Invertek Optidrive E3 Programming: Parameters and First Start
Invertek Optidrive E3 programming is quick once you know which parameters matter and which manual matches your drive. This guide walks you through the keypad, the basic parameters, a first-start checklist, unlocking extended parameters and a factory reset. It works on its own, so you do not need the training videos to follow it.
On this page
- What you need before Invertek Optidrive E3 programming
- Which E3 model and manual applies to your drive
- Keypad basics for Invertek Optidrive E3 programming
- Basic parameters P-01 to P-14 explained
- Motor nameplate parameters: P-07, P-08, P-09 and P-10
- Speed limits and ramps: P-01 to P-05
- Control source and application mode: P-12 and P-13
- Extended and advanced parameters: the P-14 access code
- First start checklist for Invertek Optidrive E3 programming
- Resetting Optidrive E3 parameter settings to defaults
- Common trip codes and how to clear them
- Common mistakes in Invertek Optidrive E3 programming
- Where to get E3 manuals and software, and when to send a drive for repair
- Frequently asked questions
What you need before Invertek Optidrive E3 programming
What is the Invertek Optidrive E3?
The Optidrive E3 is Invertek’s general-purpose variable frequency drive (VFD). It covers 110 to 480 V single-phase and three-phase input, from 0.37 to 37 kW (0.5 to 50 HP). In addition, Modbus RTU and CAN come on board as standard. The drive runs on factory settings, but you still must enter your motor’s nameplate data.

Is the Optidrive E3 being replaced by the E4?
No. Invertek says the E3 remains in full production. The Optidrive E4 is an addition with extra capabilities, not a replacement. Because it keeps a 14-parameter basic setup and the same mounting footprint as the E3, it is a possible upgrade path later. Its first sizes are IP20 frame sizes 1 and 2, from Q3 2026.
What do I need from the motor nameplate?
First, read the motor nameplate before you touch the keypad. Then write down these values:
- Voltage (goes in P-07)
- Current, or FLA (full load amps, goes in P-08)
- Frequency (goes in P-09)
- Rated speed in RPM (optional, goes in P-10)
Which E3 model and manual applies to your drive
Use the guide for your enclosure and output type. Invertek’s E3 documentation page lists guides for IP20, IP66 indoor, IP66 outdoor, an IP66 quick start and fieldbus. However, the single-phase-output drives have their own guide, and its defaults differ from the three-phase one.
Which user guide applies to my E3?
Look at the part number on the drive label. Part numbers ending in -1F12 with a single-phase output, such as ODE-3-110070-1F12-01 or ODE-3-120043-1F12-01, belong to the single-phase-output family (ODE-3 1Ph). On the other hand, models with a 240 V or 480 V three-phase output use the three-phase guide. The E3 for single-phase motors is built for PSC or shaded-pole induction motors.
| Item | 3-phase-output guide | Single-phase-output guide (v2.02) |
|---|---|---|
| P-07 range | 0 to 250/500 V | 0 to 150/250 V |
| P-07 default | 230/400 V | 115/230 V |
| P-02 default | Varies by revision | Shown as 35.0 Hz/RPM |
Guide revisions also disagree with each other. For example, the v2.00 IP20/IP66 guide’s quick start gives P-02 a default of 0 Hz. The 20.0 default appears in other revisions, such as the v1.23 IP66 outdoor guide and the IP66 guide hosted by Rehfuss. The v2.00 guide applies to firmware 3.05. So match the guide to your drive’s firmware and model, and confirm safety-critical values in Invertek’s own PDF.
How do the single-phase-output drives differ for PSC or shaded-pole motors?
The single-phase-output guide (v2.02) changes several settings. P-05 defaults to 1 instead of 0. P-13 is reserved, so you cannot use it to pick General, Pump or Fan mode. P-09 has a minimum of 25 Hz, not 10 Hz. Also, the voltage boost for these motors is set with P-11, P-32 and P-33. Check the guide for the ranges before you change any of them.
What power-side specifications does each model need?
Input fuse or MCB ratings, cable sizes, terminal tightening torques and input chokes all depend on the model. They also change with supply voltage and frame size. For that reason, this article gives no fixed numbers. Instead, find your part number in the rating tables of your user guide and follow them exactly. The same tables cover the brake resistor connection, if your drive supports one.
Keypad basics for Invertek Optidrive E3 programming
What do the four keys do?
- Navigate: shows real-time information, enters and exits parameter edit mode, and stores changes.
- Up and Down: change speed in real-time mode, or change values in edit mode.
- Reset/Stop: resets a tripped drive and stops the drive in keypad mode.
How do I enter parameter edit mode and save a value?
- First, hold Navigate for about 2 seconds to enter the parameter list.
- Next, choose the parameter with Up or Down.
- Then tap Navigate to edit it.
- After that, change the value with Up or Down.
- Finally, store it by pressing Navigate.
- To finish, hold Navigate to return to the operating display.
The read-only P00 group shows live values, such as analog input level, motor voltage and DC bus voltage. However, you cannot change those.
Why can’t I change a parameter while the drive is running?
Certain parameters are locked during operation. This protects the drive and the machinery it runs. So stop the drive, then make the change. For exact keypad behavior on your firmware, check the printed guide.
Basic parameters P-01 to P-14 explained
What are the basic parameters on the Optidrive E3?
Parameters P-01 to P-14 are the basic group. They are read/write and visible by default. In contrast, P-15 to P-50 are extended, and P-51 to P-60 are advanced. Because each basic parameter is one small setting, most jobs need only a few of them.

| Parameter | Function | What to enter |
|---|---|---|
| P-01 | Maximum frequency/speed limit | Top speed you allow. Default 50.0 (60.0), up to 500.0 Hz |
| P-02 | Minimum frequency/speed limit | Lowest speed you allow. Check your guide for the default |
| P-03 | Acceleration ramp time | 0.00 to 600.0 s, default 5.0 s |
| P-04 | Deceleration ramp time | 0.00 to 600.0 s, default 5.0 s |
| P-05 | Stopping mode / mains loss response | Default 0, ramp to stop (1 on single-phase-output drives) |
| P-06 | Energy optimiser | Off for changing loads. On only for steady fan or pump loads |
| P-07 | Motor rated voltage | Nameplate voltage |
| P-08 | Motor rated current | Nameplate FLA |
| P-09 | Motor rated frequency | Nameplate Hz, 10 to 500 Hz |
| P-10 | Motor rated speed | Nameplate RPM, optional, default 0 |
| P-11 | Voltage boost | Raises torque at low speed. Use the least that starts the load |
| P-12 | Primary command source | Default 0, terminal control |
| P-13 | Application mode | General, Pump or Fan |
| P-14 | Access code | Default 0 |
How do I set basic parameters on an Optidrive E3?
First, start with the essential three: P-07, P-08 and P-09. Those must match the motor before the first start. Then tune P-01 to P-05 and P-10 to P-13 for the process. For each change, use the keypad steps above.
What do P-06 and P-11 do, and which loads suit them?
P-06 is the energy optimiser. When it is on, the drive lowers motor voltage at light load to save energy. It suits steady loads such as fans and pumps. However, leave it off for loads that change quickly or need fast response.
P-11 is the voltage boost. It adds output voltage at low frequency to help a motor start a heavy load. Because too much boost heats the motor and can cause over-current trips, raise it in small steps. Use more for hard-starting loads such as conveyors, and little or none for fans and pumps. The exact range depends on your guide.
Motor nameplate parameters: P-07, P-08, P-09 and P-10
What do P-07, P-08, P-09 and P-10 do?
P-07 is the motor rated voltage. For induction motors, use the nameplate voltage. For PM or BLDC motors, however, it is the back-EMF at rated speed. On the three-phase-output guide, the default is 230/400 V.
P-08 is the nameplate current. Its default depends on the drive rating. Because the motor overload protection refers to this value, a wrong entry weakens that protection.
P-09 is the rated frequency, 10 to 500 Hz, default 50 (60) Hz. Set it to the nameplate frequency. Also, P-10 returns to 0 when you change P-09, so re-enter the rated speed afterward if you use it.
P-10 is the rated speed, 0 to 30000 RPM, default 0. If you enter a value above 0, speed parameters such as P-01 and P-02 show in RPM instead of Hz.
Do I need to run an autotune?
After you enter the nameplate data, you can run an autotune. It can improve vector performance. However, the parameter number and exact steps depend on firmware. So follow the procedure in the user guide for your drive. Also note that the default control mode, P-51, is 0 (sensorless vector).
Speed limits and ramps: P-01 to P-05
How do I set min and max speed?
Set P-01 for the highest speed and P-02 for the lowest. The P-01 default is 50.0 (60.0) Hz. However, the P-02 default changes by guide revision, so read your own guide instead of trusting a fixed number. With a speed pot on the terminals, the pot varies speed from P-02 to P-01.

How do I change the acceleration and deceleration time?
Change P-03 for acceleration and P-04 for deceleration. Both run 0.00 to 600.0 s with a default of 5.0 s. Acceleration is measured from zero to base frequency (P-09). Likewise, deceleration is measured from base frequency to standstill. As a result, the ramp is not measured to P-01, which surprises many people.
How do I make the E3 coast to a stop?
P-05 sets the stopping mode. The default of 0 is ramp to stop. For example, one distributor guide says a setting of 1 gives a coast stop, which may suit some fan loads. However, the available options run 0 to 2, 3 or 4 depending on the revision. So check your guide before you change it.
Control source and application mode: P-12 and P-13
What does P-12 do and what is the default control source?
P-12 picks where start, stop and speed commands come from. The default is 0, terminal control. In that mode, the drive reacts directly to signals on the control terminals. Also, the v2.00 guide gives a range of 0 to 9. For terminal wiring, use our existing lessons on the start/stop switch and the speed potentiometer, and the input voltage post.
How do I run the motor from the keypad?
Set P-12 to 1 for keypad control in one direction. Set it to 2 for keypad control in both directions. Then use the Start key to run, Up and Down to set speed, and Reset/Stop to stop. However, the drive still needs its enable signal on terminal 1, so keep that input closed.
How do I wire forward/reverse, 3-wire control or PI control?
These setups change what each control terminal does. The extended parameter P-15 selects the input function, and your guide’s wiring table shows which terminals to use for each choice. For example, forward/reverse and 3-wire (pulse start) control each have their own wiring diagram. PI control is also chosen through P-12, and it needs a feedback signal. So follow the guide’s diagram for your firmware, and test at low speed first.
What are the General, Pump and Fan modes in P-13?
P-13 is Application Mode. In the advanced technical manual, General mode uses a 150% constant-torque limit. In contrast, Pump and Fan modes use 110% variable torque. So pick the one that fits the load, and read your guide for the other differences.
Extended and advanced parameters: the P-14 access code
How do I unlock extended parameters (P-15 and up)?
Set P-14 to the value stored in P-37. The factory value is 101. As a result, P-15 to P-50 open up. To reach the advanced set, set P-14 to P-37 + 100, which is 201 by default. However, use these only after the basic setup works.

What is the default access code?
The default access code in P-37 is 101. Meanwhile, P-14 itself defaults to 0, so extended parameters stay hidden until you change it. Also, you can set your own code in P-37 from 0 to 9999. P-14 accepts 0 to 65535.
How do I lock parameters with P-38?
P-38 is the parameter access lock, and it sits in the extended group. Set it to 1 to lock the parameters so nobody changes them by accident. Set it back to 0 to unlock them. Then confirm the behavior in your guide before you rely on it.
How do I clone parameters to another drive?
You have two options. The Optistick is an Invertek accessory that copies a parameter set from one drive and loads it into another. The E3 ASSIST / Optidrive Passport software does the same job from a PC. You can also save a parameter file with it. Both tools are on Invertek’s E3 documentation and software pages, and the guide gives the exact steps. Clone only between drives of the same model and rating.
First start checklist for Invertek Optidrive E3 programming
What order should I follow for a first start?
- First, confirm the supply and motor wiring match the model.
- Next, enter P-07, P-08 and P-09 from the nameplate, and P-10 if you use it.
- Then set P-01, P-02, P-03 and P-04 for the process.
- After that, check that P-12 matches how you wired control.
- Now start the drive. In the default terminal setup, closing a switch between terminals 1 and 2 starts it. A 5k to 10k pot on terminals 5, 6 and 7 sets speed.
- A few seconds after start, compare the displayed motor current with the nameplate.
- Finally, stop the drive and confirm the ramp-down and stop mode suit the process.
Resetting Optidrive E3 parameter settings to defaults
How do I factory reset the E3 and what does P-DEF mean?
Hold Up, Down and Stop together for more than 2 seconds. The display then shows P-DEF. Next, press Stop and the display returns to Stop. P-DEF is not a fault. Afterward, check P-12, because control returns to terminal control. Also re-check P-07 to P-10 against the nameplate.
Can I save my own default parameter set?
Yes. The E3 can store user-defined defaults, so a reset loads your set instead of Invertek’s. However, if you want Invertek’s factory defaults again, clear the user set from the PC software. The advanced technical manual describes the process.
Common trip codes and how to clear them
What do the common trip codes mean?
- O-I: over-current at the drive output. Look for a motor overload, a short circuit, a ramp that is too short or wrong motor data.
- hO-I: another over-current trip. Treat it like O-I, and check the fault table in your guide for the exact cause.
- I.t-trp: motor overload. The drive ran above the P-08 current for too long.
- Over-voltage: the DC bus voltage went too high. A deceleration ramp that is too short is a common cause, because the motor feeds energy back.
- Under-voltage: the DC bus voltage fell too low. Check for a weak or lost supply.
How do I clear a trip?
First, find and fix the cause. Then press the Reset/Stop key, or use a reset signal on the control terminals. For example, lengthening P-04 helps with over-voltage trips. If the same trip keeps returning, stop and check the load, wiring and motor. Your guide may also set a short wait before the drive accepts a reset after repeated trips.
Common mistakes in Invertek Optidrive E3 programming
What are the most common E3 programming mistakes?
- Leaving P-07 and P-08 at defaults.
- Using the three-phase guide for a single-phase-output model, or the reverse.
- Not seeing P-15 and above because P-14 is still 0.
- Assuming ramp times run to P-01 instead of P-09.
- Forgetting that P-10 changes the units from Hz to RPM.
- Resetting the drive and forgetting control returns to terminal control.
Does the E3 protect the motor from overload?
Yes. The E3 has internal motor overload protection, and its current limit is set at 150% of FLA. Because that protection works from P-08, enter the nameplate current correctly. Otherwise, a wrong value can cause nuisance trips or leave the motor poorly protected.
Where to get E3 manuals and software, and when to send a drive for repair
Where do I download Optidrive E3 manuals and software?
Go to Invertek’s Optidrive E3 documentation page. It lists the IP20, IP66 indoor and IP66 outdoor user guides, the IP66 quick start and the fieldbus guide. It also links the E3 ASSIST / Optidrive Passport tool and the CE and UKCA declarations. For Invertek Optidrive E3 programming, use Invertek’s own PDF for your drive instead of third-party copies.

When should I send an E3 in for repair?
If the drive trips again and again, shows a hardware fault after correct programming, or will not power up, stop reprogramming. Instead, send it for a repair quote. Precision Electric has repaired drives for over 35 years. In addition, quotes are free, and repairs carry a 12-month in-service warranty.
We also stock E3 drives in IP20, IP66 non-switched and IP66 switched versions, with 120 V and 240 V single-phase input and 480 V three-phase input.
Frequently asked questions
How do I program an Invertek Optidrive E3?
Hold the Navigate key for about 2 seconds to enter the parameter list. Then use Up and Down to select a parameter, and Navigate to edit and store it. At minimum, enter the nameplate voltage (P-07), current (P-08) and frequency (P-09). After that, set speed limits (P-01, P-02) and ramps (P-03, P-04) as the process needs.
What are the basic parameters on the Optidrive E3?
P-01 to P-14 are the basic group and are visible by default. They cover max and min speed, ramps, stop mode, motor nameplate data (P-07 to P-10), voltage boost, command source (P-12), application mode (P-13) and the access code (P-14).
How do I get to extended parameters on an Optidrive E3?
Set P-14 to the value in P-37, which is 101 by default. That unlocks P-15 to P-50. For the advanced parameters, set P-14 to P-37 + 100 (201 by default).
How do I factory reset an Optidrive E3?
Hold Up, Down and Stop together for more than 2 seconds. The display then shows P-DEF. Next, press Stop and it returns to Stop. However, if you stored a user default set, the reset loads that instead of Invertek’s defaults.
Which manual do I need for my Optidrive E3?
Use the guide for your enclosure and output type: IP20, IP66 indoor or IP66 outdoor, from Invertek’s E3 documentation page. In addition, single-phase-output models (ODE-3 1Ph) have their own user guide with different P-07 and P-02 defaults.
Good Invertek Optidrive E3 programming comes down to correct nameplate data, the right guide for your model, and a careful first start. So check your guide’s defaults before you rely on any value in this article. If you need help, a repair quote or a replacement drive, contact Precision Electric or browse our E3 drives.