Motor Controls Guide: Choose the Right Device for Each Job
Choosing the right electric motor controls is easier when you start with the job the motor must do. This guide maps each job to a device: start and stop, gentle start, speed, or position. You will also learn how each device works, how to set it up, and where it usually goes wrong.
On this page
- What Is a Motor Control?
- Types of Motor Controls Compared
- How Does a VFD Control Motor Speed?
- How to Control the Speed of an AC Motor
- How Do You Size VFDs and Motor Protection?
- Soft Starter Settings and Bypass Contactors
- VFD Cabling, EMC and Harmonics
- DC Motor Speed Control
- Stepping Motor Control
- How Do You Control a Servo Motor?
- How Do You Size a Stepper or Servo System?
- Stopping, Braking and Reversing
- What Is a Motor Control Center (MCC)?
- Safety Before You Work on Motor Controls
- How to Choose the Right Motor Control
- Common Mistakes and When to Call for Repair
- Where to Find Manuals, Software and Standards
- Frequently asked questions
What Is a Motor Control?
A motor control is the equipment between the power supply and a motor. First, it starts and stops the motor. Depending on the type, it also controls how fast the motor accelerates, how fast it runs, or where it stops.
The range is wide. At the simple end, a contactor switches power on and off. At the other end, a VFD, DC drive, stepper driver or servo drive controls speed or position.
What jobs can motor controls do?
Most motor controls handle one or more of these jobs:
- On/off control: start and stop the motor.
- Controlled acceleration and deceleration: ramp the motor up and down gently.
- Speed control: run the motor at the speed the process needs.
- Position control: move a load to a set point and hold it there.
- Protection: guard the motor and the circuit from faults.
Protection and wiring rules for motor circuits come from your electrical code. For that reason, follow the edition your local authority has adopted, and check the code text itself for your case. A later section shows how to size the protection.
Devices and assemblies
The term covers two groups. Devices include contactors, starters, soft starters and drives. In contrast, assemblies include control panels and the motor control center, which houses many devices in one lineup.
A quick map from job to device
| Job | Typical device |
|---|---|
| Start and stop only | Contactor or across-the-line starter |
| Gentle start and stop at fixed speed | Soft starter |
| Variable speed, AC motor | VFD (AC drive) |
| Variable speed, DC motor | DC drive |
| Point-to-point position | Stepper driver |
| Precise, fast motion | Servo drive |
| Housing many starters and drives | Motor control center |
Next, the rest of this guide expands on each row.
Types of Motor Controls Compared
Three motor control types cover most AC motor work: the contactor or starter, the soft starter and the VFD. Each one adds capability, but each one also adds cost and complexity.

What are the main types of motor controls?
This table compares the three on the points buyers ask about most.
| Feature | Contactor / starter | Soft starter | VFD |
|---|---|---|---|
| Speed control | None | None while running | Full range |
| Soft start | No | Yes | Yes |
| Mechanical stress at start | High | Low | Low |
| Cost | Lowest | Middle | Highest |
| Complexity | Lowest | Middle | Highest |
Five starter types come up often: direct-on-line (DOL), star-delta, soft starter, VFD and auto-transformer. Star-delta and auto-transformer starters are reduced-voltage options. In other words, they lower the voltage at startup to cut the starting current.
What is the difference between a soft starter and a VFD?
A soft starter controls voltage during starting and stopping only. A VFD controls both voltage and frequency, so it controls speed the whole time the motor runs.
A VFD can also ramp a motor up and down like a soft starter. As a result, a motor with a VFD does not need a separate soft starter. However, using a VFD only for soft starting wastes its speed control.
Contactors and Across-the-Line Starters
A contactor gives basic on/off control. It has the lowest cost and the least complexity of any motor control equipment.
The trade-off is stress. Because the motor gets full voltage at once, the start is hard on the motor and the driven machine. Also, a contactor gives you no speed control. For more depth, our existing post on how to control how a motor starts and stops covers these methods.
Soft Starters
A soft starter uses thyristors, also called SCRs, to ramp up the voltage during start and stop. As a result, it reduces inrush current and mechanical stress. Once the motor reaches full speed, a bypass takes over.
A soft starter does not control speed during normal running. Instead, it suits loads that run at a fixed speed, such as pumps and compressors. Vendor guides often quote ramps of about 2 to 5 seconds, but treat that as a rough range, not a rule. Also, the soft starter’s current rating must be at least the motor’s current rating. For more detail, our post on the ABB PSTX softstarter goes deeper.
Variable Frequency Drives (AC Drives)
A VFD is an electronic controller between the supply and an AC motor. It sets the output frequency and voltage. In addition, it does everything a starter and soft starter do, and it adds continuous speed control.
However, the cost is higher, and cabling and harmonics need more care. For failure modes, read our post on how a VFD works and fails.
How Does a VFD Control Motor Speed?
A VFD changes the frequency and voltage it sends to an AC motor. Because AC motor speed follows frequency, a lower frequency gives a lower speed. This is the most common form of motor speed control for AC motors.
The synchronous speed formula
Synchronous speed is the speed of the motor’s rotating magnetic field. To find it, use this formula:
Synchronous rpm = 120 × frequency (Hz) ÷ number of poles
Here are worked examples for a 4-pole motor:
- 60 Hz gives 120 × 60 ÷ 4 = 1,800 rpm.
- At 50 Hz, the result is 120 × 50 ÷ 4 = 1,500 rpm.
- Dropping to 30 Hz gives 120 × 30 ÷ 4 = 900 rpm.
- Finally, 10 Hz gives 120 × 10 ÷ 4 = 300 rpm.
What happens inside the drive
A VFD is an AC-to-DC-to-AC converter. First, a rectifier turns the incoming AC into DC on a DC bus. Next, an inverter section of IGBT transistors switches thousands of times per second. This builds a PWM waveform with controlled frequency and voltage.
Because of this design, the drive can start the motor at 0 Hz and ramp the frequency up. That gives a gentle start with low current. Most VFD inverters use IGBTs. Also, low-voltage drives cover roughly 110 to 690 V, and medium-voltage drives serve much higher voltages.
Why does a VFD change voltage as well as frequency?
The motor’s iron core can only handle so much magnetic flux. For example, if the drive drops to 30 Hz but leaves the voltage at 480 V, the core saturates. As a result, the motor draws high current and overheats.
To keep torque steady at lower speed, the drive lowers voltage in proportion to frequency. This is called volts-per-hertz. For example, to run a motor at half speed, the drive halves both voltage and frequency.
Slip and practical limits
An induction motor needs slip to make torque. So it runs a little below synchronous speed. For example, a 4-pole motor at 60 Hz turns at about 1,750 rpm under load, not 1,800.
However, the formula alone does not tell the whole story. In practice, several limits apply:
- Low-speed cooling, because a shaft-mounted fan slows down with the motor.
- Torque demand of the load.
- Field weakening above base frequency, which reduces torque.
- Motor insulation, switching frequency and cable length.
How to Control the Speed of an AC Motor
The pole count is fixed when the motor is built. So the practical way to change AC motor speed is to change the supply frequency. A VFD is the standard tool for that job.
Steps to set up a VFD for speed control
- Confirm the fit. Check that the motor and load suit a VFD, including low-speed cooling.
- Enter the nameplate data. Type it in exactly as printed.
- Run an autotune. The drive measures the motor and adjusts its model.
- Set the ramps and limits. Choose acceleration and deceleration times, plus minimum and maximum speed.
- Choose the speed reference. Options include the keypad, an analog signal, a network command or a PID loop.
Menu paths and parameter names differ by brand and model, so follow the drive manual for those. For tuning in more depth, our posts on AC electric motor speed control and energy savings, ACS355 vector tuning and the Lenze PID lesson are good next reads.
What data does a VFD need to be set up for a motor?
A VFD needs the motor nameplate data: rated voltage, current, frequency, speed and power. Wrong entries lead to poor control, nuisance trips or a hot motor. Therefore, read the nameplate on the motor itself, not a drawing or an old record.
When is a soft starter enough?
If the load runs at one speed, you may not need speed control. In that case a soft starter gives a gentle start and stop at lower cost. However, if the process ever needs a different speed, choose the VFD.
How Do You Size VFDs and Motor Protection?
Matching nameplate data is only the first step. You also need to size the drive for the duty, the site and the supply, and then protect the circuit.
How do you size a VFD beyond the nameplate?
First, size the drive by motor current, not by horsepower alone. The drive’s output current rating must cover the motor’s full-load current. Next, check the duty rating. Many drives list a normal duty rating for variable torque loads such as fans and pumps. They also list a heavy duty rating, which is lower in current but allows more overload for loads such as conveyors and crushers. Commonly, normal duty allows about 110% current for a minute and heavy duty about 150%, but the manual has the real numbers.
Then check the site. Many makers allow the full rating only up to a set altitude, often around 1,000 m (3,300 ft), and up to a set ambient temperature, often 40°C (104°F). Above those limits, derate the drive as the manual says, or pick a larger one. Finally, protect the drive input with the fuse or breaker type and size the manual lists. A line reactor or DC choke can also help on a weak or noisy supply.
How do you size motor branch-circuit protection?
Each motor circuit needs a short-circuit and ground-fault device, plus overload protection. In the United States, NEC Article 430 sets the rules. For the short-circuit device, use the full-load current from the code tables, not the nameplate. The code gives maximum ratings as a percentage of that current:
- Dual-element time-delay fuse: up to 175%.
- Inverse-time circuit breaker: up to 250%.
- Non-time-delay fuse: up to 300%.
- Instantaneous-trip breaker: up to 800%.
If the motor will not start on those sizes, the code allows higher ratings in set steps. Check Article 430 and your local amendments before you go higher.
How do you set overload protection for each controller type?
For overload protection, use the nameplate current. The code usually sets the overload at 125% of nameplate current for motors with a service factor of 1.15 or more, and 115% for many others. Confirm the limits in Article 430 for your motor.
| Controller | Short-circuit device | Overload |
|---|---|---|
| Contactor / starter | Sized from code tables, as above | Overload relay, usually trip class 10; class 20 for hard-to-start loads |
| Soft starter | Fuse or breaker type the maker lists | Built-in electronic overload with a selectable trip class |
| VFD | Input fuse or breaker the maker lists | Built-in electronic motor overload set to motor current |
A trip class describes how long the relay takes to trip under a heavy overload. For example, a class 10 relay trips within 10 seconds at 600% current. Pick a higher class when a long start would trip a lower one. Also confirm in the drive manual that its built-in overload meets your code.
Soft Starter Settings and Bypass Contactors
Soft starter settings depend on the load, so no single value fits every job. Instead, start from the maker’s defaults and adjust in small steps while you watch the start.

What soft starter settings should you use?
Set these four items first:
- Initial voltage or torque: set it just high enough that the shaft begins to turn at once. Too low wastes time and heats the motor.
- Current limit: many starters let you cap start current at several times motor current. Keep it high enough that the motor still reaches full speed.
- Ramp time: raise it for a gentler start, but not so long that the motor overheats. The 2 to 5 second range quoted earlier is a rough starting point only.
- Stop time: use a soft stop on pumps to ease flow changes. Set it longer than the coast-down time, or it has no effect.
When do you need a bypass contactor?
A bypass contactor closes once the motor reaches full speed. It carries the load current, so the SCRs stop making heat. Without a bypass, the SCRs run hot all the time. That needs more panel cooling and wastes energy.
Many soft starters have a built-in bypass. If yours does not, add an external one, or plan for the extra heat. Also note that a bypass takes the soft starter out of the circuit, so keep the overload protection active in bypass mode.
VFD Cabling, EMC and Harmonics
Good wiring keeps a VFD reliable. It also protects the motor and nearby equipment from electrical noise.
How long can the motor cable be?
The maximum motor cable length depends on the drive, the motor and the cable type. Each maker publishes a limit, so follow the drive manual. Long cables cause voltage spikes at the motor, called reflected waves, and these stress the motor insulation. Therefore, add an output reactor or a dv/dt filter when the cable is long or the motor is not inverter-duty. The manual lists when each is needed.
What cable and grounding practices reduce noise?
Use shielded cable made for VFDs between the drive and the motor. Then follow these habits:
- Terminate the shield around its full circumference at both ends, not with a long pigtail.
- Keep motor cables apart from control and signal wiring. Where they must cross, cross at 90 degrees.
- Bond the drive, the panel and the motor to ground with short, solid connections.
How do you limit harmonics?
A VFD draws current in pulses, and this adds harmonics to the supply. IEEE 519 is the common guide for harmonic limits at the point where your plant connects to the utility. To reduce harmonics, add a line reactor or DC choke at the drive input. Larger installations may need active filters or multi-pulse drives. A power quality study can show whether you need more.
DC Motor Speed Control
For a DC motor, speed is roughly proportional to armature voltage. It is inversely proportional to field flux. For this reason, an industrial DC drive uses both, and it supplies the field from a separate power supply called a field exciter.
How do you control the speed of a DC motor?
Below base speed, vary the armature voltage and hold the field at rated strength. This gives speed control from zero up to base speed. Also, keep the applied armature voltage within the nameplate rating. Torque stays constant in this range.
Older systems put a resistor in series with the armature to reduce speed. It works, but it is the older method.
What is field weakening and what are its risks?
Above base speed, the drive weakens the field by reducing field current. Less flux makes the motor speed up. As a result, you get more speed, but torque falls. Power stays roughly constant.
Industrial DC drives usually combine both methods. They use armature voltage from zero to base speed, then field weakening up to maximum speed. However, how far you can weaken the field depends on the motor and drive, so check both.
The risks are serious:
- Weakening the field too far can cause loss of commutation and motor damage.
- Losing the field while the armature is energized can let the motor overspeed until it destroys itself.
- A field-loss relay must be wired and working to catch this fault.
If a motor accelerates out of control when the armature is energized, suspect field loss. In that case, stop the drive and check the field contactor and the field-loss relay wiring. Also, a feedback device must be connected to the motor when you use field weakening. Armature feedback will not work in that range.
Stepping Motor Control
Stepping motor control moves a motor a set amount for each command. It suits simple, repeatable positioning at a modest cost.

How does stepping motor control work?
A controller sends pulse and direction commands to a stepper driver. For each pulse, the motor moves one step. The number of pulses sets the distance, and the pulse rate sets the speed.
Most stepper systems run open loop. That means the driver gets no position or velocity feedback, so it is essentially running blind. Even so, stepper motors are easy to control this way, and they have high holding torque.
Most stepper drivers also use microstepping. This splits each full step into smaller equal segments. As a result, motion is smoother, vibration drops and resolution rises beyond a few hundred steps per revolution. For example, some drivers offer microstepping up to 1/256.
Why do stepper motors lose steps and how do you prevent it?
An open-loop stepper loses steps when the load torque exceeds the motor’s torque. The driver cannot detect this, so the position error stays hidden. An undersized motor makes the problem worse, and a mechanical blockage looks the same to the driver.
You have three remedies:
- Size the motor with margin over the load.
- Add an encoder, so the controller can measure position and re-command the difference.
- Use a closed-loop stepper driver, which compares command pulses with encoder data and corrects.
Should I use a stepper or a servo?
The choice comes down to cost, simplicity and feedback. A stepper is simple and low in cost, and it works well when the load is predictable and the motor has torque to spare. In contrast, a servo adds feedback and correction as part of its design. If lost steps would cause scrap or damage, lean toward closed loop. Next, the following section covers servo systems.
How Do You Control a Servo Motor?
A servo drive compares a command with feedback from an encoder or similar device on the motor. It then adjusts the current to the motor to correct the error. The command is usually pulse/direction, analog or a network signal.
In concept, a servo is closed-loop control. The system senses the rotor position and drives the motor toward its target as quickly as it can. That is the main difference from an open-loop stepper.
The details vary a lot between makers. Feedback types, tuning steps, limits and homing all depend on the drive and motor. So use the servo manufacturer’s manual for setup, and do not copy settings from another brand.
Compared with a stepper, a servo costs more and takes more setup. In return, it corrects errors as they happen. Likewise, compared with a VFD, a servo is built for position and fast motion, not just speed.
How Do You Size a Stepper or Servo System?
Sizing starts with the load. Work out the torque, the speed and the inertia the motor must move, then add margin.
How much torque margin do you need?
Compare the load torque, including friction and acceleration, with the motor’s torque at the speed you need. Stepper torque falls as speed rises, so read the maker’s speed-torque curve, not just the holding torque. Because an open-loop stepper hides lost steps, keep a generous margin. Many designers leave 50% or more, but follow the maker’s advice. A servo can use a smaller margin, but it must still handle its peak torque.
What is inertia matching?
Inertia is how hard a load resists changes in speed. Compare the load inertia with the motor’s rotor inertia. A lower ratio gives better control and less overshoot. Makers often suggest keeping the ratio low, and they list their limits. A gearbox helps, because it reduces the inertia the motor sees by the square of the gear ratio.
How do you choose encoder resolution, tune and home?
Pick an encoder whose counts per turn give a step finer than the position accuracy you need. Then tune the servo. Start with the maker’s auto-tune if it has one. Otherwise, raise the gains slowly until the motor starts to buzz, and then back off.
For homing, the axis moves to a home switch or an encoder index mark, and the controller sets that point as zero. Always home after power-up if the system has no absolute encoder.
| Point | Stepper | Servo |
|---|---|---|
| Feedback | Usually none (open loop) | Always (closed loop) |
| Cost and setup | Lower | Higher |
| Lost steps | Possible, unseen | Corrected |
| Best fit | Predictable loads | Fast, varying loads |
Stopping, Braking and Reversing
How a motor stops matters as much as how it starts. The right method depends on the load and the control.

How do braking resistors and regeneration work?
When a VFD slows a motor faster than the load slows on its own, or when a load pulls the motor, the motor acts as a generator. That energy raises the DC bus voltage. A braking resistor, switched by a brake chopper in the drive, burns off that energy as heat. Alternatively, a regenerative drive sends the energy back to the supply. If you see overvoltage trips on stopping, a longer deceleration time is the first fix.
How do you reverse and soft stop a motor?
A VFD reverses a motor through a command, with no wiring changes. A contactor-based reversing starter swaps two phases with two contactors. Add an interlock so both can never close together. A soft starter can ease a stop on a pump, but it does not brake the load.
Which motors work with which controls?
- Inverter-duty motors: built with insulation that handles drive voltage spikes. Use them with long cables or frequent drive use.
- Single-phase motors: usually not suited to a standard VFD. Capacitor-start types can be damaged, so check with the drive maker.
- Permanent-magnet motors: need a drive that supports permanent-magnet control.
- Brushless DC motors: use a matching brushless DC drive, not a standard VFD.
What Is a Motor Control Center (MCC)?
A motor control center is a floor-mounted assembly of one or more enclosed vertical sections. It usually has a common horizontal power bus. In practice, it mainly holds combination motor control units, such as starters and drives.
Why use a motor control center?
An MCC groups motor control, protection, power distribution and monitoring in one coordinated lineup. It centralizes starting, stopping, speed control and monitoring for many motors. Also, drives and soft starters can be installed as MCC units, so one lineup can hold several kinds of motor control equipment.
What standards apply to a motor control center?
In North America, MCCs are built and listed to UL 845 and NEMA ICS 18. By contrast, international projects follow IEC 61439-1 and IEC 61439-2. Some makers also list compliance with CSA C22.2 No. 14.
NEMA ICS 18 sets several rules you should know:
- Each section must carry a short-circuit rating, in maximum rms symmetrical amperes, with a maximum voltage.
- Two classes describe how much control integration the maker supplies.
- Three wiring types describe where field wiring terminates.
Class I is a mechanical grouping of units on the common bus. It has no interwiring or interlocking between units or to remote devices. Only diagrams of the individual units come with it. Class II adds more integration, so check the maker’s guide for what it includes.
For brand detail, our posts on Eaton and Cutler Hammer MCCs are a good place to look.
Safety Before You Work on Motor Controls
Motor controls hold lethal energy, even when they look off. Follow your site procedure and these basics.
What lockout/tagout steps apply?
- Shut off the control and open the disconnect.
- Lock and tag the disconnect with your own lock.
- Test with a rated meter to prove every conductor is dead. Test the meter on a known source before and after.
- Only then begin work.
Why wait for DC bus capacitors to discharge?
A VFD keeps voltage in its DC bus capacitors after power is off. The drive label or manual states a wait time, often several minutes. After that wait, measure the DC bus voltage at the terminals the manual names. Do not touch anything until the meter reads a safe level.
What about arc flash in an MCC?
Opening or racking an energized MCC unit can cause an arc flash. Read the arc-flash label on the equipment, and wear the personal protective equipment it calls for. NFPA 70E covers these rules. Whenever you can, de-energize the unit before you open it.
How to Choose the Right Motor Control
Start from the need, then work toward the device. This table gives a first pass.
| Need | Likely choice |
|---|---|
| On/off only | Contactor or starter |
| Gentle start, fixed speed | Soft starter |
| Variable speed, AC motor | VFD |
| Variable speed, DC motor | DC drive |
| Point-to-point position | Stepper driver |
| High-dynamic motion | Servo drive |
What is motor speed control and which method fits which motor?
Motor speed control means holding or changing a motor’s speed on purpose. The method depends on the motor type. For example, an AC induction motor uses a VFD to vary frequency. A DC motor, on the other hand, uses a DC drive to vary armature voltage and, above base speed, the field. Finally, stepper and servo motors set speed through their command signal.
How do I choose the right motor control for my application?
Work through this checklist before you buy:
- Motor type and nameplate data.
- Load type, constant torque or variable torque.
- Starting frequency and duty cycle.
- Supply voltage.
- Enclosure type for the environment.
- Short-circuit rating of the installation.
- Feedback needs.
Also size the control for the motor. For example, a soft starter’s current rating must be at least the motor’s current rating, and ratings rise with motor current, voltage and power.
How much do motor controls cost and how long do they last?
In rank order, a starter costs the least, a soft starter sits in the middle and a VFD costs the most. One vendor guide puts a VFD at roughly two to three times the cost of a soft starter. Treat that as a rough range, because prices vary by size and brand.
Electronic units can last many years. For example, a vendor guide estimates 15 to 20 years, with capacitors needing replacement after about 7 to 10 years. However, those are estimates, not guarantees. Heat, dust and load all change the real number.
Common Mistakes and When to Call for Repair
Most problems with motor controls trace back to setup, not hardware. Watch for these mistakes:

- Wrong nameplate data or no autotune. As a result, the drive controls the motor poorly.
- Low speed without cooling. A motor that runs slowly for long periods can overheat.
- Mixing up the devices. Using a VFD only as a soft starter wastes money. Expecting a soft starter to control speed will not work.
- An undersized stepper. The motor loses steps and the error goes unseen.
- No DC field-loss protection. This risks overspeed.
- Using the formula alone. However, voltage, slip and torque limits still apply.
What do common VFD fault codes mean?
Code names and numbers differ by brand, so use the fault list in your manual. Still, most faults fall into a few groups. Always de-energize and wait for the DC bus to discharge before you open anything.
- Overcurrent: the drive saw too much current. Check for a short in the motor or its cable, a jammed load, or an acceleration time that is too short.
- Overvoltage: the DC bus rose too high. Check for a deceleration time that is too short, an overhauling load, or high line voltage. A braking resistor may help.
- Undervoltage: the DC bus fell too low. Check for a supply sag, a lost phase, a blown input fuse or loose connections.
- Overtemperature: the drive or motor ran hot. Check for blocked vents, dirty heat sinks, failed fans, high ambient heat or an overloaded motor.
- Ground fault: current leaked to ground. Disconnect the motor cable and test the cable and motor insulation to find the fault.
When should you call for repair?
Call for help when a drive trips again right after a reset, or when a DC drive shows field faults. Also call when a servo drive will not hold position, or when you see burn marks or swollen capacitors. First, stop, and do not keep resetting a drive that keeps faulting. In addition, Precision Electric repairs drives, DC drives and servo drives, and our technicians can help you decide between repair and replacement.
Where to Find Manuals, Software and Standards
You can find most of what you need from a few places.
- Manufacturer manual libraries. Rockwell Automation keeps its CENTERLINE 2100 MCC specification in its Literature Library. Eaton publishes a low-voltage MCC design guide. Most makers also offer drive software for setup and parameter backup, so check the maker’s site for your model.
- Standards bodies. Buy or access NEMA ICS 18 and UL 845 from NEMA and UL. Do not rely on unofficial copies.
- Component maker documents. Texas Instruments publishes open-loop stepper design resources and an application note on stepper motion smoothness. Oriental Motor’s blog also has an article on closed-loop steppers.
Frequently asked questions
What is a motor control?
It is the equipment between the power supply and a motor that starts and stops it. Depending on type, it also controls acceleration, speed or stopping position. The range runs from a contactor, through a soft starter, to a VFD, DC drive, stepper driver or servo drive.
How does a VFD control motor speed?
A VFD changes the frequency and voltage it sends to an AC motor. Because speed follows frequency, a 4-pole motor at 30 Hz has a synchronous speed of 900 rpm instead of 1,800 rpm at 60 Hz. In addition, the drive lowers voltage along with frequency to avoid saturating the motor.
How do you control the speed of an AC motor?
Because the pole count is fixed, vary the supply frequency with a VFD. First, enter the motor nameplate data, run an autotune, and set ramps and speed limits. Then give the drive a speed reference. A soft starter, however, controls only starting and stopping.
How do you control a servo motor?
A servo drive compares a command with feedback from an encoder or similar device on the motor. It then adjusts the current to the motor to correct the error. The command is usually pulse/direction, analog or a network signal.
How do you control the speed of a DC motor?
Vary the armature voltage to control speed from zero to base speed, with the field held at rated strength. Above base speed, weaken the field. As a result, you get more speed but less torque. Never lose the field supply while the armature is energized.
What is a motor control center?
It is a floor-mounted assembly of enclosed vertical sections with a common power bus. It mainly holds combination motor control units, such as starters and drives. In North America, MCCs are built and listed to UL 845 and NEMA ICS 18.
Motor controls range from a simple contactor to a servo drive, and the right one depends on the job, the motor and the load. First, match the device to the need, then set it up from the nameplate and the manual, and protect the motor against the faults that fit your type. If you need help choosing, repairing or replacing motor control equipment, contact Precision Electric for a quote or repair.