If you need an Invertek Optidrive E3 quick start guide you can use at the bench, this page walks you through it. You will learn how to pick the right E3 variant, wire it, set the first parameters and start the motor. You will also see where to get the official manuals and software.

On this page

What the Invertek Optidrive E3 quick start guide covers

What the E3 is and what ratings it comes in

The Optidrive E3 is Invertek’s general purpose variable frequency drive (VFD). It takes 110 to 480 V single or 3 phase input. In addition, it covers 0.37 to 37 kW (0.5 to 50 HP) in IP20 and IP66/NEMA 4X enclosures.

Isometric illustration of an orange variable frequency drive mounted on a plate, with two motors, circuit breakers, a cable
Loose gland and grey sealing nut sit on the bench, awaiting installation.

The IP20 drive comes in sizes 1 to 5, up to 37 kW (50 HP). Meanwhile, the IP66 outdoor drive comes in sizes 1 to 4, up to 22 kW (30 HP). Also, both are CE, UL and RCM listed.

What the official E3 quick start guide includes

The official quick start is short. It lists the steps as check, prepare, mount, connect, final check, power on, commission and operate. However, it says plainly that it does not give detailed installation, safety or operating instructions. Because the user guide is the full reference, keep both at hand.

Invertek also says only a qualified electrician should install the drive. If that is not you, hand the job to someone who is.

Choose the right Optidrive E3 variant for your quick start

Start with the label. First, the voltage rating must suit your supply. Next, the output current must meet or exceed the motor full load current.

There are two E3 families. The standard E3 gives 3 phase output for 3 phase motors. In contrast, the E3 for Single Phase Motors takes single phase in and gives single phase out.

The 0.5 HP drives we sell span both families. Because the part number tells you which one you have, read it before you order or wire.

Standard E3 or single phase E3: which setup fits your motor?

The single-phase-output drive suits only PSC (permanent split capacitor) or shaded-pole single phase induction motors. Invertek lists fans, blowers, centrifugal pumps, fume extractors and airflow controllers. As a result, it fits jobs where high starting torque is not required.

This drive removes the need for 3 phase supply wiring and offers the same features as the 3 phase E3. Also, it comes in 110-115 V and 200-240 V models, from 0.37 to 1.1 kW (0.5 to 1.5 HP).

For example, the ODE-3-110070-1F12-01 is 0.37 kW (0.5 HP) and 7 A, with 110-115 V single phase in and out. It is IP20 size 1 with an internal EMC filter and no brake transistor. Its supply current is 8.5 A, and the datasheet calls for a 16 A Type B fuse or MCB.

Never connect a 3 phase motor to a single-phase-output drive. Likewise, never connect a single phase motor to a 3 phase output drive.

Which single phase motors does the single phase E3 not support?

Other single phase motor types are not supported. For example, capacitor-start motors with a starting switch need high starting torque, so they do not suit this drive. Set the motor nameplate values the same way as on a 3 phase E3, and check the single phase user guide for the boost settings that suit your motor.

IP20, IP66 non-switched and IP66 switched for your E3 setup

Which enclosure do you need? It depends on where the drive will live.

  • IP20: a compact enclosure for a panel or cabinet. It mounts on DIN rail or keyholes. Power comes in at the top and the motor leaves at the bottom (frame size 5 differs).
  • IP66 non-switched: a tough polycarbonate enclosure that is dust tight and washdown ready. You mount it straight on the machine. Then you wire start/stop and speed controls to the control terminals.
  • IP66 switched: the same enclosure, plus a front-panel isolator and an OFF/REV/FWD selector. Both IP66 types are rated for outdoor use.

Temperature limits differ too. IP20 runs at -10 to 50 °C. By comparison, IP66 runs at -20 to 40 °C, with derated operation up to 50 °C. In both cases, storage is -40 to 60 °C.

For environments, IP20 suits class 3C2/3S2, and IP66 suits 3C3/3S3 (IEC 60721-3).

Optidrive E3 quick start: our 0.5 HP models at a glance

The model-number key in Invertek’s user guide defines the enclosure character. The key shows 2 = IP20, A = IP66 non-switched and B = IP66 switched (older guides use X and Y). Brake transistor and filter type are coded in other positions of the same key. Always confirm each part number on its Invertek datasheet.

Part numberInputOutputEnclosureAmps
ODE-3-110070-1F12-01100-120 V, 1 phase1 phaseIP207.0
ODE-3-120043-1F12-01208-240 V, 1 phase240 V, 1 phaseIP204.3
ODE-3-120043-1F1A-01208-240 V, 1 phase240 V, 1 phaseIP66 non-switched4.3
ODE-3-120043-1F1B-01208-240 V, 1 phase240 V, 1 phaseIP66 switched4.3
ODE-3-140012-3F1A400-480 V, 3 phase480 V, 3 phaseIP66 non-switched1.2
ODE-3-140012-3F1B400-480 V, 3 phase480 V, 3 phaseIP66 switched1.2
ODE-3-110023-1012100-120 V, 1 phase240 V, 3 phaseIP202.3
ODE-3-110023-101A100-120 V, 1 phase240 V, 3 phaseIP66 non-switched2.3
ODE-3-110023-101B100-120 V, 1 phase240 V, 3 phaseIP66 switched2.3
ODE-3-120023-1F12208-240 V, 1 phase240 V, 3 phaseIP202.3
ODE-3-120023-1F1A208-240 V, 1 phase240 V, 3 phaseIP66 non-switched2.3
ODE-3-120023-1F1B208-240 V, 1 phase240 V, 3 phaseIP66 switched2.3

Datasheet checks before your E3 quick start

Do not assume a 4.3 A, 240 V drive is 0.5 HP. Invertek’s datasheet for the 3 phase output ODE-3-120043-1012 lists it as 1 HP. However, our single-phase-output listings call the 4.3 A drives 0.5 HP, so check the datasheet for your exact part number.

Voltage figures differ slightly too. For instance, our listing shows 120 V output for the ODE-3-110070-1F12-01, but Invertek’s datasheet and configurator say 110-115 V. In that case, use the Invertek figure.

How do the 110-115 V input, 230 V 3 phase output models work?

These models, such as the ODE-3-110023-1012, use a voltage doubler. The drive steps up the single phase 110-115 V supply internally, then builds a 3 phase output at about 230 V. As a result, you can run a 230 V 3 phase motor where only a 110 V outlet is available.

Because the supply voltage is lower, the drive pulls more current from the supply than it sends to the motor. So check the supply circuit and fuse against the input current on the datasheet, not just the motor current. Also, take the current limits for each model from its datasheet.

This option makes sense when you have a 230 V 3 phase motor and only 110 V single phase power. If you can get a 230 V supply, a standard single phase input model draws less supply current.

Optidrive E3 startup instructions: mounting, cabling and safety checks

This part of any Optidrive E3 startup instructions matters most. Because a mistake here can hurt someone, work through the list below before you apply power.

Isometric illustration of a variable frequency drive mounted in a box with a lockout padlock, wire cutters, and a gloved
The orange hand probes the terminal block while leads run along the rail below.

Optidrive E3 startup instructions: checklist before power-up

  • Isolate the drive and wait 10 minutes before any work. The STOP function does not remove lethal voltage.
  • Unpack the drive and look for damage. If you find any, tell the supplier and the shipper right away.
  • Mount the drive vertically only. Put IP20 drives in a suitable cabinet with enough cooling air, and mount IP66 drives on the wall or machine.
  • Connect the motor to U, V and W with a 3 or 4 core cable.
  • Check the motor cable length. The 0.5 HP single-phase-output datasheet lists a maximum of 100 m (328 ft) and a maximum cable size of 8 mm².
  • Tighten every terminal to the torque in the user guide. Because torque, fuse and cable sizes vary by frame size and part number, use the drive-specific tables.

When do I disconnect the EMC filter?

If your supply is IT or corner grounded, disconnect the internal EMC filter before you connect the supply. The E3 is stated as having an internal Category C1 filter. However, some datasheets list none, so check yours.

The way to disconnect the filter depends on the frame size and enclosure, so follow the steps in your user guide. Removing the filter lowers the leakage current to earth. However, the drive then no longer meets its EMC category on its own, so you may need an external EMC filter.

Overload protection

The E3 gives motor overload protection. It turns on when you enter the motor nameplate current in P-08. Also remember that E3 units are for controlled environments within the stated limits.

Invertek Optidrive E3 quick start wiring: start/stop switch and speed potentiometer

The factory default is terminal control, so you can run the motor with two simple parts. This works on IP20 and IP66 non-switched drives. To begin, follow these steps in order.

  1. Wire a start/stop switch between control terminals 1 and 2. Close it to start and open it to stop.
  2. Wire a 5k to 10k ohm potentiometer between terminals 5, 6 and 7.
  3. Enter the nameplate values in P-08 and P-09, then power up.
  4. Close the switch and turn the potentiometer to change speed.

As for limits, speed runs from P-02 (minimum, 0 Hz default) to P-01 (maximum, 50/60 Hz default).

What do the E3 control terminals do?

The first seven control terminals cover most simple jobs:

  • 1: +24 V supply for the digital inputs
  • 2: digital input 1 (start/stop in the default setup)
  • 3: digital input 2
  • 4: digital input 3 or analog input 2
  • 5: +10 V supply for a potentiometer
  • 6: analog input 1 or digital input 4 (potentiometer wiper)
  • 7: 0 V common

The drive also has output and relay terminals. Check the terminal diagram for your enclosure before you wire them. Then use P-15 to choose what the inputs do, for example run forward/run reverse or 3-wire control, as covered below. For a 4-20 mA signal, set the analog input format in P-16.

E3 quick start for IP66 switched drives

Switched drives need no external switch. Instead, turn the mains on with the built-in front isolator. Then use the OFF/REV/FWD selector to enable the output.

In keypad mode, P-31 decides whether the drive starts at once or waits for the keypad Start key. For full wiring photos, see our Training Lessons 1 to 4. They cover this step by step.

E3 quick start parameters to set first

The E3 has 14 basic parameters, P-01 to P-14, visible by default. First, set the motor ones from the nameplate.

Motor wired to a wall-mounted Optidrive E3 drive with orange keypad, beside two screwdrivers on a workbench.
The thick cable hangs in a loose loop, leaving slack before the cabinet.

Basic parameters P-01 to P-14 in the E3 quick start

ParameterWhat it does
P-01 / P-02Maximum and minimum frequency
P-03 / P-04Acceleration and deceleration ramps
P-05Stopping mode (default 0, ramped stop)
P-07Motor rated voltage
P-08Motor rated current; cannot exceed the drive’s continuous rating
P-09Motor rated frequency (10 to 500 Hz, default 50 (60) Hz)
P-10Motor rated speed
P-11Low frequency torque boost
P-12Primary command source (default 0, terminal control)
P-13Operating mode select
P-14Extended menu access code

How do I enter the nameplate values and ramp times on the keypad?

Use the same steps for P-07, P-08, P-09, P-10, P-03 and P-04. Read the values from the motor nameplate first.

  1. Hold the Navigate key for a couple of seconds to enter the parameter menu. The display shows a parameter number such as P-01.
  2. Press the Up or Down key until you reach the parameter you want, for example P-08.
  3. Press Navigate once to show the value.
  4. Press Up or Down to change the value to match the nameplate.
  5. Press Navigate again to save it, then pick the next parameter.
  6. Hold Navigate for a couple of seconds to leave the menu.

Enter voltage in P-07, current in P-08, frequency in P-09 and rated speed in P-10. For P-03 and P-04, enter the acceleration and deceleration times in seconds. A longer time gives a gentler start or stop, but a ramp that is too short can trip the drive.

How do I unlock P-15 and the extended parameters?

Set P-14 to 101 to unlock P-15 to P-50. To reach the advanced group, P-15 to P-60, set it to 201. Because P-15 sits in the extended group, you cannot see it until you do this.

P-15 selects the digital input function, also called the macro. The default of 0 suits most jobs. For example, setting 5 gives run forward/run reverse control, and 11 gives 3-wire control. In addition, it assigns the analog and digital inputs. P-16 sets the format for Analog Input 1, and P-47 sets Analog Input 2.

The E3 also has application macros for Industrial, Pump and Fan modes. For keypad navigation, see Training Lesson 2.

What does P-31 do?

P-31 sets the keypad start behaviour. Here are the values from the manual:

  • 0: minimum speed, keypad start
  • 1: previous speed, keypad start
  • 2: minimum speed, terminal enable
  • 3: previous speed, terminal enable
  • 4: current speed, keypad start
  • 5: preset speed 4, keypad start
  • 6: current speed, terminal start
  • 7: preset speed 4, terminal start

Settings 2, 3, 6 and 7 start the drive from the control terminals. As a result, they ignore the keypad Start and Stop keys.

What software and tools can I use to program an E3?

You have four main ways to program an E3. First, the built-in keypad and 7-segment LED display come standard, and a remote keypad is optional. Second, the Optistick Smart clones parameters quickly and gives you a Bluetooth link to a PC (it also works by NFC).

Third, OptiTools Studio is the PC software for setup and parameter work. Finally, Modbus RTU and CAN are on board as standard, so a PLC or controller can write parameters too.

For Modbus, the register for a parameter is 128 plus the parameter number. So P-15 is register 143.

Common mistakes during E3 quick start and fault finding

Most setup problems trace back to a short list of causes. For that reason, check these first.

  • Wrong supply: the voltage or phase count does not match the model. Read the label.
  • No nameplate current in P-08: overload protection then uses the wrong value, which can cause nuisance trips.
  • Cannot find P-15: set P-14 to 101 first.
  • Wrong motor type: a single-phase-output drive on a motor that needs high starting torque will struggle.

Why will my E3 not start after the quick start steps?

Check P-12 and P-31. Terminal-start settings in P-31 ignore the keypad Start key. Likewise, if P-12 is set for terminal control, the switch must be closed.

Also look for a fault code on the display. For example, code 08 is heatsink over temperature, which means the drive is too hot.

What do the other E3 fault codes mean and how do I clear them?

The display shows the code when the drive trips. Here are common ones:

  • O-I: output overcurrent. Look for a short or earth fault in the motor or cable, a jammed load, or a ramp time that is too short.
  • O-volt: DC bus overvoltage. The deceleration ramp is often too short, or the load pushes energy back into the drive. Lengthen P-04.
  • U-volt: DC bus undervoltage. The supply is low or was lost, so check the incoming voltage.
  • I.t-trp: motor overload. The drive ran above the P-08 current for too long, so check the load and the P-08 value.
  • P-LOSS: input phase loss on a 3 phase drive. Check the supply phases and fuses.

Fix the cause first. Then press the Stop/Reset key, use a reset input if you wired one, or cycle the power. If the fault returns right away, the user guide’s fault table lists the full set of codes.

How do I restore factory defaults on the E3?

Press the Up, Down and Stop keys together for more than 2 seconds. The display shows a default-loaded message, and the drive returns every parameter to its factory value. Confirm this key sequence in your user guide for your drive.

Because it resets all parameters, note down your settings first. Afterward, enter the nameplate values in P-07 to P-10 again, plus any ramp and control settings.

When should I send an E3 for repair?

Invertek says not to attempt any repair of the Optidrive. So if the drive stays faulted after the checks above, stop troubleshooting. Instead, send it to us for repair.

Where to get the Optidrive E3 quick start guide, manuals and software

Optidrive E3 quick start guide and manuals on invertekdrives.com

Go to Invertek’s E3 documentation page on invertekdrives.com. It lists the IP66 Quick Start Guide, the IP66 outdoor and indoor user guides and the IP20 user guide. In addition, it lists the Fieldbus user guide, the IP66 sun shade guide and the E3 ASSIST/Optidrive Passport.

Isometric illustration of a worktable holding a stack of papers, a USB cable, a USB drive, an orange tablet, glasses, and a
Shelving behind the bench holds boxes and motors waiting for installation.

The single-phase-output E3 has its own user guide. Use it for the 110-115 V and single phase output models. Meanwhile, datasheets sit on invertekdrives.com per part number.

Software and options

You can find OptiTools Studio on Invertek’s VFD range page. However, third-party manual mirrors may be older revisions, so use Invertek’s own pages.

Finally, external options include EMC filters, brake resistors, input chokes and output filters.

Optidrive E3 vs E4 and other alternatives

Is the E3 being replaced?

No. Invertek says the E4 does not replace the E3, and the E3 stays in full production as its core general-purpose range.

The E4 adds dual-channel SIL3 STO, embedded diagnostics with a flight recorder, USB-C and Bluetooth, and Industrial Ethernet. Also, its mounting is identical to the E3.

It is listed at 110-480 V 3 phase input, 0.37 to 4 kW (0.5 to 5 HP). However, it starts in IP20 sizes 1 and 2 from Q3 2026, so check availability first.

Should I buy the E3 or the new E4?

Choose the E3 for a simple general-purpose drive, an IP66 enclosure or single phase motor control. In addition, the E3 reaches 37 kW (50 HP), while the E4 tops out at 4 kW (5 HP). On the other hand, choose the E4 when the job needs integrated safety, diagnostics or Ethernet.

Because the mounting is identical, you can swap between them without redrilling. For higher-spec or other-brand options, see our guides to the Optidrive P2, Eco and ABB drives.

What buyers ask before ordering

Before you order, confirm these points:

Two workers in hard hats point at an orange drive in an open cabinet beside a motor, for an Optidrive E3 quick start.
Spare drive units and enclosures sit on the shelves behind the cabinet.
  • Input voltage and number of phases
  • Motor type and full load amps
  • Enclosure: IP20 in a cabinet or IP66 on the machine
  • Switched or non-switched, if you choose IP66
  • Whether the drive has a brake transistor
  • Whether it has an internal EMC filter

The last two vary by part number. For example, the 4.3 A IP20 ODE-3-120043-1012 datasheet shows no brake transistor and no internal filter. In contrast, the 3 HP IP66 ODE-3-220105-1F4B shows both. As a result, you should check each datasheet.

Finally, if a drive fails later, our repair and exchange service can help.

Frequently asked questions

Where can I download the Invertek Optidrive E3 quick start guide?

Invertek’s E3 documentation page lists the IP66 Quick Start Guide and the IP20, IP66 indoor and IP66 outdoor user guides. The single-phase-output E3 has its own user guide. Because the quick start says it is not a full installation or safety manual, use the user guide alongside it.

How do I follow the E3 quick start for the first time?

Wire a start/stop switch between terminals 1 and 2 and a 5k-10k ohm potentiometer between terminals 5, 6 and 7. Next, enter the nameplate current in P-08 and the nameplate frequency in P-09, then power up. After that, close the switch to start and turn the potentiometer to change speed. However, switched IP66 models use the front isolator and the OFF/REV/FWD selector.

How do I get to the extended parameters on an Optidrive E3?

Set P-14 to 101 to unlock P-15 to P-50. Set it to 201 for the advanced parameters, P-15 to P-60. Note that P-15, which sets the digital input function, is in the extended group.

What is the difference between the IP66 switched and non-switched E3?

Both are IP66/NEMA 4X outdoor-rated. The switched version has a built-in front-panel isolator and an OFF/REV/FWD selector. In contrast, the non-switched version uses external start/stop and speed controls wired to the control terminals.

Can I run a 3 phase motor from a single phase supply with the E3?

Invertek lists 1-phase-input models with 3 phase output in the standard E3 range. It also lists a separate E3 for Single Phase Motors with single phase output, which suits only PSC or shaded-pole motors. So match the part number to the motor type, and check the datasheet for voltage and current.

Is the Optidrive E3 being replaced by the E4?

No. Invertek says the E4 does not replace the E3, and the E3 remains in full production as its core general-purpose range. However, the E4 adds dual-channel STO, diagnostics and Ethernet.

This Invertek Optidrive E3 quick start guide gives you the order of work: pick the right variant, check and mount, wire, set the nameplate parameters and test. For anything deeper, use Invertek’s user guide for your enclosure. If you need help choosing an E3, want a quote or have a drive that needs repair, contact Precision Electric or browse our E3 drives.