Submersible Water Pump Guide: Sizing, Cooling and Power
A submersible water pump sits under the water it moves, so the motor, the cable and the water flow all have to work together. This guide covers the electrical and motor side that many buyer guides skip. You will learn how a submersible water pump works, how to size it, how to power and protect it, and how to test it.
On this page
- What a submersible water pump is
- How a submersible pump works
- Types of submersible pumps and where each is used
- How to size and select a submersible pump
- Motor cooling: the requirement most installs get wrong
- Electrical supply, starting and protection
- What supply voltage, current unbalance and start limits apply?
- Drop cable and voltage
- How do I size the breaker, overload and underload protection?
- How do 2-wire and 3-wire single-phase motors differ?
- How do I check rotation and balance current?
- How do I splice and waterproof the motor leads?
- What surge protection and grounding do I need?
- Starting methods
- Overload protection
- Using a VFD with a submersible pump
- Installing a submersible pump: a practical checklist
- Testing and troubleshooting a submersible pump and motor
- Maintenance, repair or replace, and when to call for help
- Where to get manuals, selection tools and data
- Frequently asked questions
What a submersible water pump is
What is a submersible water pump?
A submersible water pump has a hermetically sealed motor close-coupled to the pump body. In short, the whole unit runs underwater. It pushes water to the surface with pressure instead of pulling it with suction, because the water is already at the pump inlet.
The defining feature is the close-coupled, submerged arrangement. It is not the hydraulic principle inside. In other words, the motor and the wet end (the part that moves water) form one assembly that runs under the liquid.
What are the main parts of a submersible pump?
Every submersible pump has the same basic parts, whether it sits in a well or a sump:
- Sealed motor: the electric motor that drives the pump.
- Shaft: carries the turning force from the motor to the impeller.
- Impeller or impellers: spinning wheels that add energy to the water.
- Mechanical seal: sits between the motor and the wet end to keep water out of the motor.
- Intake screen: lets water in and keeps large debris out.
- Sealed power cable: brings power to the motor. It is a specialized cable made for deep wells and other harsh conditions.
- Discharge: the outlet where water leaves the pump and enters the pipe.
How a submersible pump works
How does a submersible pump work?
First, power enters through the sealed cable and runs the motor. The motor turns the shaft, and the shaft turns the impellers. As a result, the impellers raise the pressure of the water inside the housing, and that pressure pushes the water up the pipe.

Deep-well units are vertical multistage centrifugal pumps. Each stage adds head, which is the lift the pump can give the water. A deep well submersible pump stacks stages until the total head covers the job.
Why the seal and cooling matter
First, the mechanical seal keeps water out of the motor. Motor housings are often oil-filled. If the seal fails, water reaches the motor and the pump will eventually burn out.
The pumped water also cools the motor as it flows past. Because that point decides whether an install lives or dies, it has its own section below.
Types of submersible pumps and where each is used
What is the difference between a submersible pump and a pedestal pump?
For example, this question comes up most with sump pumps. A residential sump pump is either a pedestal type or a submersible type. On a pedestal pump, the motor is not sealed and sits above the pit. On a submersible sump pump, the sealed motor sits in the pit.
Submersibles are now the most popular choice. However, the level switch is the main point of failure, so check it first when a sump pump misbehaves.
What types of submersible pumps are there and what is each used for?
The main types are deep-well pumps, sump pumps, and wastewater pumps. For example, a deep-well or borehole pump draws water from a well for water supply. In addition, wastewater and non-clog pumps handle liquids with solids. Some designs use a jacket or other cooling, and solar submersible pumps run on solar power. Our existing wastewater and solar posts cover those two in detail, so this guide stays on the shared electrical points.
| Type | Typical use | Liquid | Solids |
|---|---|---|---|
| Deep-well or borehole pump | Water supply from wells | Clean water | Very little |
| Submersible sump pump | Draining pits and basements | Clean or lightly dirty water | Small amounts |
| Wastewater or non-clog pump | Sewage and wet wells | Wastewater | Yes, by design |
| Solar submersible pump | Remote water supply | Clean water | Very little |
Also, drive method varies by job. Many use a simple across-the-line starter, while others use a soft starter or a VFD (variable frequency drive, which changes motor speed). Check the manual for the exact motor before you choose.
How to size and select a submersible pump
How do I size a submersible pump (flow and total dynamic head)?
First, gather your data. Grundfos lists these inputs: flow rate, head, liquid temperature and the pumped liquid. For a well, you also need the rated voltage, starting method, cable length and borehole diameter.

Next, calculate total dynamic head (TDH). It has three parts:
- The distance from the dynamic water level to the outlet (static lift).
- The friction loss in the pipe and fittings.
- The pressure you need at the outlet, converted to feet.
First, use this conversion: 1 psi equals 2.31 ft of head. Then add the three parts together.
A worked example
This example comes from a Grundfos presentation. The well needs 25 gpm. The static water level is 250 ft, and drawdown (how far the level falls while pumping) is 20 ft. The outlet sits 30 ft above ground. The example converts its 40/60 pressure switch setting to 116 ft of head, and friction loss is 23 ft.
Add them up: 250 + 20 + 30 + 116 + 23 equals 439 ft of total dynamic head. So you would look for a pump that delivers 25 gpm at 439 ft.
How do I calculate friction loss for my pipe size and fittings?
First, use the friction-loss table from the pipe maker, or the Hazen-Williams formula. In US units, loss in feet per 100 ft of pipe is 0.2083 × (100 ÷ C)1.852 × Q1.852 ÷ d4.8655. Here Q is flow in gpm, d is the inside pipe diameter in inches, and C is the pipe roughness factor. Plastic pipe is commonly rated at C = 150.
For example, 25 gpm through 2 in. plastic pipe loses about 1.3 ft per 100 ft. Next, multiply by your pipe length. Then add each fitting as an equivalent length of straight pipe, using the fitting maker’s chart. Finally, add the check valve loss.
How do I set up the pressure tank and pressure switch?
A pressure switch has a cut-in pressure, where the pump starts, and a cut-out pressure, where it stops. Common pairs are 30/50 and 40/60 psi. The gap between them is the differential.
- With power off and the tank empty, set the air precharge 2 psi below cut-in. For a 40/60 switch, that is 38 psi.
- Drawdown is the water the tank gives you between cut-out and cut-in. At 40/60 with a 38 psi precharge, it is roughly a quarter of the tank size.
- Size the tank so the pump runs at least one minute per cycle. Multiply pump gpm by one minute to get the drawdown you need.
As a result, a larger tank means fewer starts. That keeps you inside the start limits in the electrical section below.
How do I read a submersible pump curve?
A pump curve shows how much flow the pump gives at each head. Centrifugal pump curves use feet of head, not psi. A fixed-speed pump runs where its performance curve crosses the system curve. That crossing is the duty point.
In general, flow drops as head rises. For example, a Grundfos pump gives 100 gpm at 226.6 ft. Raise the head to 252 ft, and flow falls to just under 92 gpm.
Check valve and final selection
Allow for a non-return (check) valve. Grundfos notes that running without one increases the actual head at nominal performance by 0.5 to 1.0 m. Finally, select for the duty point, not for the motor rating. A bigger motor does not fix a pump that sits at the wrong spot on its curve.
Motor cooling: the requirement most installs get wrong
How much cooling flow does a submersible motor need?
The pumped water must flow past the motor at a minimum speed. The Franklin Electric 60 Hz AIM manual requires 0.25 ft/s for 4 in. motors rated 3 hp and higher. It requires 0.5 ft/s for 6 in. and 8 in. motors. Both figures apply to water up to 86 °F (30 °C).
However, small 4 in. motors of 2 hp and smaller have no required minimum flow, except that flow must be greater than zero. Warmer water needs more flow. Because the table figures vary by edition and brand, check the current manual for your exact motor.
When do I need a flow inducer sleeve?
You need a flow inducer sleeve when the installation cannot provide the minimum cooling flow. A sleeve is a shroud that forces water to move past the motor. Franklin lists these conditions:
- The well is too large to meet the flow table.
- Water enters the well above the lowest part of the motor.
- The pump sits in an open body of water.
- The water is warmer than 86 °F (30 °C).
Here is the manual’s example. A standard motor runs in water over 86 °F, and 90 gpm is needed for proper cooling. An 8 in. or smaller flow sleeve provides that flow.
What do I do for water hotter than 86 °F?
You have two choices. First, keep a standard motor and add more cooling flow, often with a flow inducer sleeve, as in the example above. Second, choose a Hi-Temp motor, which the maker builds for hotter water. A Hi-Temp motor still needs the minimum flow past it.
The derating steps and flow figures change with motor size and brand. So use the heat factor tables in the Franklin Electric AIM manual or your maker’s manual for your exact motor. Do not guess a derating factor.
Shut-off and pressure relief
The pump must never reach a point on its curve where cooling flow is lost. Franklin requires a pressure relief valve. Choose it so the motor still gets adequate cooling flow as the pump nears shut-off.
If the minimum cooling flow is not met for more than 10 seconds, shut the system down at once. Otherwise, you risk permanent motor damage.
Electrical supply, starting and protection
What supply voltage, current unbalance and start limits apply?
First, check the nameplate for hp, voltage, phase and Hz. Make sure they match the application. Then keep the pump inside the Franklin limits:

- Run within ±10% of nameplate voltage.
- Never exceed nameplate maximum amps.
- Keep current unbalance at 5% or less.
- Limit starts to fewer than 10 per 24 hours.
- Wait at least 20 minutes between shutdown and the next start-up.
In practice, short cycling breaks the start rules quickly. If a pump starts too often, find out why before you replace anything.
Drop cable and voltage
Next, size the drop cable for the motor and the run length. Longer runs to a more powerful motor need heavier conductors to keep enough voltage at the motor. For cable sizes, use the cable tables in the Franklin Electric AIM manual and the code that applies to your site. The right gauge depends on hp, voltage, phase and length, so this guide does not replace those tables.
How do I size the breaker, overload and underload protection?
For overload protection, Franklin calls for a quick-trip device, typically Class 10, that trips within 10 seconds at locked-rotor current. Do not set it above the nameplate maximum amps. Use the manufacturer’s heater or setting tables for the exact motor.
For the breaker, follow the motor-circuit rules of your electrical code and the manual. For underload protection, use an underload relay or a drive with a dry-run setting. Set it a little below normal running amps, so it trips when the pump loses water.
How do 2-wire and 3-wire single-phase motors differ?
A 2-wire motor has its starting parts inside the motor. You wire it to the line through a switch, with no control box. A 3-wire motor has a separate control box with a start capacitor, a relay and sometimes a run capacitor.
A 3-wire motor has three leads, usually yellow, black and red, plus a ground. Match each lead to its control box terminal, and follow the box’s wiring diagram. To test a capacitor, cut the power first and discharge it. Then check it with a capacitance meter against the microfarad rating on its label. Replace it if it is open, shorted or well off its rating.
How do I check rotation and balance current?
Single-phase motors turn the right way by design. On a three-phase motor, run the pump with a valve partly closed and note flow, pressure and amps. Then swap any two leads and repeat. The connection that gives higher flow and pressure is the right rotation.
Next, check current unbalance. Measure amps on each line. Find the average, then the largest difference from that average. Divide that difference by the average. The result should be 5% or less.
If it is higher, roll the leads. Move all three leads one position, so L1 goes to L2, L2 to L3 and L3 to L1. This keeps the rotation the same. Measure again at each of the three positions, and keep the one with the lowest unbalance. If every position is bad, look for a supply problem.
How do I splice and waterproof the motor leads?
Use a splice kit made for submersible cable, and follow its steps. Strip the conductors cleanly without nicking the copper. Crimp or join them, and then seal each splice with the kit’s heat-shrink or other waterproof layers. Keep the splice dry and clean while you work.
Afterward, test insulation to ground before you lower the pump. A bad splice is a common cause of low readings.
What surge protection and grounding do I need?
Ground the motor and the control box to the supply ground, following your electrical code. A metal well casing and metal drop pipe need proper bonding too. In addition, fit a surge or lightning arrestor at the control box or service, and ground it. Lightning is a leading cause of submersible motor failure.
Starting methods
For example, a soft starter limits the starting surge. Grundfos recommends a VFD or soft start with a 1-second ramp up to maximum frequency. See our soft-start post for how to set one up. One more rule: Franklin’s single-phase 2-wire and 3-wire encapsulated motors can only run on a VFD with the matching Franklin constant pressure controller.
Overload protection
As a pump wears, motor current rises until the overloads trip. The overload protects you in an emergency. However, it does not replace periodic checks, so log running current over time.
Using a VFD with a submersible pump
Our VFD posts cover drives in general. However, this section covers only the rules that are specific to a submersible water pump.
Can a submersible pump run on a VFD or soft starter?
Yes, within the manufacturer’s rules. For three-phase encapsulated motors, size the drive on the motor’s nameplate maximum amps, not on horsepower. Then follow the limits for frequency, ramps and filters below. Soft starters work too, and the same 1-second ramp guidance from Grundfos applies.
What minimum frequency should a submersible pump run at?
Thirty hertz (50% speed) is a typical minimum. Grundfos MS and MMS motors allow 30 Hz to 60 Hz, and Lowara recommends 30 Hz or more. However, some makers set a different minimum on specific motors. Do not treat 30 Hz as a safe default.
The pump must still produce flow, and the water must still pass the motor at the required speed at every duty point. For this reason, Grundfos advises setting the minimum frequency so the velocity past the motor is never below the requirement.
The static head trap
Suppose the VFD minimum is 30 Hz, but the system needs 48 Hz just to lift the water. Then the pump runs between 30 and 47 Hz without moving any water. As a result, the motor gets no cooling flow in that range. So set the operating minimum 2 to 5 Hz above the zero-flow frequency.
Ramps and maximum frequency
Also, use fast ramps. Grundfos recommends a 1-second ramp to maximum frequency. Lowara asks for acceleration and deceleration ramps to be as quick as possible, because they lubricate the thrust bearing. For large three-phase induction submersibles, standard practice is to cap operation at 60 Hz.
Is a sine-wave filter required on a submersible VFD?
Not always, and the makers differ. Franklin says typical installations use a reactor, a dV/dt filter or a sine-wave filter. It calls the sine-wave filter generally best but not always required. Grundfos recommends a sine-wave or equivalent RLC filter under listed conditions, for warranty purposes.
Grundfos does not treat RL-only or dV/dt filters as equivalent. It also says a line-side filter does not replace an output sine-wave filter. Finally, filter sizing needs the VFD model, carrier frequency, motor voltage, max amps, cable length and operating frequency.
In addition, match the VFD carrier frequency to the filter’s nameplate range. For example, a filter marked fs ≥ 3.6 kHz needs a carrier of at least 3.6 kHz.
Installing a submersible pump: a practical checklist
How do I install a submersible pump correctly?
Work in three stages: before lowering, while lowering, and after start-up. Use the motor manual for torque values and fit details.

Before lowering:
- Verify the nameplate hp, voltage, phase and Hz.
- Turn the shaft by hand. It must rotate freely.
- Inspect the lead assembly for damage.
- Test insulation to ground. It should read at least 200 megohm at 500 V.
- Check the splices and drop cable.
- Check the pump-to-motor coupling, shaft height and end play, and the lead connector jam nut torque.
How deep should I set the pump?
Set the intake below the lowest water level the well reaches while pumping, which is the dynamic level. The water above the intake must cover the pump’s NPSH requirement, with a margin. NPSH (net positive suction head) is the pressure the inlet needs to avoid cavitation, and the pump curve lists it. Use the maker’s figure rather than a rule of thumb.
Also keep the pump well above the bottom of the well. Silt and sand collect there and can clog the intake. Remember the cooling rule: the motor should sit above the well screen unless you use a flow sleeve.
How do I protect against dry running or low water level?
Use more than one layer. A low-level probe or float switch cuts power when the water drops. An underload relay trips when current falls because the pump has lost water. In addition, a flow switch or a drive with a dry-run setting adds a third check. Pick the layers that fit your well.
While lowering
Next, check insulation resistance again as the pump goes down the well. A gradual drop is normal as more cable enters the water. However, a sudden drop points to cable, splice or lead damage, so stop and find the cause.
After submerging and at start-up
Once the unit is submerged, insulation to ground should read at least 0.5 megohm at 500 V. Then start the pump and check these items:
- Rotation direction.
- Supply voltage.
- Running amps against the nameplate.
- Current unbalance.
- Flow against the cooling requirement.
Finally, record the motor model, hp or kW, voltage and serial number. You will want that data at the first service call.
Testing and troubleshooting a submersible pump and motor
What insulation resistance should a submersible motor have?
First, disconnect the motor leads from the control box or drive. Then measure insulation resistance from each lead to ground with a 500 or 1000 V DC megohmmeter (often called a megger). Also measure winding resistance.
| Condition | Reading |
|---|---|
| New motor, without drop cable | 200 megohm or more |
| Before submerging (installation check) | 200 megohm minimum |
| After submerging | 0.5 megohm minimum |
| In service, below 10 megohm | Test more often |
| In service, 0.5 megohm or below | Pull the pump |
So, a reading below 0.5 megohm after submerging means damage that you must locate and repair.
What winding resistance and line current are normal?
Normal winding resistance depends on the motor model, so use the resistance table in the maker’s manual for your exact motor. First, measure lead to lead with a meter made for low resistance. Then subtract the drop cable resistance if you measure at the control box. The result should land within the tolerance the manual lists.
For line current, normal means at or below the nameplate maximum amps, with unbalance at 5% or less. Also compare readings against the pump’s first start-up record. A single-phase motor should show the same pattern from run to run.
Cable fault or motor fault?
After you pull the pump, dry the cable and splices and test again. If the reading rises to 50 megohm or more, repair the cable or splice fault. If it stays low, disconnect the cable and test the motor by itself.
Why does my submersible pump trip on overload or ground fault?
A ground fault often comes from a damaged or wet cable, or from low insulation. Franklin’s chart says to check insulation resistance on the motor and the control box cable. For a stalled motor, the chart says to repair or replace the motor.
Overload trips usually come from one of these causes:
- Loss of cooling flow.
- Seal failure that let water into the motor.
- Unbalanced current.
- Misalignment or abrasives.
- Short cycling.
- A worn pump that draws more current.
On a VFD, watch for a wrong single-phase or three-phase setting, output leads over 1000 ft, and unequal motor cable resistance. As a result, each of these can cause faults that look like a bad motor.
Maintenance, repair or replace, and when to call for help
How often should I test a submersible motor?
Franklin Aqua practice is to megger the motor insulation every six months. For best results, record the reading along with the running current. If the reading falls below 10 megohm, test more often. Pull the pump when it reaches 0.5 megohm or below.

Also watch the running current. A rising trend tells you the pump is wearing before the overloads trip.
When should I repair or replace a submersible pump or motor?
If the motor tests as defective, check the pump end for wear first. Then replace the motor alone or the whole pump unit, depending on what you find. For a stalled motor, Franklin’s guidance is to repair or replace it.
However, do not try to repair sealed motors or seals in the field beyond what the manufacturer allows. Send them to a repair shop instead. Our Industrial Pump Repair post covers repair services, and our Custom Machined Pump Motor Lead Cap post covers lead cap parts.
Call for help when
- Insulation stays low after you dry the cable.
- The motor stalls or ground faults keep coming back.
- You cannot meet the cooling flow.
Where to get manuals, selection tools and data
Where can I find manuals and selection data for submersible pumps and motors?
Go to the maker’s own documents for numbers. These are the best sources:
- The Franklin Electric Submersible Motors AIM manual (application, installation and maintenance), in 60 Hz and 50 Hz editions.
- The Franklin Electric AID guide to VFDs and submersible motors.
- Grundfos SP-G Submersible Pumps Data Booklet.
- For motor details, the Grundfos Submersible Motor Guide for MS and MMS motors.
- Also, the Grundfos ECADEMY pump selection basics modules on TDH, the pump curve and selecting the pump.
- The Lowara guide to VFD applications with submersible motors.
Also, use the current edition from the maker’s site, and use the manual for your exact motor model. Some makers set different minimum frequencies on specific motors.
What does a submersible pump cost?
However, we do not quote prices here. Cost depends on the job, and these factors drive it most:
- Head and flow.
- Motor size.
- Cable length.
- Filters.
- The drive or starter.
As a result, a bigger head or a longer run raises the cost of both the pump and the cable. Ask for a quote once you know your flow, TDH and supply voltage.
Frequently asked questions
What is a submersible water pump?
It is a pump with a hermetically sealed motor close-coupled to the pump body. The whole unit runs underwater and pushes water to the surface with pressure instead of suction.
How does a submersible pump cool its motor?
The pumped water flows past the motor. Franklin requires 0.25 ft/s for 4 in. motors rated 3 hp and higher, and 0.5 ft/s for 6 in. and 8 in. motors, in water up to 86 °F (30 °C). If the installation cannot provide that flow, use a flow inducer sleeve.
Can I run a submersible pump on a VFD?
Yes, within the manufacturer’s rules. Size the drive on nameplate maximum amps. Then keep the frequency at or above the minimum (typically 30 Hz) that still gives cooling flow, and use the output filter the manufacturer calls for. Grundfos recommends a sine-wave filter under listed conditions.
How do I test a submersible pump motor?
Disconnect the leads and measure insulation resistance from each lead to ground with a 500 or 1000 V DC megohmmeter. A new motor reads 200 megohm or more without the drop cable. After submerging, you need at least 0.5 megohm. Below that, locate and repair the damage.
How do I size a submersible pump?
Find the flow you need and the total dynamic head. That is the lift to the dynamic water level, plus pipe friction, plus the required outlet pressure, where 1 psi equals 2.31 ft of head. Then pick a pump whose curve covers that flow at that head.
How often can a submersible pump start?
Franklin recommends fewer than 10 starts per 24 hours. It also recommends at least 20 minutes between shutdown and the next start-up.
A submersible water pump lasts when you size it to its duty point, keep cooling flow past the motor, and stay inside the supply and VFD limits. Test the insulation at install and every six months after that. If you need a pump, a motor or a repair, contact Precision Electric for a quote or help with your next job.