ABB ACS310 Guide: Status, Ratings, Manuals, Wiring and Faults

Isometric illustration of an open gray enclosure housing a drive unit, coiled cable, terminal block, and DIN rail.

If you have an ABB ACS310 ABB drive on a spec sheet or in a panel, you need to know three things: can you still buy one, how do you set it up, and what do you do when it faults. This guide covers the lifecycle status, ratings, manuals, wiring, start-up, pump control and fault codes, and it explains your replacement options. Also, we tied the details to ABB documents rather than blog summaries.

On this page

Is the ABB ACS310 still available? Lifecycle status

No, ABB no longer sells new units. ABB’s life cycle statement for the ACS310 and ACS355 lists both as Obsolete since 1 January 2026 and says the product is no longer available. So treat that as the current status for the ABB ACS310 drive.

Is the ABB ACS310 discontinued or obsolete?

Yes, it is both. However, two ABB notices give different dates. An earlier sales ramp-down announcement planned the Limited phase from 1 July 2025 and the Obsolete phase from 1 July 2026. Because the newer life cycle statement says 1 January 2026, use that one.

The ramp-down announcement also gave last time buy and last delivery dates by region. For example, the USA centre of excellence had a last time buy of 30 June 2025 and a last delivery of 31 December 2025.

What obsolete means for your plant

In short, new supply from ABB is over. As a result, any remaining ABB ACS310 inverter stock comes from distributors and surplus. We hold some models, and the list is in the buying section below.

In practice you have two realistic paths. First, you can repair an installed unit. Second, you can plan a move to a current ABB drive. Both are covered later in this guide, and our repair team can help with either.

What the ACS310 is and where it fits

What is the ABB ACS310 used for?

The ABB ACS310 is a wall or cabinet mountable drive for AC induction motors. ABB built it for variable torque loads, which means centrifugal pumps and fans. Also, it uses scalar U/f control, so it does not use vector control.

Centrifugal pump driven by an electric motor beside an orange wall-mounted drive enclosure, with a wall fan above.
Conduit runs from the control box along the wall to the motor terminal box.

For these loads, the ACS310 pump and fan drive includes the following features:

  • PFC and SPFC multi-pump control
  • Built-in PID control
  • Pipefill and pump cleaning functions
  • A load analyzer and energy savings display in kWh and CO2
  • Coated control boards, automatic fault reset and protection against unstable supply networks

What power range and voltages does the ACS310 cover?

Overall, the range is 0.37 to 22 kW (0.5 to 30 hp). Supply frequency is 48 to 63 Hz, and the supply options are:

  • 1-phase 200-240 V ±10%, from 0.37 to 2.2 kW (0.5 to 3 hp)
  • 3-phase 200-240 V ±10%, from 0.37 to 11 kW (0.5 to 15 hp)
  • 3-phase 380-480 V ±10%, from 0.37 to 22 kW (0.5 to 30 hp)

Where it fits and where it does not

Use the ABB ACS310 VFD for centrifugal pumps, fans and boosters. However, do not pick it for conveyors, crushers or positive displacement pumps. Because ABB positions it for variable torque, those loads need a different drive. Our ABB VFD selection guide helps with that choice.

A drive saves energy because it slows the motor instead of throttling flow with a valve or damper. For example, ABB’s catalog claims energy savings of up to 50% in pumping compared with direct-on-line starting. That is a vendor claim, so your result depends on your duty cycle.

ABB ACS310 ratings, frame sizes and type code

How do I read an ACS310 type code?

Take the code ACS310-03U-17A2-4+J400. Each part tells you something:

  1. ACS310 is the series.
  2. 03 means 3-phase input. The 01 code is for 1-phase input.
  3. U is the region and filter letter. The U units are the ones we stock.
  4. 17A2 is the output current code, 17.2 A.
  5. 4 is the voltage class. A 2 means 200-240 V, and a 4 means 380-480 V.
  6. +J400 is a plus-option code after the plus sign.

ABB catalogs often print an X in place of the letter, as in 03X-17A2-4. The X stands for the E or U variant. In the European catalog, E means the RFI filter is connected, 50 Hz, and you can disconnect the filter.

What is the difference between the two current ratings in the ACS310 catalog?

The catalog lists two current values per model. First, I2N is the maximum continuous output current at 40 °C ambient. It has no overload capability, and you lose 1% for each °C above 40, up to 50 °C.

The second value, which ABB calls ILD, is the continuous current at a maximum of 50 °C ambient. It allows 10% overload for one minute every 10 minutes. For example, the 10 hp 480 V unit lists 17.2 A for I2N and 15.6 A for the second value.

Also, our product titles use the second value. So compare that number with the motor nameplate current, and size the drive on motor full load amps.

Which ACS310 model matches my motor?

Match three things: supply voltage, motor horsepower and motor nameplate amps. Note that 240 V and 480 V units are different models. In addition, the 240 V class stops at 15 hp, while the 480 V class goes to 30 hp.

Type codeRatingInputAmps on our listingFrame
ACS310-01U-06A7-21.5 hp1-phase 208-240 V6.5 ACheck ABB catalog
ACS310-03U-07A4-21.5 hp3-phase 208-240 V6.7 AR1
ACS310-03U-03A6-41.5 hp3-phase 400-480 V3.3 ACheck ABB catalog
ACS310-03U-34A1-210 hp3-phase 208-240 V31.0 AR4
ACS310-03U-17A2-410 hp3-phase 400-480 V15.6 AR3
ACS310-03U-50A8-215 hp3-phase 208-240 V46.2 AR4
ACS310-03U-25A4-415 hp3-phase 400-480 V23.1 AR3

Frame sizes come from ABB catalog rows for the matching X codes. However, where the table says to check the catalog, the frame was not confirmed in our sources.

The +J400 versions of each model are the same drive with the advanced keypad option, per our listings. Still, check the J400 description in ABB’s catalog before you rely on a specific keypad name.

ABB ACS310 specifications and environmental limits

What are the ACS310 specifications and ambient limits?

These are the main figures from ABB’s catalog:

White drive module with orange heatsink mounted on DIN rail, with a cooling fan on the wall and a thermometer nearby.
Fins run vertically, so airflow past the sides carries heat away from the body.
  • Output: 3-phase, from 0 to the supply voltage, 0 to 500 Hz.
  • Switching frequency: selectable from 4 to 16 kHz in 4 kHz steps.
  • Ramp times: acceleration and deceleration from 0.1 to 1800 s.
  • Motor control: scalar U/f.
  • Ambient temperature: -10 to 50 °C, with no frost.
  • Voltage analog input: 0(2)-10 V unipolar or -10 to 10 V bipolar, with input resistance above 312 kOhm.
  • Current analog input: 0(4)-20 mA with 100 Ohm input resistance.

Derating for heat and altitude

Remember the 1% per °C cut above 40 °C that applies to I2N. For altitude, the catalog lists rated current from 0 to 1000 m, with a 1% reduction per 100 m. However, the source text we used was cut off, so confirm the starting altitude in the manual.

Next, our units are IP20 enclosed. That means you need a cabinet or a clean, dry location. Also, check the ABB manual’s technical data chapter for the degree of protection and UL type.

Which ACS310 document to use

Where do I find the ACS310 user’s manual and which version applies?

Go to ABB’s Document Library and search by document code. The full manual is 3AUA0000044201, Rev D, effective 2016-01-11. It applies to firmware 4.050 or later. Meanwhile, the short form manual is 3AUA0000044200 and covers basic installation and commissioning.

However, older Rev C manuals apply to firmware 4.00E or later. They show both SI and imperial units and include special instructions for US installations. To pick the right one, read parameter 3301 FIRMWARE on the drive and match it to the manual.

Other documents worth having

First, the user’s manual is the complete reference. Its chapters cover safety, installation, start-up, control panels, macros, program features, parameters, fault tracing, maintenance, technical data and dimensions.

DocumentCode
User’s manual, German3AUA0000048396
User’s manual, Italian3AUA0000048398
User’s manual, French3AUA0000048400
User’s manual, Spanish3AUA0000048401
MFDT-01 FlashDrop user’s manual3AFE68591074
MUL1-R4 installation instructions3AUA0000025916
Capacitor reforming guide3AFE68735190
Maintenance schedule (ACS310, ACS320, ACS350)DOCMSACS35001

There is also a manual for the MREL-01 relay output extension module. In addition, our post on drive classes, type codes and where to find manuals goes deeper on searching ABB’s library.

Installing and wiring an ABB ACS310

First, start with the safety chapter and the installation checklist in the manual. Then, for wiring rules, follow the manual’s installation chapters and your local electrical code.

Mounting, clearances and derating

Use the manual’s mechanical installation and dimension chapters for clearances and cooling air on each frame size, R0 to R4. Then apply the temperature and altitude derating from the specifications section. Also keep the cabinet clean and dry, because the drive is IP20.

How do I wire an ACS310 on single-phase supply?

First, use a 1-phase model, which is made for this. These are the 200-240 V units up to 2.2 kW (3 hp). Then connect power to the U1/L and V1/N terminals.

However, running a 3-phase model on single-phase input is different, because it needs de-rating. Our single-phase de-rating post covers that.

Power and motor wiring

First, check the supply voltage against the drive nameplate. Next, fasten the grounding conductor (PE) of the input power cable under the grounding clamp, as the short form manual directs. Then use the motor connection data in the technical data chapter.

Also, do not swap the input and output cables. For example, fault 0035 OUTP WIRING means the input power cable is connected to the drive output.

How do I disconnect the EMC filter on an ACS310?

The internal EMC filter is held by an EMC screw. ABB’s short form manual says to remove the EMC screw when the supply is ungrounded or corner-grounded. Removing it disconnects the internal filter, so the drive does not stress the supply network on those systems.

Before you touch the screw, lock out power and wait the full discharge time in the next section. Then find the screw’s exact position for your frame size in the manual’s installation chapter. Also, do not assume it matches the ACS320 procedure.

Safety and lockout before service

First, use lockout/tagout and verify zero voltage with a rated meter before you touch the drive or motor. Then wait 5 minutes after you disconnect power, because the capacitors need that time to discharge, per ABB’s short form manual. Also read the manual’s safety chapter before you start.

ABB ACS310 start-up: panels, Assistant and group 99 data

How do I start up an ACS310 and enter motor data?

First, have the motor nameplate on hand before you start. The Basic Control Panel powers up in Output mode. In contrast, the Assistant Control Panel asks whether to run the Start-up Assistant. The Start-up Assistant needs the Assistant panel, and it splits the work into tasks such as Motor Set-up and PID Control. In addition, the drive works with the ACS-CP-C Basic Control Panel, Rev M or later.

ABB ACS310 drive wired to a motor, with a laptop and an orange handheld panel on a workbench.
Cables run from the wall-mounted enclosure to the finned machine beside it.

Follow this order:

  1. Select the language in 9901 (Assistant panel only).
  2. Choose the macro in 9902 APPLIC MACRO.
  3. Enter motor data in group 99, such as 9905 motor nominal voltage and 9908 motor nominal speed.
  4. Set ramps and limits.
  5. Test direction, then run the motor.
  6. Save your settings as a user macro if you want a reusable set.

Take care with 9908. For example, entering 1500 rpm for a motor that runs at a different speed results in wrong drive operation. Also, you can copy settings between drives with the MFDT-01 FlashDrop tool.

Application macros for the ABB ACS310 drive

Which application macro should I choose?

Parameter 9902 APPLIC MACRO sets the I/O layout and many related parameters. These are the values:

ValueMacro
1ABB Standard
23-Wire
3Alternate
4Motor Pot
5Hand/Auto
6PID Control
7PFC Control
15SPFC Control

First, choose ABB Standard for simple speed control. Next, pick Hand/Auto when an operator needs a local mode. For a single pump holding a pressure or flow, use PID. Finally, for several pumps or fans on one drive, use PFC or SPFC.

The PFC macro uses a default I/O layout with a Hand/PID-PFC selection, interlock inputs, relay output 1 as PFC, a 4-20 mA process actual value and a 0-10 V setpoint. However, each macro moves the start/stop, speed reference and relay functions to different terminals. So use the default I/O table for your macro in the manual’s macro chapter, and check it against your wiring.

How do I set up PID control for a pressure booster pump?

First, choose macro 6, PID Control. Next, connect the setpoint and the process actual value, such as a 4-20 mA pressure transducer. You can then use the Start-up Assistant’s PID task, or enter the settings by hand.

The drive compares feedback with the setpoint and changes motor speed to close the gap. For example, if demand rises and pressure falls, the pump speeds up. If demand falls, it slows down.

Then tune the PID settings in group 40. Parameter 4001 is the proportional gain, 4002 is the integral time and 4003 is the derivative time. Parameter 4010 picks the setpoint source. Because the right values depend on your pipe, pump and transducer, we do not give fixed numbers. Change one value at a time in small steps, which helps you avoid hunting, where speed swings up and down.

If the pump should stop at low demand, look for the sleep function in the PID parameter group of the manual’s parameter list.

Multi-pump and fan control with PFC and SPFC

How does ACS310 PFC multi-pump control work and how is it enabled?

PFC means pump and fan control. First, one drive runs the lead motor at variable speed. Then it starts and stops auxiliary motors through relay outputs. Also, ABB’s catalog says one drive can run 4 to 5 pumps or fans in parallel.

To enable it, set 9902 APPLIC MACRO to 7. Then set the group 81 parameters. Parameter 8123 PFC ENABLE turns the function on, and you can adjust the other settings from there.

These are the key parameters named in ABB’s catalog:

  • 8109 and 8110: start frequencies for the auxiliary motors.
  • 8115 AUX MOT START D: the delay before an auxiliary motor starts.
  • 8116 AUX MOT STOP D: the delay before an auxiliary motor stops.
  • 8122 PFC START DELAY: a delay before the PFC logic starts.
  • 1402: set relay output 2 to PFC.
  • 1805 DO SIGNAL: set to PFC if you use a digital output.

Next, read the manual for how interlock inputs behave. They tell the drive which motors are available.

What is the difference between PFC and SPFC?

SPFC is for pump alternation where lower pressure peaks are wanted when a new auxiliary motor starts. It adds a soft start for those auxiliary motors. To enable it, set 9902 to 15, and set 8123 PFC ENABLE to 3.

Use PFC for a plain multi-pump setup. However, use SPFC when a pressure spike at each pump start would stress the pipework.

What are pipefill and pump cleaning on the ACS310?

Pipefill is a soft fill of empty pipes. The drive brings the pump up gently instead of slamming water into an empty line. Pump cleaning, in turn, is a function that helps clear a pump. Also, ABB’s catalog lists inlet and outlet pressure functions.

The old version of this post made claims about water hammer. However, we could not confirm them from a primary source. So we describe these functions in ABB’s wording and leave out the pressure-surge claims.

ABB ACS310 fault codes and what to check

What do the common ACS310 fault codes mean?

First, the panel shows faults as four-digit codes. Also, alarms appear with an A prefix. Always find and fix the cause before you reset a fault. Because the table below uses summaries from third-party lists, the manual’s Fault tracing chapter is the final word.

Open electrical enclosure showing a drive unit, contactor, and motor, with a multimeter, screwdriver, and gloves on a rubber
Cabinet door swung wide, with red indicator lamp and pushbutton mounted on it.
CodeNameFirst checks
0001OVERCURRENTMotor load, ramp times, motor and drive power match
0002DC OVERVOLTAGEDeceleration time, parameters 2203 and 2206
0004SHORT CIRCUITMotor cables and motor
0006DC UNDERVOLTAGEMissing phase, fuse, rectifier fault, low supply
0007 / 0008AI1 LOSS / AI2 LOSSAnalog signal wiring, limits in 3021 and 3022
0009MOTOR OVERTEMPERATURELoad, motor size, cooling, start-up data
0010PANEL LOSSPanel connection
0012MOTOR STALLMechanical load and motor data
0014EXT FAULT 1External device, setting in 3003
0016EARTH FAULTMotor cable and motor
0022SUPPLY PHASEInput fuses, terminations, all three phases
0035OUTP WIRINGInput cable connected to the output

How do I reset a fault and read the fault history?

Parameter 1604 FAULT RESET SEL picks where the reset signal comes from, such as the panel, a digital input or the fieldbus. You can also reset from the control panel. If the cause is still there, the fault returns.

To read the history, look at group 04. Parameter 0401 shows the last fault. The next two parameters, 0402 and 0403, hold earlier faults. Write down the code before you reset, because it helps you spot a repeat problem.

The drive can also reset some faults on its own. The automatic reset settings are in group 31, where you choose how many tries it makes and the delay between them. However, an auto-reset restarts the motor with no warning. So use it only where that is safe for people and for the machine.

What causes ACS310 short circuit or earth fault trips?

A short circuit (0004) points to a short in the motor cables or motor. It can also come from a defective output transistor or current sensor. Meanwhile, an earth fault (0016) is a ground fault in the motor cable or motor.

For overcurrent (0001), first check for mechanical causes such as a seized bearing or a blockage. Then check motor and drive power, and try a longer acceleration time. For 0034 MOTOR PHASE, look for a missing motor phase or a fault in a motor thermistor relay.

Do not disable earth fault protection to clear a trip. One source says it may void the warranty, and another says it may damage the drive. Either way, you gain nothing by it.

Why does the ACS310 show DC undervoltage or supply phase fault?

DC undervoltage (0006) comes from a missing input phase, a blown fuse, a rectifier fault or low supply voltage. Supply phase (0022) means the DC link voltage is oscillating. In that case, the drive trips when the ripple passes 14% of nominal DC voltage.

In both cases, start at the supply. Check the fuses, the terminations and the incoming voltage on all phases.

For DC overvoltage (0002), the motor usually acts as a generator during a fast stop. So extend the deceleration time in 2203 or 2206. For 0009 and 0012, look at excess load, an undersized motor, poor cooling and wrong start-up data in group 99.

Why do I get AI1 loss or panel loss faults?

AI1 LOSS (0007) and AI2 LOSS (0008) mean an analog signal fell below the limit in 3021 or 3022. On PID loops, check the transducer and its wiring first. PANEL LOSS (0010), however, means the drive lost contact with the panel that is the active control location.

These panel alarms also come up often:

  • 5011: the drive is controlled from another source. Switch to local control.
  • 5012: direction of rotation is locked. Check 1003 DIRECTION.
  • 5014: panel control is disabled by an active fault. Clear the fault and try again.
  • 5015: local lock is active. See 1606 LOCAL LOCK.
  • 5081: operation is blocked by an active fault.

When should an ACS310 be repaired instead of reset?

In short, repair it when the code points inside the drive. Codes 0018 THERM FAIL, 0021 CURR MEAS and 0026 DRIVE ID are internal faults. For 0101 SERF CORRUPT, ABB’s text says to record the code and contact the ABB representative.

Also send the drive for repair if short circuit, overcurrent or DC bus faults return after the motor and cable test good. Visible damage is another reason. Our repair service handles these units. Before you decide, compare that cost with a replacement.

Maintenance and capacitor reforming for the ABB ACS310

What maintenance does an ACS310 need and how do I reform capacitors on a spare?

Use ABB’s maintenance schedule for the ACS310, ACS320 and ACS350 (DOCMSACS35001) for service intervals. Between those, apply common sense. For example, keep the drive and cabinet clean, check that terminals are tight, and watch for signs of heat.

Also, a spare drive that sat in storage needs its capacitors reformed before you power it up. ABB’s capacitor reforming guide, 3AFE68735190, covers the ACS310 and gives the procedure. Read it first, because the right steps depend on how long the unit has been stored.

Replacing an ABB ACS310: ACS180, ACS380 and other options

What replaces the ABB ACS310?

ABB’s conversion guidance, as copied by a distributor, points non-demanding applications to the ACS180 if features permit. It sends demanding applications and fieldbus use to the ACS380. In addition, a distributor article gives the same split.

Isometric illustration of two ABB ACS310 drive enclosures on a workbench with mounting brackets, a coiled cable, and cable
The smaller unit’s orange side band helps it stand out on the bench.

The guide is marked confidential on the site that hosts it. So confirm the advice with ABB before you quote it as ABB’s position. Also, neither drive is a drop-in swap, because footprints and terminal layouts do not line up one-to-one.

What do I need to check when swapping an ACS310 for an ACS180 or ACS380?

In either case, plan for rewiring and re-entering parameters. Work through this list:

  • Motor current and overload needs
  • Supply voltage and phase
  • Whether you use PFC, SPFC or PID, and whether the new drive has the same functions
  • Fieldbus needs
  • The control panel you want
  • Mounting footprint in the cabinet
  • EMC filter needs
  • Control wiring changes

Our ACS180 page and ABB VFD selection guide help with the next step. However, we have no prices or lead times for replacement drives in this guide. So ask us for current figures.

Buying an ABB ACS310 from Precision Electric

Which ACS310 models does Precision Electric stock?

We list these models, each also with the +J400 advanced keypad version:

First, match the model to your motor nameplate amps and your supply voltage. Because ABB no longer supplies new units, stock is limited. In addition, we can repair your installed drive or help you pick a replacement.

Frequently asked questions

Is the ABB ACS310 discontinued?

Yes. ABB’s life cycle statement lists the ACS310 and ACS355 as Obsolete since 1 January 2026 and says the product is no longer available. An earlier ramp-down notice planned 1 July 2026, so use the newer statement. Meanwhile, remaining stock comes from distributors, and repair is available for installed units.

What replaces the ABB ACS310?

ABB’s conversion guidance, as copied by a distributor, points non-demanding applications to the ACS180 where features allow. Demanding or fieldbus applications go to the ACS380. Because footprint and terminal layout differ, plan for rewiring and re-entering parameters. Also, check the guidance against ABB before you order.

Where can I download the ACS310 manual?

First, search ABB’s Document Library for 3AUA0000044201 (user’s manual, Rev D, firmware 4.050 or later) or 3AUA0000044200 (short form). Then check parameter 3301 FIRMWARE to match the manual revision to the drive.

How do I set up pump and fan control (PFC) on an ACS310?

Set parameter 9902 APPLIC MACRO to 7 for PFC or 15 for SPFC, which adds a soft start for auxiliary motors. Then set the group 81 parameters, such as 8123 PFC ENABLE, the start frequencies, and the auxiliary motor start and stop delays. Also, ABB’s catalog says one drive can run 4 to 5 pumps or fans in parallel.

What does ACS310 fault 0022 SUPPLY PHASE mean?

In short, it means the DC link voltage is oscillating, usually from a missing input phase or a blown fuse. The fault trips when the ripple exceeds 14% of nominal DC voltage. So check the supply fuses, terminations and incoming voltage on all phases.

Can an ACS310 run on single-phase power?

Yes. The 1-phase 200-240 V models, up to 2.2 kW (3 hp), are made for it, with power connected to U1/L and V1/N. However, running a 3-phase model on single-phase input needs de-rating, which our single-phase de-rating post covers.

The ABB ACS310 is a solid pump and fan drive, but it is now obsolete, so your plan should cover stock, repair and a future replacement. If you keep the right manual, the parameter numbers and the fault table close to the drive, you will solve most problems fast. Finally, if you need a unit, a repair quote or help choosing a replacement, contact Precision Electric or browse our ACS310 models.