Smvector Lenze AC Tech Parameters: A Technician’s Setup Guide

Open navy electrical enclosure with an orange terminal block on a DIN rail, green-yellow wires, a crimping tool, and a spool

Getting the smvector lenze ac tech parameters right is the difference between a drive that runs the first time and one that shows a fault. This guide walks you through commissioning in the order a technician works. Each stage lists the parameters, the values to enter, a check, and the mistakes to avoid.

On this page

What the SMVector parameters are and how they are organised

What are SMVector parameters?

The smvector lenze ac tech parameters are numbered settings called P-codes. Each one controls one part of the drive, such as start source, ramp time or motor data. The drive keeps them in the EPM (Electronic Programming Module), which holds its operational memory. As a result, your edits go into the “User settings” area of that module.

What are the Lenze SMVector parameters, as a list?

The lenze smvector parameters fall into families by number. First, find the family, because it tells you where to look.

FamilyWhat it coversExamples
P1xxBasic setup and I/OP100 start source, P102/P103 frequency limits, P120 assertion level
P2xxPID and sleep functionsProcess control settings
P3xxDrive mode and motor dataP300 mode, P302…P306 motor data, P399 calibration
P4xxNetworkP400 network protocol
P5xxRead-only display valuesP506 voltage, P508 current, P527 output frequency

This is a map, not a full table. However, ranges and numbers change between manual revisions, so treat the manual for your drive as the final word on any SMVector parameter list.

Why the manual revision matters for SMVector parameters

Older manuals list the digital inputs as P121…P123. Newer ones use P121…P124 and add P100 = 6, which exists only on 15 HP and larger drives. In addition, the behaviour of P399 differs between revisions. As a result, always match the manual to your drive before you change anything.

How do I find my drive’s software or manual revision?

First, read P501, which shows the drive’s software version. Next, check the nameplate on the drive for its model and type code. Then pick the operating instructions (EDBSV01) revision that fits that drive. If the parameter numbers in your manual do not match what you see on the keypad, you likely have the wrong revision.

How do I read the ESV model number to pick the right SMVector parameters?

The model number tells you which settings apply. For example, take the shop’s ESV153N02TXD-DR as a sample of reading a type code. The voltage digit is the “2” in “02”: 1 means 120/240 VAC, 2 means 240 VAC, 4 means 400/480 VAC, and 6 means 600 VAC. Next comes the phase letter: S is single phase only, Y is single or three phase, and T is three phase only. An F in the code means an integral EMC filter.

So “02T” reads as 240 V, three-phase input. Likewise, “04T” is 400/480 V and “06T” is 600 V. However, the enclosure and option letters differ by model, so check the type code table in the manual for those. Also confirm ratings from the nameplate, not from the model number alone.

What you need before you start the SMVector parameters setup

First, gather these items. Doing so saves you from stopping halfway through.

Workbench with a multimeter, a spool of wire, four orange-handled screwdrivers, wire strippers, a tray of terminals, loose
Open enclosure on the right is where the drive is wired and programmed.
  • The right operating instructions (EDBSV01) for your drive’s revision.
  • Motor nameplate data: voltage, current, frequency, speed in RPM, and power factor (cos phi).
  • A plan for how the drive starts and gets its speed reference: keypad, terminal strip or network.
  • The type of control devices, dry contact or PNP versus NPN, so you set the Assertion Level switch correctly.
  • A cold motor, at 20 to 25 °C, if you will run auto-calibration.
  • Your ambient temperature and altitude, because current derating (a lower allowed current) starts above 40 °C and above 1000 m.

The derating figures are 2.5% per °C above 40 °C, and 5% per 1000 m above 1000 m. Meanwhile, the drive’s stated range is -10 to +55 °C.

Safety first when you change SMVector parameters

Before you change any smvector lenze ac tech parameters, read the safety rules below. Some settings can quietly remove a stop function.

  • Follow lockout/tagout and the manual’s safety chapter before you open the drive or wire the terminal strip.
  • Know that P100 = 0 disables TB-1 as a STOP input.
  • Remember that a reset with P199 can disable STOP and EXTERNAL FAULT circuitry, so re-check P100 and P121…P124 after any reset.
  • Match the Assertion Level switch and P120 before you set P100 or any digital input. If they differ, you get an F.AL fault.
  • Never change the Assertion Level switch or P120 while the drive runs.
  • Connect protective earth, because earth leakage current is above 3.5 mA to PE.

Step 1: Get into the SMVector parameters (keypad and password)

How do I enter the password and change a parameter?

Use the keypad’s up and down arrows and the Mode button. When the display shows PASS, enter the password. Then you can scroll to the parameter you want. When a value blinks, you can change it with the arrows, and pressing Mode enters the new value.

Technician holding an orange handheld keypad with up and down arrow buttons and a Mode button, aimed at a wall-mounted drive
The enclosure door is open, with a screwdriver resting on the panel floor.

What is the default SMVector password?

The default password is 0225. It sits in parameter P194. However, if you changed it and lost it, you will need your records or the manufacturer’s support.

Check the SMVector parameters after Step 1

  1. The display shows P100 and you can scroll through the parameters.
  2. The drive shows StoP.

Note that the manual marks some parameters with (1). Those changes take effect only when the drive is stopped.

Step 2: Set the basic SMV drive settings (P100–P108)

How do I set the start source and speed reference (P100, P101)?

P100 is the Start Control Source. Choose from these values:

  • 0: local keypad (default)
  • 1: terminal strip
  • 2: remote keypad only
  • 3: network only
  • 4: terminal strip or local keypad
  • 5: terminal strip or remote keypad
  • 6: CTRL button select (15 HP / 11 kW and larger only)

Settings 4 and 5 need one TB-13 input (P121…P124) set to 08, Control Select. With that input open or not configured, the drive uses the terminal strip. With it closed, the drive uses the local keypad (P100 = 4) or remote keypad (P100 = 5).

P101 is the Standard Reference. It defaults to 0, the keypad. In this case it picks the speed or torque reference when no Auto Reference is chosen with the TB-13 inputs.

How do I set minimum and maximum frequency, and run above 120 Hz?

P102 is the minimum frequency and defaults to 0.0 Hz. P103 is the maximum and defaults to 60.0 Hz, with a range of 7.5 to 500 Hz. Both limits apply to every speed reference. However, you cannot set P103 below P102.

To set P103 above 120 Hz, scroll up to 120 Hz and release the button. Then wait one second and press the up button again.

What about ramp times (P104, P105)?

P104 is the time from 0 Hz to the base frequency in P167. P105 is the time from P167 back to 0 Hz. For example, on the 0.5 to 10 HP manual, P104 defaults to 20.0 s with a range of 0 to 3600 s. Set P105 the same way for deceleration. A long load may need a longer P105, or the drive can trip on overvoltage.

How do I set the stop method and DC injection braking (P111)?

P111 is the Stop Method. It chooses between coasting to a stop and ramping to a stop, with or without DC injection braking (a DC current that holds the motor shaft). Enter the value that matches your load, and set P105 if you want a ramp stop. The manual lists the exact values and the DC brake settings for your revision.

For SMV models of 40 HP (30 kW) and larger, P189 controls the Integrated Dynamic Brake. These drives use a braking resistor kit to absorb regenerative energy. Smaller drives need an external brake option instead.

How do I set motor overload (P108)?

P108 equals the motor current rating divided by the SMV output rating, times 100. The default is 100 and the range is 30 to 100%. For example, a 3 A motor on a 4 A drive gives 75%.

How do P107, P171 and P108 protect the motor?

P107 sets the motor overload type. It decides whether the overload function accounts for speed, because a motor cools less at low speed. Pick the setting that fits your motor and fan type.

P171 is the current limit. It caps the motor current as a percent of the drive’s output current rating. P108 works with the drive’s built-in motor thermal overload function, so a wrong P108 changes when the drive trips on overload. Set it from the nameplate, as shown above. If the motor is protected by a separate device, check the manual for how the two work together.

Check the SMVector parameters after Step 2

First, start from your chosen source with the motor uncoupled or the load safe. Next, confirm the direction and the ramp. Then read the P5xx values to confirm what the drive reports.

Step 3: Configure inputs, outputs and the speed reference (P120–P161)

How do I set the assertion level (P120) and digital inputs?

Set the Assertion Level switch (ALsw) and P120 to the same level. Use High (+) for dry contacts and PNP devices, and use Low (−) for NPN devices. High is the default. Always do this with the drive stopped.

The input levels are HIGH = +12 to +30 V and LOW = 0 to +3 V. After that, program the digital inputs P121…P124 on TB-13. These handle auto references, control select and similar functions.

Which function codes can P121–P124 use?

Two codes matter most for start and network control. Code 08 is Control Select, which switches between terminal strip and keypad. Code 09 is Network Enable, which a network-controlled drive needs. The same table also holds functions such as presets, jog, reverse, fault reset and external fault. However, the code numbers for those change with the manual revision. Look them up in the P121…P124 table of your manual before you wire a real application.

How do I wire the terminal strip for start and stop?

A 2-wire setup uses one maintained contact, such as a switch, to run and stop. A 3-wire setup uses a momentary start button and a momentary stop button. Either way, set P100 to 1 (or 4 or 5), and remember that TB-1 is the stop input. It stops working as a STOP input if P100 = 0.

Take the terminal numbers for reference, common and each input from the wiring diagram in the manual. The same manual gives the fuse or breaker size, wire size and maximum cable length for your model. Do not guess these values, because they depend on the drive rating and voltage.

How do I scale a 0–10 V or 4–20 mA speed reference (P160, P161)?

First pick the analog input type with P156. TB5 takes 0–10 V, 0–5 V or 2–10 V, while TB25 takes 4–20 mA.

Then scale it. P160 sets the output frequency at 0% input (4 mA). In contrast, P161 sets it at 100% (20 mA).

Keep the electrical limits in mind. The 0–10 V input resistance is above 50 kΩ, and the 4–20 mA input is 250 Ω. Also, the internal +10 VDC supply gives a maximum of 10 mA.

Finally, the analog output is configured with P150…P155, and P525 shows its value.

How do I set up preset speeds (P131–P137)?

P131…P137 hold preset speeds, each in Hz. First, enter the speed you want in each preset. Next, set P121…P124 inputs to the preset functions, and choose the preset with the TB-13 inputs. Then test each preset and read P527 to confirm the output frequency.

How do I set up PID process control (P2xx)?

The P2xx family holds the PID settings. Start with P200, which turns on PID mode. Then set the feedback source, the setpoint and the gains in the P2xx parameters. Start with low gains and raise them while you watch the process. The manual lists the P2xx ranges and defaults for your revision.

Check the SMVector parameters after Step 3

  • First, look for an F.AL fault. If it appears, the switch and P120 disagree.
  • Next, watch P527, the actual output frequency, against the input signal at minimum and maximum.

Step 4: Tune V/Hz, carrier and boost with SMV drive parameters (P165–P178)

These Lenze SMV VFD programming settings shape how the motor behaves under load.

Belt-driven orange motor and pump wired to a blue drive cabinet and clamp meter: smvector lenze ac tech parameters.
Pulley ratio sets the load-side speed, so verify it before changing frequency settings.
  • P167 Base Frequency: set it to the motor’s rated frequency for standard applications. The default is 60 Hz, with a range of 10 to 1500 Hz.
  • P168 and P169: fixed boost and acceleration boost, for extra starting torque.
  • P170 Slip compensation: raise it until motor speed no longer changes between no load and full load.
  • P177 and P178: speed units. Note that P178 must be non-zero for the P177 units to show.

How does carrier frequency affect drive rating?

P166 sets the carrier frequency. A higher carrier means less motor noise, but the drive must be derated. For example, at setting 1 (6 kHz), derate the drive’s continuous current to 92%.

Setting 2 (8 kHz) calls for 84%. Setting 3 (10 kHz) calls for 76%. However, these figures come from the v18 manual’s rating tables, so confirm them in your revision.

Check the SMVector parameters after Step 4

After any carrier change, watch P508 (motor current) and P507 (load as a percent of the drive output current rating). Both must stay inside the drive’s rating.

Step 5: Enter motor data and run auto-calibration for vector mode (P300–P399)

How do I set up vector mode with SMVector parameters?

P300 picks the drive mode. Mode 3 is Enhanced Variable V/Hz. Next, Mode 4 is Vector Speed, for single-motor jobs that need higher starting torque and speed regulation. Finally, Mode 5 is Vector Torque, which controls torque independent of speed.

For modes 4 and 5, set P302…P306 from the nameplate. For modes 2 and 3, you only need P302…P304, though calibration is still recommended.

ParameterMotor dataDefault or range
P302Rated voltageDefaults to drive rating
P303Rated current0.1–500 A
P304Rated frequency60 Hz
P305Rated speed1750 RPM (300–65000)
P306Cosine phi0.80 (0.40–0.99)

How do I run motor auto-calibration?

These steps follow the newer (v21-era) manual. However, older revisions differ, so check yours.

  1. Enter the nameplate data in P302…P306.
  2. Make sure the motor is cold, at 20 to 25 °C.
  3. Set P399 = 1 for standard calibration. Use 2 for advanced calibration if option 1 failed or the motor is non-standard.
  4. Apply Start. The display shows CAL.
  5. Wait for StoP to appear.
  6. Apply Start a second time to run the motor.

How long does auto-calibration take?

The CAL display lasts about 40 seconds. Then StoP appears, and a second Start runs the motor.

What do the P399 values mean?

The values are: 0 calibration not done, 1 standard enabled, 2 advanced enabled, 3 bypass calibration, 4 standard complete, and 5 advanced complete. However, older revisions use 1, which becomes 2 when complete. If P300 is 4 or 5, you must calibrate unless P399 = 3.

Check the SMVector parameters after Step 5

First, confirm P399 reads 4 or 5 (or 2 on older revisions). Then compare P508 current and P509 torque at a known load. P509 shows only in vector mode.

Watch for two faults here. If you start in vector or Enhanced V/Hz mode before calibration, the drive shows F.n1d and will not run. Likewise, an alternating CAL and Err means you tried calibration with P300 = 0 or 1, or before entering motor data. In addition, calibration is not possible while the drive runs from OEM settings.

Step 6: Add options and network SMVector parameters (P400 and up)

How do I set up network communications (P400)?

P400 is the Network Protocol. The values are 0 not active, 1 remote keypad, 2 Modbus RTU, 3 CANopen, and 4 DeviceNet. Because the choices depend on the I/O or communications module you install, check which module you have first. Then pick the P400 value that matches its protocol. Lenze also keeps a DeviceNet EDS file in its application knowledge base.

Blue drive enclosure with orange trim and two Ethernet cables on a gray panel, beside a gray electric motor and a tray of
Modular plugs seat into the module’s ports, and a lead drops down the wall.

What else does a network setup need?

First, set P100 to 3 if the network should start and stop the drive. Next, set one of P121…P124 to 09, Network Enable, because the drive needs that input before it accepts network control. Then set the address, baud rate and data format on the network side.

On drives of 15 HP and up, the P600 parameters set up the onboard communications. The manual lists the Modbus address, baud rate and format choices for your revision.

Our other posts cover CANopen, Ethernet/IP and the I/O and communications modules.

Resetting, backing up and copying SMVector parameter settings (P199 and the EPM)

How do I reset the drive or restore OEM settings (P199)?

P199 is Program Selection. The values are:

  • 0: operate from User settings
  • 1: operate from OEM settings (no changes allowed)
  • 2: reset to OEM defaults
  • 3: reset to 60 Hz defaults
  • 4: reset to 50 Hz defaults

P199 = 4 sets P103, P152, P161 and P167 to 50.0 Hz. It also sets P304 to 50 Hz and P305 to 1450 RPM. On 400/480 V drives, P165 becomes 400 V.

Both the 50 Hz and 60 Hz resets set P120 to 2 (High). If your devices are NPN, change it back, along with the switch, with the drive stopped. Also, a flashing GF means the EPM has no valid OEM data when P199 is 1 or 2.

After any reset, do these checks:

  1. Check P100 and P121…P124 again so STOP and EXTERNAL FAULT circuits work.
  2. Compare P120 with the switch.
  3. Enter the motor data again and recalibrate.

How do I back up or copy parameters between drives?

Use the EPM. With the EPM Programmer, you save settings as “User settings,” which you can edit, and “OEM default settings,” which you cannot edit. That lets you return to the original machine settings. In addition, a pre-programmed EPM fitted to an unpowered drive takes effect at the next power-up. Our EPM Programmer post covers the tool in detail.

Common SMVector parameter mistakes and fault messages

What are the most common programming mistakes and faults (F.AL, F.n1d, P100 = 0)?

Most faults on these SMVector parameter settings come from a short list of errors. The three you will meet most often are F.AL, F.n1d and P100 = 0 with no stop input.

Illustration of a navy electrical enclosure open on a table, showing a white drive unit with a red warning light, loose
Stripped conductor ends dangle from the terminal block, so check each wire before power-up.
  • F.AL: the Assertion Level switch does not match P120 while P100 or a digital input is not 0.
  • F.n1d: vector or Enhanced V/Hz mode was started before calibration.
  • P100 = 0 with no stop input: TB-1 is no longer a STOP input, so set up another stop before you rely on the terminal strip.

To clear F.AL, set the switch and P120 to the same level. To clear F.n1d, enter the motor data and calibrate with a cold motor. As for P100 = 0, add a stop input and test it before you hand over the machine.

What do the power and motor fault codes mean?

These faults come from the load, the supply or the motor. Use the table as a starting point, and confirm the codes in your manual revision.

FaultMeaningCommon causes
F.OUOvervoltageDecel ramp too short, or a load that drives the motor
F.LUUndervoltageLow or dipping supply voltage
F.PFMotor overloadOverloaded motor, or P108 set too low
F.AFHigh drive temperatureHot ambient, blocked airflow, or high carrier frequency
F.GFGround faultDamaged motor or cable insulation
F.OFOutput faultShort between output phases, or a wiring or motor fault

How do I reset a fault, and what does P110 do?

First, find and fix the cause. Then reset the fault with the stop input, or cycle the power. P110 is the start method, and it includes auto-restart choices. With auto-restart, the drive can start the motor again by itself after a fault. As a result, use it only when it is safe for the machine to restart without warning.

What other SMVector parameter errors cause trouble?

  • Accidental P199 resets: the reset may disable STOP and EXTERNAL FAULT circuitry and clears motor data.
  • Calibrating a hot motor or entering wrong nameplate data.
  • Editing in OEM mode: changes are not allowed when P199 = 1.
  • Wrong manual revision: parameter numbers and ranges can differ.
  • High carrier frequency without derating, or ignoring ambient and altitude derating.

When to call for repair or technical help with SMVector parameters

Where can I download the SMVector manual and get support?

Lenze writes the SMVector (ESV/SMV) operating instructions, document EDBSV01. Section 4.5, Parameter Menu, has the full list. Be sure to use the revision that matches your drive.

Lenze lists its SMV Support Portal in the v21.0 manual (document 13554876). You can also find the v18 manual (13465100), and Precision Electric hosts a copy of the manual. However, copies on other sites are hosted elsewhere, so confirm the revision.

When should I send the drive for repair or call support?

  • If a fault persists after a P199 reset to 3 or 4 and reprogramming, the manual says to contact factory technical support.
  • When a Drive ID warning shows, the EPM does not match the drive model (a P502 mismatch). In that case, verify the motor data and run auto-calibration. If that fails, replace the EPM.
  • For overheating, repeated trips or hardware faults, send the drive for repair.

Frequently asked questions

What is the default password for SMVector parameters?

The default is 0225. The display shows PASS, and you enter the code with the up and down arrows. Then press Mode to reach the parameters.

How do I reset an SMVector to factory defaults?

Use P199. A value of 3 resets to the 60 Hz defaults and 4 resets to the 50 Hz defaults. Afterwards, re-check P100 and P121…P124, because STOP and EXTERNAL FAULT circuitry may be disabled. Also re-enter the motor data.

Why does my SMVector show F.AL?

The Assertion Level switch does not match P120 while P100 or a digital input (P121…P124) is not 0. As a result, you must set the switch and P120 to the same level for your input devices. Use High for dry contacts and PNP, and Low for NPN.

Why does my SMVector show F.n1d and won’t run?

The drive was started in Vector or Enhanced V/Hz mode before motor calibration. First, enter the motor data in P302…P306. Then set P399 to 1 (or 2) with the motor cold, and run the calibration.

Which parameter sets the start source on an SMVector?

P100, Start Control Source. Use 0 for local keypad (default), 1 for terminal strip, 2 for remote keypad, and 3 for network. Values 4, 5 and 6 give switchable sources, and 6 works on 15 HP and larger only.

Where do I find the full SMVector parameter list?

Look in the Lenze SMVector (ESV/SMV) operating instructions, EDBSV01, section 4.5 Parameter Menu. For best results, use the revision that matches your drive.

Work through the stages in order and check after each one. Doing so keeps your smvector lenze ac tech parameters correct, and it keeps the stop circuits working. If you need a drive, help with settings or a repair, contact Precision Electric or browse our SMVector drives.