Three Phase Motor Wiring Diagram: Connect 3, 6, 9 and 12 Leads
A three phase motor wiring diagram shows how to join the winding ends so the motor matches your supply. This guide helps you pick the right diagram, wire it, check each stage and start the motor safely. It also covers single-phase motors, because many people land here with one of those.
On this page
- How to read a three-phase motor wiring diagram
- What you need before you start
- Safety first: isolate and prove the circuit is dead
- How to wire a three-phase motor, step by step
- How do I wire a 3 phase motor?
- Step 1: Read the nameplate and match the supply voltage
- Step 2: Open the terminal box and identify the leads
- How do I identify unmarked leads on a 9- or 12-lead motor?
- Step 3: Make the connections for your lead count
- Six-lead and IEC terminal links
- Nine- and 12-lead notes
- Step 4: Connect the supply, overload and ground (three phase wiring)
- What conductor, breaker and overload size should I use?
- Step 5: Test the motor before energizing
- Step 6: First start and rotation check
- Wye vs delta: what changes and why it matters
- Star-delta (wye-delta) starter wiring: six conductors, no links
- How to reverse a three-phase motor
- Two-speed and part-winding-start motor wiring
- Three-phase motors on a VFD or a 50 Hz supply
- Single-phase motor wiring diagram (1 phase)
- Common three-phase motor wiring mistakes
- Troubleshooting and when to call for repair
- Where to find the wiring diagram for your motor
- Frequently asked questions
How to read a three-phase motor wiring diagram
What a three phase motor wiring diagram shows
A three phase motor wiring diagram shows how the winding ends are joined with links or wire nuts. It also shows which ends take L1, L2 and L3. However, it does not show the starter or the control circuit.
So always use the connection diagram on the nameplate or inside the terminal box lid. Because stud layouts differ by manufacturer, a diagram for another motor can mislead you. In this article, three phase wiring means two things: the lead connections at the motor, and the power path from the disconnect to the motor.
Terminal numbers: NEMA T1–T12 and IEC U1/V1/W1
NEMA motors mark leads T1 to T9, plus T10 to T12 on 12-lead motors. IEC motors use U, V and W for the main terminals. So a 3 phase motor connection diagram may use either system.
For example, on six-lead motors the two systems match like this:
- T1 = U1
- T2 = V1
- T3 = W1
- T4 = U2
- T5 = V2
- T6 = W2
However, do not guess the shaft direction from the numbers. NEMA MG 1 says terminal markings on polyphase induction machines are not related to the direction of rotation. As a result, you must check rotation on every job.
Which diagram do you need: 3, 6, 9 or 12 leads?
First, count the leads. Next, read the nameplate voltage, which may be single or dual, such as 230/460 V. Then match both to the supply you measured.
| Leads | What it means | Connection choices |
|---|---|---|
| 3 | Connected inside and fixed to one voltage | T1, T2, T3 to L1, L2, L3 |
| 6 | Dual voltage, wye or delta | Wye on the higher voltage, delta on the lower |
| 9 | Common dual-voltage industrial motor | High or low voltage, wye or delta |
| 12 | Most flexible | Wye or delta, series or parallel |
In addition, on a 9-lead motor, the manufacturer connects the winding as wye or delta inside. As a result, nine-lead delta, 9-lead wye and 12-lead wye motors can all be wired for 240 or 480 V.
What you need before you start
First, gather the right information and tools before you open the terminal box. As a result, you save time and prevent mistakes.

- The nameplate and the connection diagram from the terminal box lid.
- A true-RMS multimeter with a CAT rating that suits the voltage.
- A voltage tester that is not a non-contact tick tracer.
- A megohmmeter for insulation testing.
- A phase rotation meter, or a plan for a brief jog.
- Lugs, wire nuts or links that fit the lead size.
- A torque screwdriver or wrench, plus lead tags.
- A starter and overload set from the nameplate current for the connection you choose.
Also measure the supply voltage at the disconnect. Do not assume it. For conductor size, breaker size and torque values, use the nameplate, the manufacturer’s manual and the applicable electrical code. Step 4 below shows a worked example.
Safety first: isolate and prove the circuit is dead
Lockout/tagout, often called LOTO, keeps a circuit off while you work. OSHA 29 CFR 1910.147 covers hazardous energy control, and 1910.333 covers electrical equipment. In addition, the current NFPA 70E covers electrical safety work practices. However, a visual check of the disconnect alone does not prove the circuit is dead.
- Lock out and tag out the supply at the disconnect.
- Check your meter on a known live source.
- Test phase-to-phase and phase-to-ground at the point of work.
- Check the meter again on the known live source. This is the test-test-test, or live-dead-live, method.
- Discharge any capacitors, and think about temporary grounding where induced voltage or stored energy is possible.
Non-contact detectors are for troubleshooting only. Shielded cable or a grounded conductor inside the cable can give false readings. As a result, they do not prove that voltage is absent, so use a direct-contact meter.
Also, keep in mind that the testing step is itself energized work. It needs a qualified person and rated PPE.
How to wire a three-phase motor, step by step
This process works for any three phase motor wiring diagram. Also, each step ends with a check you must pass before you move on.

- Read the nameplate and match the supply voltage.
- Open the terminal box and identify the leads.
- Make the connections for your lead count.
- Connect the supply, overload and ground.
- Test the motor before you energize it.
- Start the motor and check rotation.
How do I wire a 3 phase motor?
To wire a 3 phase motor, start with the 3 phase motor wiring diagram on the nameplate or inside the terminal box lid. First, match the nameplate voltage to your supply. Next, make the links your lead count calls for. Then connect L1, L2 and L3 through the starter and overload, and ground the frame.
Finally, test the windings and check the rotation. The six steps below cover each stage in detail.
Step 1: Read the nameplate and match the supply voltage
On a dual-voltage plate, the lower voltage is delta and the higher voltage is wye (also called star). For example, take a 400 V supply. A plate reading Y 380–420 V / D 220–240 V means star. A plate reading Y 660–720 V / D 380–420 V means delta.
Next, the voltage ratio tells you the lead count. Six-lead delta/wye motors use a ratio of √3, such as 220/380 or 380/660. In contrast, nine- and 12-lead motors use a 2:1 ratio, such as 230/460.
Also note the full-load amps for the connection you chose. Because delta line current is √3 times star line current, overload settings follow the connection.
Check: the nameplate voltage and frequency match the supply you measured.
Step 2: Open the terminal box and identify the leads
First, count the leads and confirm the numbering matches the diagram in the lid. If numbers are missing, tag each lead before you disconnect anything. Then map the windings with a multimeter in resistance mode.
Check: lead count and markings agree with the diagram. If they do not, stop and call a repair shop. Also, do not open the motor or rewire the winding inside it.
How do I identify unmarked leads on a 9- or 12-lead motor?
Power must be locked out and proven dead first. Then tag every lead and use the ohms range to find which leads have continuity. Each winding section has a small, equal resistance, so compare readings instead of looking for one fixed number.
- Six leads: you find three separate pairs, and all three pairs read about the same.
- Nine leads, wye inside: you find three pairs plus one group of three leads that all connect to each other.
- Nine leads, delta inside: you find three groups of three leads. In each group, two readings match and the third reads about double.
- Twelve leads: you find six pairs, and all six read about the same.
In a group of three, the lead that reads low to both others is the shared junction. However, these tests only sort the leads into groups. Giving each lead its correct number needs a low-voltage polarity test or the maker’s data. If you cannot do that with confidence, send the motor to a repair shop, because a wrong guess can damage the winding.
Step 3: Make the connections for your lead count
This is the core of any 3 phase motor lead connections job. For reference, use the table below, but let the diagram on your motor win if the two differ.
| Motor | Connection | Links and line connections |
|---|---|---|
| 3 leads | Fixed | T1, T2, T3 to L1, L2, L3. No links. |
| 6 leads | Wye | L1, L2, L3 to T1, T2, T3. Join T4-T5-T6. |
| 6 leads | Delta | L1 to T1+T6, L2 to T2+T4, L3 to T3+T5. |
| 9 leads | Wye, high voltage | L1, L2, L3 to 1, 2, 3. Join 4&7, 5&8, 6&9. |
| 9 leads | Wye, low voltage | L1 to 1+7, L2 to 2+8, L3 to 3+9. Join 4-5-6. |
| 9 leads | Delta, high voltage | L1, L2, L3 to 1, 2, 3. Join 4&7, 5&8, 6&9. |
| 9 leads | Delta, low voltage | Group 1-6-7, 2-4-8 and 3-5-9. Each line goes to one group. |
| 12 leads | Wye, high voltage | L1, L2, L3 to 1, 2, 3. Join 4&7, 5&8, 6&9. Join 10-11-12. |
| 12 leads | Wye, low voltage | L1 to 1+7, L2 to 2+8, L3 to 3+9. Join 4-5-6-10-11-12. |
| 12 leads | Delta, high voltage | L1 to 1+12, L2 to 2+10, L3 to 3+11. Join 4&7, 5&8, 6&9. |
| 12 leads | Delta, low voltage | L1 to 1, 6, 7, 12. L2 to 2, 4, 8, 10. L3 to 3, 5, 9, 11. |
Six-lead and IEC terminal links
For example, on an IEC six-terminal box, delta links are U1-W2, V1-U2 and W1-V2. For star, join W2, U2 and V2 together. These match the NEMA connections above, so the same logic applies.
Nine- and 12-lead notes
However, beware third-party walkthroughs for 9-lead motors. Some say high-voltage wye ties 4-5-6 and leaves 7-8-9 taped. In fact, that conflicts with the standard layout, where 4-5-6 are joined for low-voltage wye. So use the nameplate or lid diagram as the final authority.
High voltage puts the winding sections in series, and low voltage puts them in parallel. Also, the table covers every standard single-speed case, but a maker may number leads differently. So check the plate diagram before you make any link.
Also, insulate every unused lead separately. Then torque terminals to the manufacturer’s value.
Check: every lead is used exactly once, and the connection matches the plate diagram for your voltage.
Step 4: Connect the supply, overload and ground (three phase wiring)
Good three phase wiring follows a clear power path. It runs from the disconnect to short-circuit protection, then the contactor or starter, then the overload relay, and last to motor terminals T1 to T3. Finally, connect the protective earth from the motor frame to the panel ground.
Check:
- The ground path is continuous and low-resistance from frame to panel.
- All terminal screws are tight.
- No conductor is pinched under the cover.
- The conduit entry is secure.
What conductor, breaker and overload size should I use?
In the US, NEC Article 430 sets the rules, so check your local code too. For conductors and short-circuit protection, use the full-load current in NEC Table 430.250, not the nameplate. For the overload, use the nameplate current.
- Conductors: at least 125% of the table current.
- Overload trip: up to 115% of nameplate amps for a motor with a 1.15 service factor or a temperature rise of 40°C or less. Otherwise, up to 125%.
- Short-circuit protection: an inverse-time breaker may go up to 250% of the table current. A dual-element fuse may go up to 175%.
For example, take a 10 hp, 460 V three-phase motor. Table 430.250 lists 14 A. So the conductors need at least 17.5 A of ampacity, and the breaker can go up to 35 A. Now suppose the plate reads 13 A with a 1.15 service factor. Then the overload can trip at up to 15 A.
Next, pick the wire size from NEC Table 310.16 at the temperature rating of your terminals. These limits are maximums, so a smaller setting is fine if the motor still starts. In addition, the manufacturer’s manual may set tighter limits.
Step 5: Test the motor before energizing
First, winding resistance should be balanced between phases. Next, run an insulation resistance test with a megohmmeter. AEMC says to disconnect the field coils where possible. For example, on a delta 9-lead motor, that means removing the wire nuts from 4 and 7, 5 and 8, and 6 and 9.
The manufacturer’s or your company’s limit comes first. If you have neither, IEEE 43 gives minimums for a one-minute reading. For motors rated under 1000 V, test at 500 V DC. The minimum is 5 megohms for random-wound windings and 100 megohms for form-wound windings. Also, temperature changes the reading, so correct it to 40°C and compare against past tests. A reading below the minimum is a fail.
Check: resistance is balanced, nothing shorts to the frame, and insulation resistance is above the limit.
Step 6: First start and rotation check
First, close the cover and remove locks per your procedure. Then bump the motor, with the load uncoupled where possible. Check rotation with a phase rotation meter, or jog it briefly and watch the shaft.
Next, measure voltage between each pair of phases at the motor terminals. All three pairs should read the same. Then compare the line current on each phase to the nameplate amps.
However, a hum or uneven current points to a wrong link or a missing phase. So stop and re-check the connections.
Wye vs delta: what changes and why it matters
In a wye connection, the winding ends meet at a neutral point. Each winding sees phase voltage. In delta, however, each winding sees the full line voltage.
For example, WEG shows that delta puts full line voltage (220 V) on each winding. In star, a 380 V line can feed the same winding, which still sees 220 V. Because of this, any wye delta motor wiring diagram depends on the supply voltage, not on preference.
For the same winding, delta line current is √3 times the wye line current. So set the overload for the connection you use. In addition, a wrong connection for the supply voltage can cause weak magnetic flux or winding damage, so never run a six-terminal motor in the wrong connection.
Star-delta (wye-delta) starter wiring: six conductors, no links
A star delta motor wiring diagram looks different from a fixed connection. With a star-delta starter, you fit no links in the terminal box. Instead, six conductors run from the starter to the motor, and the starter switches the windings from star to delta.
However, the motor must meet these conditions:
- It must have at least six terminals.
- Its delta voltage must match the supply, such as 400/690 V on a 400 V supply.
- It must have a dual-voltage winding.
As a result, a motor connected in delta inside, with a three-lead terminal box, cannot use this starter without rewiring inside.
Star starting cuts starting current to about 25–33% of the delta value, according to WEG. Torque falls too, so the load torque must still be high enough to accelerate the machine. As a result, this suits light starts.
Check: with the motor running in delta, measure voltage between each phase pair at the terminals. However, a hum after the switch to delta points to the delta contactor wiring.
How do I wire the star-delta starter itself?
The starter uses three contactors and a timer. Wire them like this, using IEC marking for the motor ends:
- The main contactor connects L1, L2 and L3 to U1, V1 and W1.
- The delta contactor joins U1 to W2, V1 to U2 and W1 to V2.
- The star contactor joins W2, U2 and V2 together.
In the control circuit, the start button closes the main and star contactors and starts the timer. When the time ends, the star contactor drops out. After a short pause, the delta contactor closes. Also, the star and delta contactors must be interlocked, both electrically and ideally mechanically. If both close together, they short the supply.
The main and delta contactors carry about 58% of the motor line current, and the star contactor carries about one third. However, follow the maker’s selection table. If the overload sits in the winding leg, set it to about 58% of the line current. There is no standard timer setting. Instead, set it long enough for the motor to reach close to full speed in star, then watch the current spike at the switch and adjust.
How to reverse a three-phase motor
To reverse a three-phase motor, lock out the power first. Then swap any two of the three supply lines at the starter, contactor or disconnect. However, do not swap leads inside the terminal box.

Also, moving the supply to a different terminal group, with links repositioned, does not reverse rotation by itself. Only the phase sequence does. In addition, a Brook Crompton terminal box label says the same: change over any two supply lines.
For regular reversing, use a forward/reverse starter. It has two three-pole contactors, each giving a different phase sequence. Also, an interlock stops both closing together.
After any change, confirm direction with a phase rotation meter or a brief jog while you watch the driven load.
Two-speed and part-winding-start motor wiring
How are two-speed motors wired?
A two-speed motor has either one winding that changes poles (a consequent-pole motor) or two separate windings. A consequent-pole motor has six leads. For constant-torque duty, low speed takes the supply on T1, T2 and T3 with T4, T5 and T6 left open. High speed joins T1, T2 and T3 and puts the supply on T4, T5 and T6. However, variable-torque and constant-horsepower types wire differently, so use the plate diagram.
A two-winding motor has a separate set of three leads for each speed. In both cases, use a two-speed starter with interlocked contactors, so the two speeds can never close together. Also, each speed needs its own overload setting from the nameplate.
How is a part-winding-start motor wired?
A part-winding motor has its winding split into two equal halves. On a 9-lead motor wired for the lower voltage, the first contactor puts the supply on T1, T2 and T3. That is half the winding. After a short delay, the second contactor puts the supply on T7, T8 and T9. This adds the other half in parallel. As a result, starting current drops, but so does starting torque.
The delay must be short, so do not leave the motor on half winding. Also, use the maker’s diagram for lead numbers, because they vary by model.
Three-phase motors on a VFD or a 50 Hz supply
What changes when the motor runs on a VFD?
A variable frequency drive (VFD) replaces the starter. You wire the drive output terminals, usually U, V and W, to the motor leads. First, make the motor connection for the voltage the drive puts out, not the line voltage feeding the drive. Next, use cable made for drives and bond the ground at both ends.
Also, do not open a contactor between the drive and the motor while the drive runs. To reverse, swap any two output leads or change the direction setting in the drive. In addition, set the drive’s motor data and overload from the nameplate. A motor with a long cable or a high-voltage winding may need an inverter-duty rating.
What if the supply is 50 Hz or non-standard?
Synchronous speed equals 120 times the frequency, divided by the number of poles. So a 4-pole motor runs near 1800 rpm at 60 Hz and 1500 rpm at 50 Hz. Some plates list both frequencies with their own voltage and amps. If yours does not, ask the manufacturer before you run it on a different frequency. A wrong voltage and frequency pair can overheat the motor.
For other supply voltages, use the nameplate range. For example, a plate reading 380–420 V covers a 400 V supply. However, a supply outside every listed range needs a different motor or a transformer.
Single-phase motor wiring diagram (1 phase)
What a single-phase diagram looks like
A 1 phase motor wiring diagram has a main winding and a start winding. It usually adds a capacitor and a centrifugal switch. That switch opens the start circuit once the motor is up to speed.

The common types differ in how those parts connect:
- Split-phase: main and start windings, with a centrifugal switch.
- Capacitor-start: the start capacitor sits in series with the centrifugal switch.
- Permanent split capacitor (PSC): a capacitor stays in the circuit. A smooth spin-down with no click suggests this type.
- Capacitor-start/capacitor-run: uses both a start and a run capacitor.
In addition, dual-voltage motors (115/230 V) put the main winding in parallel for low voltage and in series for high voltage.
However, any motor wiring diagram single phase is less standard than a three-phase one. Many makers use colour-coded leads and publish a diagram for each model. Lafert North America and Bison Gear both post these. So use the diagram for your exact motor.
What are the NEMA single-phase terminal numbers and 115/230 V connections?
NEMA marks the main winding T1 to T4 and the start winding T5 to T8. A thermal protector, if fitted, uses P1 and P2. The main winding has two halves: T1-T2 and T3-T4.
- 115 V (parallel): join T1 with T3 and T2 with T4. Then connect one line to the T1-T3 pair and the other to the T2-T4 pair.
- 230 V (series): join T2 with T3. Then connect the lines to T1 and T4.
However, the start winding leads, the protector and the capacitor wiring differ by motor. Wire colours are not standard either, so do not rely on colour alone. Use the maker’s diagram for the start circuit.
How can I tell whether a motor is single-phase or three-phase?
Look for a start or run capacitor, a centrifugal switch, or a terminal block with five to eight terminals. Any of these confirms single-phase. In contrast, a three-lead motor with no capacitor and a 208-230/460 plate is three-phase.
How do I reverse a single-phase motor?
Swapping the line wires does nothing. Instead, reverse the start winding leads relative to the run winding. This works on capacitor-start, capacitor-run and capacitor start/run types.
However, the leads to swap vary by model. For example, Bison Gear diagrams give a different instruction for different motors, and Lafert’s differ by series. Also, some motors are not reversible at all. So follow the diagram for the exact motor.
For a reversing switch, a DPDT switch or reversing contactor must switch the start winding independently of the main winding.
Check: find the winding pairs by resistance. The run winding is the lower-resistance pair, and the start winding is the higher. Also, discharge capacitors before you touch them.
Common three-phase motor wiring mistakes
These errors show up again and again on service calls:
- Misreading the nameplate. The higher voltage is wye, and the lower is delta.
- Jumpering the wrong lead pairs on 9- and 12-lead motors, or leaving unused leads bare.
- Using a diagram from a different motor, or a third-party diagram that does not match the plate.
- Assuming the T-numbers set the rotation direction.
- Reversing by swapping leads inside the terminal box.
- Setting the overload for the wrong connection’s current.
- Skipping the proof-of-dead test, or using a non-contact tester as proof.
- Using star-delta starting on a motor that cannot run in delta at the supply voltage.
Troubleshooting and when to call for repair
What if the motor hums, will not start, or has lost its lead markings?
If the motor hums or will not start after a connection change, re-check the links. Then measure voltage between each phase pair. Next, if it still fails, de-energize and prove it dead before you touch anything.

When lead numbers are missing, tag the leads and map the windings by resistance. Still, if you cannot match them to a diagram, stop. Guessing can damage the winding.
When should I send the motor for repair instead of rewiring it?
Send the motor to a repair shop if you find any of these:
- Low insulation resistance.
- Unbalanced winding resistance.
- Lead numbers that are missing or unreadable.
- A burnt winding smell.
Because these point to a fault inside the motor, do not try to fix it at the terminal box. In addition, Precision Electric repairs motors, so you can send yours in rather than open it.
Where to find the wiring diagram for your motor
First, use the nameplate and the label inside the terminal box lid. Next, use the manufacturer’s connection diagrams, searched by catalog or model number. For example, the WEG download center has a specification guide for electric motors. Also, Lafert North America and Bison Gear post single-phase connection diagrams.
For testing, the AEMC note on three-phase dual-voltage motor insulation resistance is a good guide. In addition, NEMA MG 1 defines the standard terminal markings and internal wiring diagrams for single-phase and polyphase motors. For sizing, use NEC Article 430 and its tables. Finally, our other posts on VFDs, nameplates and phase converters cover those topics in more depth.
Frequently asked questions
How do I wire a 3 phase motor?
Read the nameplate for voltage and lead count, match it to the supply, and make the links for that connection. On a 6-lead motor, wye joins T4-T5-T6 and delta joins T1+T6, T2+T4 and T3+T5. Then connect L1, L2 and L3 to the starter and motor. Before any of this, lock out and prove the circuit dead.
How do I know if my motor should be wired wye or delta?
Check the nameplate. On a dual-voltage plate, the lower voltage is delta and the higher is wye (star). If your supply matches the lower voltage, wire delta. For the higher voltage, wire wye.
How do I reverse a three-phase motor?
Lock out the power, then swap any two of the three supply lines at the starter or disconnect. Also, do not swap leads inside the motor terminal box. Lastly, confirm the new direction with a phase rotation meter or a brief jog.
What is the difference between a single-phase and a three-phase motor wiring diagram?
A three-phase diagram links winding ends and connects L1, L2 and L3. A single-phase diagram also includes a start winding, a capacitor and usually a centrifugal switch. In addition, a single-phase motor reverses by swapping the start winding leads, and the exact leads vary by model.
Can I use a three-phase wiring diagram from the internet for my motor?
Only if the lead numbering and voltage match your nameplate. Otherwise, use the diagram on the nameplate or in the terminal box lid, or get one from the manufacturer for your model, because layouts vary.
The right three phase motor wiring diagram comes from your motor, not from a guess. Count the leads, read the nameplate, match the supply, and check after every stage. If your motor fails a test or the markings are gone, Precision Electric can help with repair, a quote or the parts you need.