Harmonic Filter Guide: Types, IEEE 519 Limits and Sizing

Isometric illustration of an open cabinet holding three orange capacitor-like units wired to a harmonic filter reactor

A harmonic filter cuts the distorted current that variable frequency drives (VFDs) and other nonlinear loads draw from your plant’s power system. You may be facing a utility notice, a spec that calls for IEEE 519, or a transformer that runs hot. This guide explains each filter type, the limits you must meet, VFD and chiller choices, and how to size, install, test, price and repair a filter.

On this page

What is a harmonic filter?

A harmonic filter is a device that reduces harmonic distortion in an electrical system. Harmonics are current or voltage components at whole-number multiples of the 50 or 60 Hz supply frequency. For example, the 5th harmonic on a 60 Hz system is 300 Hz. Nonlinear loads such as VFD rectifiers create them because they draw current in pulses instead of a smooth sine wave.

Where a harmonic filter sits in the system

A filter usually goes in one of two places. First, it can sit in series between the source and a single drive input. Second, it can connect in parallel at a shared bus, such as switchgear or a motor control center (MCC), and treat several loads at once. Passive filters are most often per-drive, while active filters often serve a whole bus.

The three harmonic filter families

Industry sources group harmonic filtering devices into three families:

  • Passive: inductors, capacitors and sometimes resistors tuned to the harmonic frequencies you want to cut.
  • Active: power electronics that inject a canceling current and respond to changing loads.
  • Hybrid: a mix of both, which balances cost and performance.

This guide does not re-explain the physics of harmonics. Instead, see our posts “What Are Harmonics?” and our THD guide for the basics and the math.

Why harmonic filters matter for drives and plant power

Why do harmonics from VFDs need to be filtered?

Most VFDs use a six-pulse diode rectifier on the input. This front end charges the DC bus capacitors in short bursts, so the line current is far from a sine wave. As a result, input current distortion (THDi, total harmonic distortion of current) can be high. However, no single number fits every drive.

Open gray enclosure holding an orange box and white cylindrical capacitors, wired by cables to a separate gray device.
Two cable bundles exit the central unit’s left side, one routed to the module.

Sources give a wide range for a drive with no mitigation. For example, Fuji Electric says a standard six-pulse VFD can exceed 30% to 40%. Meanwhile, a retailer buyer guide gives 35% to 80%, and a drive with no added impedance can go above 100%. The value varies for these reasons:

  • Whether the drive has a built-in DC choke or an input line reactor.
  • How heavily the drive is loaded at the time you measure.
  • How stiff the source is, which depends on transformer size and impedance.

What harmonics do to your equipment

Harmonic current adds heat in transformers, cables and capacitors. KEB notes that harmonic filters help protect capacitors and transformers from early failure. In addition, high distortion can upset other sensitive loads on the same bus. Finally, it can put your site out of line with the utility or with IEEE 519, which is the target the next section covers.

IEEE 519 limits: the target your filter has to hit

What harmonic limits does a filter have to meet?

IEEE 519 sets limits at the point of common coupling (PCC). The PCC is where your system meets the utility or other customers, not the drive terminals. The current limits depend on the ratio Isc/IL. Isc is the rated short-circuit current at the PCC, and IL is the maximum demand load current at the PCC.

So a stiff source with a small load gets looser limits. In contrast, a weak source with a large load gets tighter ones. The table below shows the 2022 edition’s odd-harmonic current limits for 120 V to 69 kV, as published in a power quality summary.

Isc/ILh below 1111 to under 1717 to under 2323 to under 3535 to 50TDD
Below 204.0%2.0%1.5%0.6%0.3%5.0%
20 to 507.0%3.5%2.5%1.0%0.5%8.0%
50 to 10010.0%4.5%4.0%1.5%0.7%12.0%
100 to 100012.0%5.5%5.0%2.0%1.0%15.0%
Above 100015.0%7.0%6.0%2.5%1.4%20.0%

Note that at Isc/IL below 20, the 4.0% limit applies to every odd order below the 11th. That includes both the 5th and the 7th. Some websites show different 5th and 7th values, so always check against the table itself.

TDD versus THD

TDD means total demand distortion. It measures harmonic current against the maximum demand current, not the current flowing at that instant. Because of this, a lightly loaded drive can show high THDi but still have low TDD. TCI notes that at Isc/IL below 20, 5% iTHD at full load is the most harmonic content allowed, which explains why many filters aim for 5%.

How do I calculate Isc/IL and TDD for my site?

You can work this out in three steps. This example assumes the PCC is at the transformer secondary and ignores the utility’s own impedance, so the result is a high estimate. Ask your utility for the real short-circuit value when you need a firm number.

  1. Find Isc. Take a 1000 kVA transformer at 480 V with 5.75% impedance. Full-load current is 1000 ÷ (1.732 × 0.48), or about 1203 A. Isc is that current divided by the impedance as a decimal: 1203 ÷ 0.0575, or about 20,900 A.
  2. Find IL. IL is your maximum demand current. IEEE 519 uses the average of the monthly maximum demand over the last 12 months. Say yours is 600 A.
  3. Find the ratio. 20,900 ÷ 600 is about 35. That falls in the 20 to 50 row, so the TDD limit is 8%.

Next, calculate TDD from measured harmonic currents. Take the square root of the sum of each harmonic current squared, then divide by IL. Suppose you measure 35 A at the 5th, 20 A at the 7th, 10 A at the 11th and 8 A at the 13th. The squares add up to 1789, and the square root is about 42.3 A. Divide by 600 A and TDD is about 7.0%, which is under the 8% limit.

Voltage distortion limits at the PCC

Bus voltage at PCCIndividual harmonicVoltage THD
1.0 kV or less5.0%8.0%
1 kV to 69 kV3.0%5.0%
69 kV to 161 kV1.5%2.5%
Above 161 kV1.0%1.5%

Current limits above 69 kV, and 12- and 18-pulse drives

Systems above 69 kV have their own, tighter current tables. The values below are for odd harmonics below the 11th and for TDD. Confirm them against the standard before you put them in a spec.

Voltage at PCCIsc/ILh below 11TDD
69 kV to 161 kVBelow 252.0%2.5%
69 kV to 161 kV25 to under 503.5%4.0%
69 kV to 161 kV50 or more5.0%6.0%
Above 161 kVBelow 502.0%2.5%
Above 161 kV50 or more3.5%4.0%

Special cases such as 12-pulse and 18-pulse drives get different treatment. Earlier editions of IEEE 519 raised the odd-harmonic limits for converters with a pulse number above six. The factor was the square root of the pulse number divided by six. Check the 2022 text to see how it applies to your case.

Why drive THDi is not the same as compliance

A filter data sheet quotes THDi at the drive input. However, IEEE 519 judges the combined current of all loads at the PCC. A 5% filter on one drive does not prove the whole site complies. Also, Eaton describes IEEE 519 as a conservative guideline written from the utility’s point of view, so confirm which limits your utility or spec actually enforces.

Even harmonics: check the standard

Sources disagree on the 2022 even-harmonic rules. One summary says only even harmonics up to the 6th are limited, at 50% of the odd limits. Other tables show even limits at 25% of the odd limits. So read the standard itself before you write these into a spec.

How should I measure for IEEE 519 compliance?

First, pick the PCC. It is normally where the utility connects you to other customers, so agree on the point with your utility in writing. Then measure voltage and current there with a power quality analyzer.

The 2022 edition judges results with statistics over a period of about one week. It uses very short readings of about 3 seconds and short readings of about 10 minutes. Limits apply to the 95th and 99th percentile of those readings. For current, the 95th percentile of the weekly short readings should stay within the table limit, and the 99th percentile may run higher, by set multiples of the limit.

For the analyzer, look for one that meets IEC 61000-4-30 Class A and IEC 61000-4-7 for harmonic measurement. Check the exact percentile rules in the standard before you report results.

Types of harmonic filters at a glance

What are the types of harmonic filters?

You can treat drive harmonics with an add-on harmonic filter or with a drive that produces fewer harmonics. The table compares the main options. The THDi figures come from manufacturer and vendor sources, so treat them as a guide and confirm with the maker’s data sheet.

OptionHow it worksReported THDiBest fitMain trade-off
Line reactor or DC chokeAdds impedance that smooths current pulsesAbout 30% lower; about 30 to 45% (vendor blog)Smaller drives, modest VFD share of loadVoltage drop; rarely reaches 5% alone
Passive harmonic filterSeries reactor plus shunt inductor-capacitor circuit tuned near the 5th and 7thAbout 5% at full load in many designsOne steady drive near full loadVaries with load and source; resonance risk
Active harmonic filterMeasures load current and injects opposite currentBelow 5% possibleShared bus, many drives, changing loadsHighest cost; needs measured sizing
Hybrid filterPassive section for the main harmonic, small active section for the restCheck maker dataLarge industrial systemsCost between passive and active
12- or 18-pulse drivePhase-shifting transformer feeds several rectifiers18-pulse below 6% (vendor blog)Larger drives, often over 50 hpLarge transformer, space
Active front end (AFE)Transistor rectifier with an LCL filterCheck maker dataRegenerative loadsHigher drive cost
Low harmonic driveDrive with built-in active filteringBelow 5% (chiller maker data)New installs or drive replacementReplaces the whole drive

What is the difference between passive and active harmonic filters?

A passive harmonic filter uses fixed inductors and capacitors tuned to certain orders, often the 5th, 7th or 11th. It costs less, but it only treats what it was tuned for. In contrast, an active harmonic filter measures harmonic current in real time and injects equal and opposite current across many orders. As a result, it adapts to changing loads and can also correct power factor and balance load, but it costs more.

Passive harmonic filter

What is a passive harmonic filter and how does it work?

A passive harmonic filter is built from inductors, capacitors and sometimes resistors. For six-pulse drives, makers usually tune it between the 5th and 7th harmonics. TCI describes the common design as a series line reactor plus a shunt tuning reactor and capacitor circuit.

Isometric illustration of a metal enclosure holding an orange coil, two gray coils, copper busbars, and white rectangular
Capacitor banks sit at right, linked to the tuning circuit by curved cables.

ABB explains the action this way. The capacitors charge from the line, and the drive draws its pulsed current from those capacitors. Meanwhile, the series inductors isolate the line from the drive current. So most of the harmonic current circulates locally instead of flowing back to the source.

According to Fuji Electric, many designs bring a six-pulse drive below 5% THDi. TCI says 5% iTHD or less is possible when the filter is applied properly. ABB’s drives page gives a typical THD of 5 to 10% with a passive filter. However, results depend on load level, drive impedance and the source. Use the maker’s data sheet for your exact drive size.

Weak points of a passive filter

  • Load sensitivity: it works best when the load stays steady and runs near full output.
  • Source sensitivity: performance changes with source impedance.
  • Leading power factor: at light load, the capacitors can push power factor leading.
  • Resonance: it can interact with other capacitors or the system and amplify a harmonic.
  • Overload: harmonic current from nearby nonlinear loads can flow into it.
  • Drive impedance: TCI recommends using all passive filters with drive impedance, such as a DC choke or line reactor.

Passive filters with generators, UPS and light load

A generator is a weaker source than a utility transformer, so harmonic voltage distortion is higher. The filter capacitors can also push the generator into leading power factor at light load, which generators tolerate poorly. For this reason, many passive filters include a contactor that disconnects the capacitors below a set load level. The right setting depends on the filter and the generator, so get it from the filter maker.

The same leading-current concern applies to a UPS, since many UPS makers limit how much leading current they accept. Ask both makers before you connect a passive filter to either one. For generator sizing, give the generator maker your drive list and filter data. We do not know a safe rule of thumb that fits every case.

Is a line reactor or DC choke enough, or do you need a harmonic filter? Often a reactor is enough on its own. A 3% to 5% line reactor or a DC link choke adds impedance and lowers distortion. Fuji Electric puts the reduction at about 30%, and one vendor guide puts the result at about 30% to 45% THDi.

That is a useful step, but it rarely reaches 5%. Also, a 5% reactor adds about 2% to 3% voltage drop at full load. For drives under about 50 hp, a reactor or DC choke is often enough if your site still meets IEEE 519 limits. That usually holds when VFDs are a modest share of the total load.

Tuned and broadband passive filters

A reactor alone only adds series impedance. In contrast, a tuned or broadband passive filter adds a shunt branch that gives harmonic current a low-impedance path. That branch is what drives THDi down toward 5%.

Designers detune the shunt branch slightly below the target harmonic to avoid sharp resonance. Even so, you should check for resonance at both minimum and maximum load. This matters most if power factor correction capacitors share the bus. Finally, remember that these harmonic filter designs assume the drive has its own impedance, so confirm this with the filter maker.

Active harmonic filter

What is an active harmonic filter and how does it work?

An active harmonic filter uses current transformers (CTs) to measure the load current. Next, its controller works out the harmonic part of that current. Then an IGBT inverter, a fast transistor power stage, injects equal and opposite current. Eaton says this cancels most harmonic currents below the 49th order.

Where an active harmonic filter fits best

Active units suit a switchgear or MCC bus that feeds many VFDs. They also handle loads that change speed often or shift the harmonic spectrum. Because they adapt, they work well when you do not know the spectrum ahead of time.

Makers rate active units by the maximum RMS harmonic current they can absorb. One trade article lists ratings of 50 to 300 A per unit, with units paralleled for more capacity. However, that article is older, so check current ratings. In addition, active units can provide variable power factor correction and do not create a leading power factor at light load.

Trade-offs of active filtering

  • They cost more than passive designs.
  • You must size them from measured harmonic current on the bus, not from drive nameplates.
  • Capacitors on the same bus can resonate with the filter, so check resonance at minimum and maximum load.
  • Some specs exclude active parts where switching-frequency resonance is a concern.
  • Performance can change at partial load, so ask the maker for data at your normal operating point.

Hybrid harmonic filters

What is a hybrid harmonic filter and when is it used?

A hybrid harmonic filter pairs a passive section with a smaller active section. The passive part handles the dominant harmonic, usually the 5th. Then the active part cleans up the remaining orders. As a result, the hybrid aims for high performance without the full cost of a purely active unit.

Patent literature describes hybrids as costing more than passive but much less than purely active solutions. A distributor guide points them at large industrial applications. So a hybrid is worth quoting when a passive design falls short of your target but an all-active unit would be oversized for the job.

Harmonic filter for VFD: when you need one and which to pick

Do you need a harmonic filter on every drive?

No, not always. Many six-pulse drives do fine with a 3% to 5% reactor or a DC choke. You need more harmonic mitigation when current distortion at the PCC exceeds IEEE 519 or utility limits. You also need it when harmonics overheat transformers or disturb other loads. A power quality measurement or study tells you which case you are in.

Isometric illustration of an open electrical cabinet with a DIN rail holding a harmonic filter reactor, wiring, and a drive
A clamp-on current meter sits on the bench, ready for measuring line current.

Which harmonic filter for a VFD should I choose?

If you searched for a harmonic filter VFD answer, work through these points in order:

  1. Drive size: under about 50 hp, start with a reactor or DC choke.
  2. Number of drives: one dedicated drive often suits a per-drive passive filter. Many drives on one bus often suit one common active filter.
  3. Load steadiness: steady loads near full output favor passive. Changing loads favor active.
  4. Isc/IL at the PCC: a low ratio means tighter limits and a stronger filter.
  5. Capacitors on the bus: power factor capacitors raise resonance risk, so plan a check.
  6. Requirement: confirm whether the utility or the spec enforces IEEE 519, and at which point.

Rules of thumb, with caveats

One retailer guide offers this rule of thumb. If more than 70% of the harmonic current is 5th plus 7th, a passive design is likely enough. However, if the 13th, 17th or interharmonics dominate, lean toward active. Treat this as a starting point, not a design rule.

Also, Eaton says that for any motor over 50 hp, an 18-pulse converter offers maximum efficiency. At smaller sizes, Eaton says an inductor or passive filter is usually enough. In addition, Eaton notes that some high-diversity, low-power sites can use an active filter cost-effectively.

Drive-based alternatives to an external filter

When is an 18-pulse drive, active front end or low harmonic drive better than a filter? Usually it is better when you are buying a new drive anyway, or when the drive is large. Here are the main choices:

  • 12- and 18-pulse drives: a phase-shifting transformer feeds several rectifiers so their harmonics cancel. They suit larger drives but need space for the transformer.
  • Active front end: a bi-directional transistor rectifier that also handles regenerative loads. Eaton notes it needs an inductor-capacitor-inductor (LCL) filter to keep switching noise off the line.
  • Low harmonic drives: drives with built-in active filtering, such as ABB’s low harmonic models. See our ABB low harmonic drives post and our harmonic drive guide for details.

Harmonic filter for chiller drives

Do I need a harmonic filter for a chiller?

A VFD on a chiller compressor is often one of the largest harmonic sources on a building’s service. So the real question is whether the factory drive already includes harmonic mitigation. KEB advises that chiller VFDs include harmonic filtering, either built in or external. Check the chiller documentation and your PCC limits before you add anything.

What harmonic filter options do chiller makers offer?

Chiller and drive makers offer several factory options. Daikin’s centrifugal chiller VFD manual lists these:

  • Integrated DC-link harmonic filters.
  • External passive harmonic filter panels, including systems with two filters.
  • A Low Harmonic Drive that combines an active harmonic filter and the drive in one package, for THD below 5%.

Also, KEB offers harmonic and sine wave filters with its F6 drives and says its harmonic filter helps users meet IEEE 519. In each case, the maker matches the filter to the drive.

Partial load on chillers

Chillers spend much of their time below full load. Chiller design literature notes that an active filter in parallel with a rectifier-front-end VFD often cancels best at full load. Because of this, ask the maker for harmonic data at the load points where your chiller actually runs.

What to do before you buy a chiller filter

First, get the chiller maker’s harmonic data and its approved filter options. Next, check the PCC limits with your building engineer. Do not add a third-party harmonic filter for chiller drives without the chiller maker’s approval. These filters are usually factory-matched, and a change may affect the drive warranty.

How to size and specify a harmonic filter

What information do I need to size a harmonic filter?

Gather this data before you call a supplier. It speeds up the quote and avoids the wrong size.

Technician in blue coveralls watches two motors connected to a cabinet while a portable power analyzer with three current
Clamp-on sensors on the bench record load data before any filter is sized.
  • Drive hp or kW, rated input current and voltage.
  • Number of drives on the bus and how they run together.
  • Any existing line reactor or DC choke on each drive.
  • Transformer kVA and impedance.
  • Isc and IL at the PCC.
  • Power factor correction capacitors on the same bus.
  • Whether the system runs on a generator at times.
  • Ambient temperature and enclosure conditions.
  • Your target THDi or TDD, and where it applies.

Sizing a passive harmonic filter

Match the filter to the drive’s rated current and voltage, using the actual load. Then confirm with the filter maker that the drive has the impedance their design needs. Without it, the filter may not reach its rated THDi.

Which filter rating matches my drive hp and voltage?

Passive filters are built for one line voltage, so a 480 V filter does not suit a 600 V drive. Choose by the drive’s rated input current on the nameplate, not only by hp. Then check that the filter’s current rating covers that figure at your supply voltage.

We cannot list filter models or current ratings here, because they differ by maker and change over time. Send us the drive nameplate, the supply voltage and your target THDi, and we will help match a filter from the maker’s data.

Sizing an active harmonic filter

Size an active unit from measured harmonic current on the shared bus. Do not add up drive nameplates, because drives rarely run at full load together. Makers also provide spreadsheet sizing programs that start from total VFD kVA, so ask for them.

How do I check for resonance?

Resonance happens when a capacitor bank and the source inductance tune to a harmonic. You can estimate the resonant harmonic order with this formula: order = square root of (short-circuit kVA ÷ capacitor kvar). You can estimate short-circuit kVA at the bus as transformer kVA ÷ transformer impedance as a decimal.

For example, take a 1000 kVA transformer with 5.75% impedance. Short-circuit kVA is about 17,400. Add a 300 kvar capacitor bank, and the order is the square root of 58, or about 7.6. That sits close to the 7th harmonic, so the risk is real. Changing the capacitor size or tuning the bank with a reactor moves the resonance away from the harmonics your drives produce.

Run the check at both minimum and maximum load, since capacitors switched in and out change the result. For a large or complex system, a harmonic study is the safer path.

When to run a harmonic study

For a large system, run a power quality survey or harmonic study before you specify equipment. A study shows the real spectrum, the Isc/IL ratio and any resonance risk. As a result, you buy the filter that fits instead of guessing.

Installing and commissioning a harmonic filter

How do I install a harmonic filter on a drive?

Always follow the filter maker’s installation manual first. Then keep these general points in mind:

  • Mount the filter as close to the drive as the maker allows.
  • Follow the wiring diagrams exactly, including CT position and polarity on active units.
  • Ground the filter as the manual specifies.
  • Provide the ventilation or cooling the maker calls for, because the filter gives off heat.

Capacitors, resonance and drive bypass

Before start-up, list every capacitor bank on the bus. Then confirm the resonance check at minimum and maximum load. Also, ask the maker how the filter should behave when the drive stops or runs in bypass. A passive filter left on with no drive load can add leading power factor, and many designs include a contactor for this case.

Commissioning checks

Log current THD and TDD at the filter input and at the PCC. Take readings at several load points, not only at full load. Finally, record the results as your baseline for future checks.

Checking that the harmonic filter works

How do I verify that a harmonic filter is working?

Use a power quality analyzer to measure THDi and TDD at light, mid and full load. Next, compare the PCC readings with the IEEE 519 limits for your Isc/IL ratio. Also, check voltage THD against the voltage limits. If results drift from your baseline, the filter or the system has changed.

Some active units report their status over Modbus TCP or EtherNet/IP. One vendor suggests bringing that status into your controls or SCADA and trending voltage THD. That way, a rising trend warns you of filter wear before problems spread.

How much does a harmonic filter cost?

Cost follows a clear order for the same job. A reactor costs least, then a passive harmonic filter, then a hybrid, and an active unit costs most. Drive-based options such as 18-pulse or low harmonic drives replace the drive, so compare them against the drive plus filter.

Isometric illustration of a cable tray carrying white cables down to a navy harmonic filter cabinet beside two grey
The motor’s orange-trimmed drive sits at the far end, apart from the others.

Published retail prices conflict by a wide margin, even for similar sizes. So they are not a reliable guide for budgeting. These factors drive the real price:

  • Drive hp or kW, or bus harmonic current for active units.
  • Your THDi or TDD target.
  • Enclosure type and cooling needs.
  • Active versus passive versus hybrid design.
  • Installation labor and any harmonic study.
  • Drive replacement you can avoid, or that a new drive makes unnecessary.

Get quotes against a stated THDi or TDD target at a named point. Then compare offers on the same basis.

Common mistakes with harmonic filters

What mistakes should I avoid when applying a harmonic filter?

  • Oversizing or undersizing a passive filter against the actual drive load.
  • Adding a passive filter or large reactor without a resonance check.
  • Ignoring capacitor banks on the same bus.
  • Using a passive filter without drive impedance where the maker requires it.
  • Sizing an active filter from nameplates instead of measured current.
  • Judging compliance at the drive instead of at the PCC.
  • Buying a sine wave, dV/dt or EMI filter when you need harmonic filtering.

Can a harmonic filter cause resonance problems?

Yes, it can. A passive filter or a large reactor can shift the system’s natural resonant frequency onto a dominant harmonic. Then the system amplifies that harmonic instead of reducing it. Also, capacitors on the bus can resonate with an active filter, so check resonance at minimum and maximum load.

Is a harmonic filter the same as a sine wave filter or EMI filter?

No. A harmonic filter treats the drive’s input, where current flows from the line. In contrast, sine wave and dV/dt filters treat the drive’s output to protect the motor and its cable. EMI filters, also called RFI filters, block high-frequency noise. See our posts on output and EMI filter types for the differences.

Troubleshooting, repair and when to call for help

Symptoms of a failing filter

  • The filter runs hotter than normal or shows heat discoloration.
  • Capacitor fuses blow.
  • The drive trips without a clear cause.
  • Measured THDi creeps back up toward pre-filter levels.
  • The filter makes unusual hum, buzz or fan noise.

What you can check safely

Before you open any filter, follow lockout/tagout. Then wait for the capacitor discharge time in the manual and verify zero energy. After that, you can look for clogged air paths, failed fans, loose connections, bulged capacitors and blown fuses. Also, read any alarm codes on active units and compare a fresh THDi reading with your baseline.

Alarm codes, discharge times and replacement parts

Alarm codes, capacitor discharge times and test values differ by maker and model. We cannot give one set of numbers that is safe for every filter. Read the discharge time on the filter label or in the manual, and confirm zero voltage with a meter rated for the system voltage before you touch anything.

When you order replacement parts, match the original nameplate data. For a capacitor, that means the voltage rating and the capacitance or kvar. For a reactor, it means the inductance and current rating. Send us the nameplate and the filter model, and we will help you find the right part.

When should I repair or replace a harmonic filter?

Repair makes sense when a single part fails, such as a fan, fuse or capacitor. However, call the maker or a qualified repair shop for reactor damage, repeated capacitor failures or active filter power modules. Consider replacement when the load has changed so much that the filter no longer fits. Also replace it when parts are no longer available.

Where to find manuals, selection tools and standards

Where do I find harmonic filter manuals and selection tools?

Start with the maker’s own documents for your filter or drive. These are useful references for harmonic filtering:

  • Eaton VFD harmonics solutions brochure (BR04007002E): compares reactors, passive filters, active filters, 18-pulse and active front ends.
  • ABB low harmonic drive document (LVD-EOTKN073U-EN): explains passive filter drives and low harmonic drives.
  • TCI Drive Impedance and Passive Harmonic Filters paper: covers why passive filters need drive impedance.
  • Daikin VFD for Centrifugal Chillers installation manual: covers chiller filter panels and the Low Harmonic Drive.
  • KEB white paper, Boosting Chiller Performance with VFDs: covers harmonic filtering on chiller drives.
  • IEEE 519 standard: buy the current edition from IEEE before you quote its limits in a spec.

For active units, also ask the maker for its sizing spreadsheet.

Documents to have on hand before you call a supplier

Have the drive manual and nameplate photos ready. Also bring the single-line diagram, the transformer data and any power quality reports. Finally, include the utility letter or spec that sets your limits.

Frequently asked questions

What is a harmonic filter?

A harmonic filter is a device that reduces harmonic distortion, the current or voltage at multiples of the 50 or 60 Hz supply frequency. It comes in passive, active and hybrid types. On VFDs, it cuts input current distortion and helps meet IEEE 519 limits.

What is the difference between a passive and an active harmonic filter?

A passive filter uses fixed inductors and capacitors tuned to certain orders, usually the 5th and 7th. It costs less but depends on load and system impedance. An active filter measures load current and injects opposite current across many orders. It adapts to changing loads but costs more.

Do I need a harmonic filter for a VFD?

Not always. Many six-pulse drives are fine with a 3% to 5% line reactor or DC choke, especially under about 50 hp. You need a filter when harmonic current at the PCC exceeds IEEE 519 or utility limits, or harms other equipment. A power quality measurement tells you which case applies.

How low can a harmonic filter bring THDi?

Maker and industry sources say many passive designs bring a six-pulse VFD to about 5% THDi at full load. Active filters and low harmonic drives can reach below 5%. However, results depend on load, drive impedance and the source. Confirm with the maker’s data and your own measurement.

Do chillers with VFDs need a harmonic filter?

VFD-driven chillers are usually harmonic sources on the building service. So first check whether the factory drive already includes mitigation. Chiller makers offer DC-link filters, passive filter panels and low harmonic drives. Check the chiller documentation and your PCC limits before adding external equipment.

The right harmonic filter starts with good data: your drives, your source and the limits at your PCC. From there, a reactor, passive, active or hybrid filter, or a low harmonic drive, will fit the job. Measure before and after so you can prove the result. If you need help reviewing your drive setup, troubleshooting a harmonic problem or repairing a drive, contact Precision Electric and our team will be glad to help.