant order with this basic formula: the square root of the short-circuit kVA divided by the bank kvar.

Detuned reactors: common tuning percentages

A detuned reactor goes in series with the capacitor. It moves the bank’s resonance below the lowest harmonic the plant makes. The tuning order equals 1 divided by the square root of the reactor percentage, written as a decimal.

  • 5.67% reactor: tunes near the 4.2nd order, about 252 Hz on 60 Hz.
  • 7% reactor: tunes near the 3.8th order, about 227 Hz on 60 Hz. This is common where the 5th is the main harmonic.
  • 14% reactor: tunes near the 2.7th order, about 160 Hz on 60 Hz. Use it when the 3rd is large.

Worked resonance example for a stepped bank

Take a 1000 kVA transformer with 5.75% impedance. Its short-circuit level is about 1000 ÷ 0.0575, or 17,400 kVA. Now add a 600 kvar bank in four 150 kvar steps with no reactor.

Resonant order is the square root of 17,400 divided by the energized kvar:

Steps onBank kvarResonant order
1150about 10.8
2300about 7.6
3450about 6.2
4600about 5.4

As steps switch in, resonance slides down. Two steps land close to the 7th, and four steps land close to the 5th. That is why one fixed bank can behave well at light load and fail at full load.

To check each step, repeat the calculation for every step combination the controller can reach. Flag any result within about half an order of a harmonic your plant makes. Then confirm with a log taken as steps switch in and out.

Drives, controls, breakers and meters

Distorted voltage can shift the zero crossings that some controls use for timing. It can also cause nuisance trips on drives, flicker in lighting and odd behavior in PLCs. Meanwhile, thermal-magnetic breakers can trip early because they respond to heat, and some electronic trip units read peak or RMS values differently.

Basic meters can also mislead you. An average-responding meter reads wrong on a distorted wave. A true-RMS meter gives the right value.

Which drive faults point to harmonics?

Fault names vary by brand, so check your drive manual for the exact code. Still, a few trip types often link to line distortion:

  • DC-bus overvoltage: voltage swells, capacitor-bank switching spikes and resonance can push the bus too high.
  • DC-bus undervoltage: a flat-topped voltage wave has a lower peak, and a weak source sags under load. Both can starve the bus.
  • Input phase loss or imbalance: heavy distortion with unbalance can trigger this alarm.

Compare fault time stamps with bank switching and large load starts. Then compare the drive’s trip levels with the measured voltage. Do not raise the trip levels just to hide the fault, because the cause remains. Fix the distortion or the weak source instead.

How to measure and confirm a harmonic problem

A symptom does not prove harmonics. Heat, trips and failures have many causes. So confirm the problem with measurements before you spend money on a fix.

Step-by-step check

  1. List the symptoms and the loads. Note which drives, power supplies and lighting share the bus.
  2. Use a true-RMS meter. Compare neutral current with phase current. A neutral that is high compared with the phases points to triplens.
  3. Use a power quality analyzer. Record voltage and current waveforms, the harmonic spectrum, THD and, for current, TDD.
  4. Measure at the right points. Take readings at the PCC, at the affected equipment and at the largest nonlinear load.
  5. Record over time. Log through a full production cycle, since harmonics change with load.
  6. Compare to limits. Check the data against the limits in your contract or utility letter, using the right edition of IEEE 519.

Instrument and method details

For a compliance check, use a Class A analyzer, which means it meets IEC 61000-4-30 accuracy rules. A lower-class meter is fine for a first look. Then set it up with care:

  • Averaging: the analyzer measures in short windows (10 cycles on 50 Hz, 12 cycles on 60 Hz). It then combines them into 3-second and 10-minute values. IEEE 519 compares to limits using these.
  • Log length: record at least one full week so you catch every shift and production mode.
  • Current probes: clamp or flexible coils on all three phases and the neutral, with the arrow toward the load.
  • Voltage leads: connect them at the same point as the current probes, and size the CT or coil range for the load.

Safety and PPE when measuring live equipment

Only a qualified person should connect an analyzer to live gear. First, do an arc-flash risk assessment and wear the PPE it calls for, following NFPA 70E in North America. Also, use leads and meters rated for the voltage and category of the point you test.

Whenever possible, use clamp-on or flexible current probes so you do not open conductors. In addition, keep the panel closed for any reading you can take from outside.

What to look for in the data

First, look at the spectrum. Large 5th and 7th peaks point to six-pulse drives. A large 3rd points to single-phase electronic loads. Next, look at the voltage THD at the sensitive equipment, then at the current TDD at the PCC.

Finally, check for resonance if you have capacitors. A switch-in of the bank that changes the spectrum sharply is a strong clue.

What limits apply? IEEE 519-2022 values at the PCC

IEEE 519 sets voltage limits for the utility side of the PCC. These are the bus voltage limits:

Bus voltage at the PCCIndividual harmonicVoltage THD
1 kV or below5.0%8.0%
Above 1 kV to 69 kV3.0%5.0%
Above 69 kV to 161 kV1.5%2.5%
Above 161 kV1.0%1.5%

Current limits depend on how stiff the source is. Find the ratio of short-circuit current (Isc) to your maximum demand load current (IL). Then read the total demand distortion (TDD) limit for systems from 120 V to 69 kV:

Isc / ILTDD limit
Below 205%
20 to below 508%
50 to below 10012%
100 to below 100015%
1000 or more20%

Limits for individual current orders are tighter, and they are in the standard. Always confirm values against your edition and your utility agreement. For more on THD, TDD and the math, see our separate post on that topic.

Standards for 50 Hz plants

IEEE 519 is used worldwide, but 50 Hz plants often face other standards too. These are the main ones:

  • IEC 61000-3-2: limits harmonic current from equipment up to 16 A per phase.
  • IEC 61000-3-12: covers equipment above 16 A and up to 75 A per phase on public low-voltage systems.
  • EN 50160: describes supply voltage quality from the utility, including a voltage THD of 8% or less, measured in 10-minute values over a week.

How to reduce harmonics: a decision table

There is no single best fix. The right choice depends on the source, the size of the problem and your budget. In general, treat the largest source first, because small gains elsewhere rarely solve a plant-wide issue.

Two wall-mounted electrical enclosures, one navy-trimmed and one orange-trimmed, with cables running down to a clipboard and
The front unit’s display window is the only visible readout.
FixBest forWatch out for
Line reactor or DC link chokeSingle drives; a low-cost first stepResults vary by size and source impedance
Passive harmonic filter (tuned)Large six-pulse drive loadsCan interact with the source and with capacitors
12-pulse or 18-pulse driveLarge drives where cost is justifiedNeeds the right transformer or phase shift
Active front end driveLow harmonics at the drive itselfHigher cost and added complexity
Active harmonic filterMixed loads with changing harmonicsMust be sized for the current it must cancel
K-rated transformerHeating from electronic loadsHandles the heat but does not remove the harmonics
Larger or separate neutralHot neutral from triplensFixes the wire, not the source
Detuned reactor on capacitor bankAvoiding resonanceNeeds a study to pick the tuning

How much does each fix reduce drive current distortion?

These are typical current THD (THDi) ranges at full load for a six-pulse drive. Your drive may differ, so use the manufacturer’s data before you commit.

Drive setupTypical THDi
No choke or reactorAbout 80% or more
3% line reactorAbout 35% to 45%
5% line reactorAbout 30% to 35%
12-pulseAbout 10% to 15%
18-pulseAbout 5% to 8%
Active front endUnder 5%
Active harmonic filterOften 5% to 10% or lower, if sized for the load

Results shift with the drive’s DC link size, the source impedance and the load level. For example, a lightly loaded drive shows a higher THDi. Also remember that THDi is a ratio, so compare TDD at the PCC to the limits above.

For a closer look at tuned passive filters, see our separate post on TCI filters. It covers how they work and when to choose one.

Choosing a fix in order

  1. Confirm the source and the problem with measurements.
  2. Try the simplest change first, such as a reactor on the worst drive.
  3. Protect capacitor banks with detuning before any other change near them.
  4. Move to a filter, a multi-pulse drive or an active solution when the simple fix falls short.
  5. Re-measure after the change to prove the result.

Common mistakes with harmonics

Many harmonic problems come from a few repeat errors. Knowing them can save you time and money. Here are the ones we see most.

  • Using an average-responding meter. It reads low or high on distorted waves, so you may miss the problem.
  • Measuring only at the service entrance. The worst distortion is often at a bus near the big drive.
  • Adding capacitors without a study. A new bank can resonate with the system and magnify a harmonic.
  • Treating the symptom. Replacing a hot transformer without fixing the source brings the same failure back.
  • Ignoring the neutral. A balanced load does not mean a quiet neutral when triplens are present.
  • Mixing up 50 Hz and 60 Hz orders. As noted above, 300 Hz is the 5th on one and the 6th on the other.
  • Using the wrong standard edition. IEEE 519-2014 and 2022 differ, including how they handle even harmonics.
  • Trusting THD alone. THD is a ratio, and a high value at light load may be harmless.

When to call a repair shop or a specialist

You can handle first checks in-house. A true-RMS reading of neutral current and a look at the spectrum cost little. However, some jobs need more skill or equipment.

Illustration of a clamp meter with test leads on a rubber mat in front of an open electrical panel showing breakers and
The orange jaws wrap around a neutral conductor, set up for a current reading.

Call for help when a drive keeps failing or tripping and the cause is unclear. Call when a capacitor bank fails more than once, when a transformer overheats within its nameplate rating, or when a utility letter cites limits you cannot meet. Also call before you add a large drive, a filter or a capacitor bank to a bus that already shows distortion.

A repair shop can test a failed drive, motor or power supply and tell you if harmonics played a part. That knowledge helps you choose between a repair, a replacement and a fix at the source. In addition, a shop can help match a reactor or filter to the drive, using the manufacturer’s data.

Putting it together: a quick recap

If you remember only a few points, remember these. Harmonics are whole-number multiples of the fundamental, so on 60 Hz the 5th is 300 Hz. Nonlinear loads such as drives create current harmonics, and system impedance turns them into voltage distortion by Vh = Ih × Zh.

Heat is the main damage. It hits transformers, neutrals, motors and capacitor banks in different ways. Measure first, treat the biggest source first, and verify the result with a second measurement.

Now you have a full answer to what are harmonics: a set of extra sine waves, made by nonlinear loads, that you can measure, predict and reduce. If you need help with a drive, motor or power supply that you think harmonics have damaged, or you want a quote or repair, contact Precision Electric or browse our products.