ABB VFD with Bypass: Models, Type Codes and Sizing Guide

Open cabinet with an orange VFD, bypass components, and wiring to a motor, illustrating an ABB VFD with bypass.

An ABB VFD with bypass keeps a motor running when the drive is down, and it puts the drive, disconnect and starter in one enclosure. This guide covers which ABB models come that way, how to read their part numbers, and what to check before you order. It also covers start-up order and common faults.

On this page

What an ABB VFD with bypass is

What is an ABB VFD with bypass?

An ABB VFD with bypass is an ABB drive packaged with a bypass starter, a door-mounted disconnect or circuit breaker, and motor overload protection. For example, the ACH580 with E-Clipse bypass comes in a UL (NEMA) Type 1, 12 or 3R enclosure. In drive mode, the drive controls the motor. In bypass mode, the motor runs straight from line power.

Why use a bypass with a VFD?

The main reason is uptime. If the drive fails, you can switch to bypass and keep the motor running. ABB’s E-Clipse macro wording says the bypass device can bypass the drive and connect the motor direct on-line.

However, bypass mode gives up the drive’s benefits. The motor runs at full line speed with no speed control, no soft start and no drive protection. Because of that, use bypass only where line speed is safe for the load.

What parts are in the power path?

First, here is the ACH580 E-Clipse power path, in order:

  1. Disconnect switch or circuit breaker
  2. Input fuse for the drive
  3. The drive itself
  4. Output contactor
  5. Bypass contactor
  6. Bypass control
  7. Optional service switch
  8. Motor

Also, the door handle on the disconnect or breaker can take a padlock in the OFF position. However, the padlock is not supplied.

Is a standard drive the same thing?

No. A standard drive such as the ACS180 or ACS255 has no bypass path. In contrast, a bypass package adds the contactors, controls and protection around the drive.

Which ABB families offer this option

Which families are available?

Two current ABB families offer a bypass: the ACH580 E-Clipse bypass family (BCR, BDR, VCR, VDR) and the ACS580-0P with the +F255 breaker and +G310 two-contactor bypass options. In addition, older ACH550 E-Clipse units are in the field. The table gives a quick view.

Three navy electrical enclosures with white doors step up in height, each with cables entering, while a worker in gray
The orange-trimmed cabinet at the far end is the one to check first.
FamilyBypass typeSize range citedEnclosureTypical use
ACH580 E-ClipseE-Clipse bypass1 to 350 hp (ABB US page)Type 1, 12 or 3RHVAC fans and pumps
ACS580-0P +F255 +G310Two-contactor bypass1 to 350 HP (ABB brochure)Type 1, 12 or 3RGeneral purpose
ACH550 E-ClipseE-Clipse bypass1 to 400 HP (manual 3AUA0000016461)See manualInstalled base, service

ACH580 with E-Clipse bypass (HVAC)

How big is the E-Clipse range?

The ABB E-Clipse bypass drive is the ACH580 with an integrated bypass motor starter. ABB’s US page lists 1 to 350 hp at 230/460/575 V. However, the E-Clipse bypass and packaged drive user manual lists 1…200 HP, so ranges differ by document revision.

Other ABB documents show more differences. For instance, a later ACH580-01 I&O manual covers BCR/BDR at 1…350 HP. The ultra-low harmonic version covers 5…400 HP. Meanwhile, ABB’s HVAC catalog covers the whole ACH580 line at 1–700 HP. As a result, you should always cite the document and revision when you specify.

What variants does the ACH580 E-Clipse come in?

  • BCR: bypass with circuit breaker
  • BDR: bypass with disconnect switch
  • VCR and VDR: vertical bypass versions
  • PCR and PDR: packaged drives with no bypass

Distributor spec data for ACH580-BCR units shows built-in BACnet MS/TP, N2 and Modbus RTU, and a keypad included. Still, confirm these against ABB’s catalog before you order.

ACS580-0P with two-contactor bypass (general purpose)

What is the ACS580-0P+F255+G310?

The ACS580-0P+F255+G310 is an ACS580 drive packaged with a circuit breaker disconnect and a two-contactor bypass. ABB lists it as an “ABB drive with bypass and circuit breaker,” 1 to 350 HP. In addition, the installation supplement covers Type 1, Type 12 and Type 3R versions.

Option +P919 puts the bypass controls on the door. This family is general purpose, while the ACH580 E-Clipse is built for HVAC. Also, the two use different manual sets.

For example, one distributor lists the ACS580-0P-014A-4+B056+F255+G310 as a 10 HP, 480 V, Type 12 unit. It has an input circuit breaker, fast-acting fuses, a padlockable door-mounted disconnect operator and door-mounted electronic motor overload protection.

Which voltage and horsepower ranges apply to each ACS580-0P bypass voltage class?

The single 1 to 350 HP range covers the whole family. Each voltage class has its own range, as ABB lists them:

Voltage classHorsepower range
230 V1 to 100 HP
480 V1 to 350 HP
575 V2 to 150 HP

So a 575 V motor above 150 HP does not fit this family. Likewise, a 230 V motor above 100 HP needs a different solution.

What is the difference between the two-contactor, three-contactor and soft-start bypass?

The standard bypass is the two-contactor type, option +G310. One contactor feeds the motor from the drive, and the other feeds it from the line.

The +F267 service switch gives the three-contactor equivalent. Choose it when you want a way to isolate the drive for service. The soft-start bypass, option +G390, is for jobs where a full-voltage line start in bypass is too hard on the motor or load. Check the ABB manual for the exact wiring and limits of each option.

ACH550 E-Clipse bypass (legacy installed base)

Is the ACH550 still supported or replaceable?

ACH550 E-Clipse bypass drives (BCR/BDR/VCR/VDR) are covered for 1…400 HP in user’s manual 3AUA0000016461. You will meet them on service and replacement jobs. However, we found no source that names a direct replacement or sets an end-of-life date.

Navy electrical enclosure with open door showing an orange drive-style unit, wiring, and terminal blocks, beside a test
Gloves and a handheld meter sit on the bench before any live work begins.

So before you specify one for new work, confirm current availability with ABB or with us. Then check any replacement against the current ABB catalog.

How to read type codes and options

What do BCR, BDR, VCR, VDR, PCR and PDR mean?

Take ACH580-BCR-012A-4 as an example. The 580 is the product series. Next, BCR is the build type. The 012A is the drive output current, and the last digit is the voltage code.

  • BCR: E-Clipse bypass with circuit breaker
  • BDR: E-Clipse bypass with disconnect switch
  • VCR: vertical bypass with circuit breaker
  • VDR: vertical bypass with disconnect switch
  • PCR: packaged drive with circuit breaker, no bypass
  • PDR: packaged drive with disconnect switch, no bypass

For voltage, -2 is 208-240 V, -4 is 380-480 V (440-480 V on the label), and -6 is the 575/600 V class. Also, the type code label sits on the heat sink, on the right side of the unit cover.

What do +F255, +G310, +B056, +B058 and +P919 mean?

  • +F255: input circuit breaker
  • +G310: two-contactor bypass
  • +B056: UL (NEMA) Type 12
  • +B058: UL (NEMA) Type 3R
  • +P919: bypass controls on the door

Also, on the ACH580, +J429 is the HVAC control panel with Bluetooth interface, type ACH-AP-W. The current in the type code is the drive output current. ACH580-BCR-027A-4+B058, for example, is 20 hp at 27 A. Because these HVAC ratings are variable torque, check the duty before you match a motor.

Models and ratings

What horsepower and voltage ranges are covered?

The ranges depend on the family and document revision, as the sections above show. Voltage classes run from 208-240 V through 575/600 V. In addition, the 208-240 V ACH580-BxR ratings run from 4.6 A through 248 A. The table lists verified examples.

Part numberRating
ACH580-BCR-07A5-2+B0582 hp, 7.5 A
ACH580-BCR-10A6-2+B0583 hp, 10.6 A
ACH580-BCR-031A-2+B05810 hp, 30.8 A
ACH580-BCR-088A-2+F26730 hp, 88 A
ACH580-BCR-04A8-4+B058+F2673 hp, 4.8 A
ACH580-BCR-027A-4+B05820 hp, 27 A
ACH580-BCR-052A-4+B05840 hp, 52 A
ACH580-BCR-096A-4+B056+F26775 hp, 96 A
ACH580-BCR-414A-4350 hp, 414 A, 460 V
ACH580-BCR-022A-6+B05820 hp, 22 A
ACS580-0P-012A-47.5 HP, 12 A
ACS580-0P-156A-4125 HP, 156 A
ACS580-0P-180A-4150 HP, 180 A (ND)
ACS580-0P-052A-650 HP, 52 A
ACS580-0P-062A-660 HP, 62 A

As another example, a sample ACH580-BCR-240A-4 label shows 200 hp, 240 A, 440…480 Vac and a 100 kA short-circuit rating.

How do I size one for my motor?

First, start with the motor’s full-load amps and the line voltage. Then pick a drive whose output current covers the motor. Do not size from the table above. Instead, for ratings and frame size, the E-Clipse manual points to the Ratings section of the ACH580-01 Hardware Manual (3AXD50000044839).

How do I match the overload settings and drive rating to my motor?

Start with the motor nameplate. The drive’s variable-torque output current must be at or above the motor’s full-load amps. Because HVAC fans and pumps are variable-torque loads, this rating is the one to use.

Next, set the bypass overload to the nameplate full-load amps, not to the drive’s rating. Then check the motor’s service factor and duty. If the motor current is close to the drive’s limit, move up one size.

Matching a unit to the job

Which unit fits HVAC fans and pumps versus general industrial loads?

For HVAC, pick the ACH580 E-Clipse. That means supply and return fans, air handlers, and chilled and hot water pumps. Also, ABB’s HVAC catalog describes this family.

Diagram of an ABB VFD with bypass cabinet wired to a pump motor beside a packaged HVAC unit and copper piping manifold.
Orange-trimmed control box mounts on the wall, with cables routed along the floor.

If the motor must run when the drive fails on a general industrial pump or fan, look at the ACS580-0P with +F255+G310.

Outdoor or washdown spots call for the right enclosure code. For example, +B058 is Type 3R. However, ABB lists Type 4X as a special-enclosure option for the ACH580, so confirm that with ABB.

As a general guide, a bypass adds little for a small standalone motor. It is also wrong for a load where full line speed is unsafe. That is engineering judgement, so check your own application.

Factory package vs the alternatives

How does an ABB bypass drive compare with a standard drive plus a separate bypass panel?

A factory package puts the drive, door disconnect, overload protection, bypass controls and manuals in one UL (NEMA) enclosure. With a separate panel, however, you check panel space, wiring and who supplies the starter. Cost and wiring time are your call, and we have no sourced numbers to give.

Within ABB’s line, the choice is simple. First, the ACH580 E-Clipse brings HVAC macros and built-in BACnet. Next, the ACS580-0P brings the G310 two-contactor bypass. Finally, the PCR/PDR packaged drives use the same kind of package as BCR/BDR but have no bypass function.

How the bypass works in drive and bypass mode

How do I switch between drive mode and bypass mode?

Use the Drive Select and Bypass Select keys on the bypass keypad. The LEDs show which mode is active. For example, the Bypass Selected LED glows solid green when bypass is selected.

In bypass mode, the bypass contactor powers the motor from line power. Also, the Auto or Hand setting on the bypass keypad decides where start and stop commands come from.

In addition, ABB manuals describe settings for drive faults, such as drive only or switch to bypass. You can find those in the manual’s parameter chapter.

What are Override 1 and Override 2, and which fits a smoke-control fan?

Override 1 is a fixed mode. It is meant to meet the intent of UL864/UUKL smoke-control rules. Override 2 is configurable, so you set how it behaves.

For a fire or smoke-control fan, Override 1 is the mode built for that purpose. However, confirm the choice with the local authority and the ABB manual before you commission.

Installing and starting up the unit

What is the correct start-up order?

Follow this order, based on ABB’s manual:

Technician in white coveralls and blue gloves mounting a blue drive unit inside an open electrical cabinet beside a motor
A coiled cable and pliers rest on the workbench, ready for wiring.
  1. Apply power to the unit.
  2. Confirm the Drive Selected LED is lit. If not, press Drive Select.
  3. Leave the system in Drive mode and set up the drive.
  4. Run the motor from the drive.
  5. Check the motor rotation direction in bypass before you connect the load.
  6. Then test bypass.

ABB manuals say to run the motor from the drive before you try bypass. Also, read the manual’s warning about bypass configurations for the exact text.

What fuses and disconnects are needed?

Use the tables in the ACH580 I&O manual. They list fuse and disconnect data by type code for the BxR box-enclosure units, with the internal fuse class and the external fuse for the disconnect option. For example, ACH580-BxR-065A-4 uses Class T internally and Class J 100A externally. So do not size fuses, wire or torque from memory.

Wiring points include the input and motor ground lugs, the input and motor terminals, the E-Clipse control board terminals X2, the fuses and the optional service switch.

Common bypass problems and when to call for repair

It means the drive’s communication settings were changed unintentionally. You may also see “Drive Link Error.” To recover, ABB says to set parameter 95.21 bit 5 to “Bypass present” on the drive keypad.

Why won’t my ABB bypass contactor close?

The drive may not have run yet. For example, the ACH550 bypass raises fault 3013 DRIVE 1ST START if you try to close the bypass contactor before running in drive mode. The fix is to run the unit in drive mode first.

Also, check rotation in bypass. Wrong rotation can damage the load.

What does the PHASE SEQ fault mean, and how do I clear it?

PHASE SEQ means the input phases are in the wrong order. To clear it, first remove power from the unit. Then wait at least 5 minutes. Finally, swap any two input phases and power up again.

How do I replace a failed bypass control board?

The bypass control board is called the RBCU. ABB’s replacement instructions name the part as 3AXD50000328055. They also give the parameter steps to set up the new board, so follow them in order. If you want help with a failed board or bypass, we can repair these units.

When should I send the unit in for repair?

Send it in when the drive section or the bypass board has failed and a reset or parameter fix does not clear it. Precision Electric can repair these units and supply parts. For turnaround and pricing, contact us.

Questions to answer before you order

What information do I need before ordering?

First, gather this list:

  • Motor hp and full-load amps
  • Line voltage class (-2, -4 or -6) and phase
  • Enclosure: Type 1, 12 or 3R
  • Circuit breaker or disconnect switch
  • Communication needs, such as BACnet MS/TP or Modbus RTU
  • Short-circuit rating
  • HVAC or general-purpose load

Then check your exact plus codes against the right ABB manual. Finally, ask us to confirm stock, lead time and any required options.

Where Precision’s stocked ABB drives fit

Do the ABB ACS180 or ACS255 drives come with a bypass?

The ACS180 and ACS255 drives we sell are standard drives, not factory bypass packages. Some ACS255 Micro versions have an NEMA 4X/IP66 enclosure. Others add the +F278 option, which gives an integrated disconnect, speed pot and forward/reverse switch. That is a disconnect and local controls, not a bypass.

Isometric illustration of a navy-and-white ABB VFD with bypass cabinet on a workbench beside a cable spool, junction box
The orange-outlined drive stands apart from the spool and the small boxes.

Our listed units are 0.5 HP, below the 1 hp start of the ABB bypass families covered here. For series detail, see our ACS180, ACS250 and ACS255 guides. For a bypass, however, check the current ABB catalog first.

Where to find ABB bypass manuals and catalogs

Where do I find manuals and catalogs?

Use ABB’s document library and the ABB product ID pages. They are the primary sources. In addition, ABB’s ACH580 HVAC drives page for the US has the catalog, and the ABB solutions for HVAC catalog covers the ACH580 at 1–700 HP. These are the key documents:

  • User manual for the ACH580 E-Clipse bypass and packaged drive: 3AXD50000289554
  • Hardware manual for the ACH580-01: 3AXD50000044839
  • Firmware manual for the ACH580-01: 3AXD50000027537
  • Installation supplement for the ACS580-0P bypass: 3AXD50000780341
  • User’s manual for the ACH550 E-Clipse bypass: 3AUA0000016461

The same documents list short-circuit ratings, enclosure dimensions, weights and wire and terminal ranges by size. Check them before you plan panel space or conduit entry.

Frequently asked questions

What is an ABB VFD with bypass?

It is an ABB drive packaged with a bypass starter, a door-mounted disconnect or circuit breaker, and motor overload protection. ABB’s ACH580 with E-Clipse bypass is built in a Type 1, 12 or 3R enclosure. As a result, the bypass can run the motor straight from line power if the drive is out of service.

Which ABB drives come with a bypass?

The ACH580 E-Clipse bypass family (BCR, BDR, VCR, VDR) and the ACS580-0P with the +F255 breaker and +G310 two-contactor bypass options. Older ACH550 E-Clipse units are in the field too. Both current families list ranges starting at 1 hp.

What do BCR and BDR mean in part numbers?

BCR is an E-Clipse bypass with a circuit breaker. BDR is an E-Clipse bypass with a disconnect switch. Meanwhile, VCR and VDR are the vertical versions, and PCR and PDR are packaged drives without the bypass.

Can I run the motor in bypass right away at commissioning?

No. ABB’s manuals say to run the motor from the drive before you attempt bypass operation. For example, the ACH550 bypass can raise fault 3013 DRIVE 1ST START if you try bypass first. Also, check the motor’s rotation direction in bypass.

It means the drive’s communication settings were changed unintentionally. To recover, ABB says to set parameter 95.21 bit 5 to “Bypass present” on the drive keypad.

An ABB VFD with bypass gives you a drive and a line-power backup in one enclosure, but you must match the family, enclosure and options to the job. So check the plus codes against the right ABB manual before you order. If you need help picking a unit, repairing one or finding a part, contact Precision Electric for a quote or repair.