Optidrive P2 Manual: Which Guide to Download and How to Use It
Finding the right optidrive p2 manual is harder than it looks, because several revisions and variants of the guide are in circulation. This article shows you which guide to download, how to read the drive label, and how to decode a trip. You will also learn how to reset it and when to send the drive for repair.
On this page
- Which Optidrive P2 Manual Do You Need?
- Where do I download the Invertek Optidrive P2 manual?
- Current user guide vs older ODP-2 guides
- What is the difference between the P2 User Guide and the Advanced User Guide?
- Application variants: Elevator and Solar Pump guides
- Other P2 documents: CAD, certificates, brochures and the P2 ASSIST Passport
- Identify Your Drive Before You Use the Manual
- Optidrive P2 at a Glance: Ratings and Enclosures
- Installation and First Start-Up According to the Optidrive P2 Manual
- Finding Your Way Around the Parameters
- Optidrive P2 Fault Codes: How the Drive Reports a Trip
- Invertek Drives Troubleshooting: A Practical Workflow
- What is the step-by-step approach?
- What do I check when an Optidrive P2 trips on over-current?
- How do I deal with over-voltage and braking trips?
- How do I choose and connect a brake resistor?
- Why does my P2 show a Modbus, CANopen or analog input fault?
- What do the motor PTC, fan and memory fault codes mean?
- How do I load factory defaults, run auto-tune or set up a PM motor?
- When to Stop Troubleshooting and Send the Drive for Repair
- Choosing a Replacement or Matching P2 Drive
- Frequently asked questions
Which Optidrive P2 Manual Do You Need?
Where do I download the Invertek Optidrive P2 manual?
First, start with Invertek’s P2 documentation page. It lists the P2 User Guide as a PDF, and that is the main document for installation, parameters and fault messages. In addition, Invertek Store has an Optidrive P2 resources page that points to the same material.

Next, check the version on the title page or footer. Copies of v3.00, v3.02 and v3.04 are in circulation. Because page and section numbers move between versions, a section number from one copy may not match yours.
Also be careful with third-party PDF mirrors. They often host older revisions. For that reason, use them only to confirm what you read, and download the current invertek optidrive p2 manual from Invertek itself.
Current user guide vs older ODP-2 guides
Older documents still exist. The ODP-2 installation and operating instructions (revision 1.30) cover 200 to 480 V, 0.75 to 160 kW, with Easy Start-Up pages for IP20, IP55 and IP66. However, these older guides cover a narrower range than the current P2, which reaches 600 V input.
So use an older optidrive p2 user guide only for a legacy drive, and confirm it against the label. For example, some details differ between revisions, such as brake transistor fitment and the trip-history log timing.
What is the difference between the P2 User Guide and the Advanced User Guide?
The P2 User Guide is the main manual. You use it for installing, wiring, first start-up and reading faults. As a result, most technicians need only this one for day-to-day work.
The separate Advanced User Guide (rev 1.10) was written for firmware 1.20 and covers 0.75 to 250 kW, 200 to 480 V. It goes deeper into the extended parameter set. Therefore, open it when you tune a drive beyond the basics, and keep the User Guide for wiring and trips.
Application variants: Elevator and Solar Pump guides
Yes, there is a different manual for these drives. Invertek publishes separate P2 Elevator and P2 Solar Pump user guides. Each has its own parameter and fault information, and the Solar Pump guide has fault messages in its own section 12.1.
So do not use a standard P2 guide for a drive running that firmware. Instead, use the standard guide for general industrial drives like the ones we stock.
Other P2 documents: CAD, certificates, brochures and the P2 ASSIST Passport
The same Invertek support page holds more than the guide. You can get these from it:
- CAD drawings by frame size: IP20 sizes 2 to 8, IP55 sizes 4 to 8, and IP66 outdoor sizes 2 to 4
- CE and UKCA declarations of conformity, a DNV certificate and SIL 2 STO certification
- Brochures and a stock drives catalogue
- Size 8 IP55 gland box and Size 8 DNV assembly instructions, plus an IP66 sun shade user guide
The page also offers P2 ASSIST, called the Optidrive Passport. It gives you the datasheet, ecodesign data, factory test certificate and product documentation.
Identify Your Drive Before You Use the Manual
How do I read the Optidrive P2 model number and label?
The guide’s quick-start process begins at the drive label. First, identify the model and ratings, then check that the voltage rating suits your supply. The label shows the model code, enclosure type and IP rating, firmware version, serial number, supply voltage and maximum continuous output current.
The model code follows a pattern. First comes a three-digit power rating. Next is the power type, where K means kW rated and H means HP rated. Then an enclosure character follows:
- 2: IP20
- N: IP55 non-switched
- A: IP66 outdoor non-switched
- B: IP66 outdoor switched
In addition, the brochure uses X and Y for indoor IP66 non-switched and switched versions.
You can see this in our catalog. IP20 part numbers end in 42, IP55 in 4N and IP66 outdoor non-switched in 4A. For example, ODP-2-34100-3HF42-MN is a 10 HP, 380 to 480 V, IP20 drive. Likewise, ODP-2-66100-3H04N-MN is a 100 HP, 540 to 600 V, IP55 drive.
Can one manual cover every P2 drive?
Not always. Match the guide revision to the label’s model code and firmware before you trust any parameter number or fault description. Otherwise, a guide for the wrong revision can send you to the wrong section.
Optidrive P2 at a Glance: Ratings and Enclosures
What are the ratings, enclosures and overload capacity?
The published figures are below. Check them against your own guide, because ranges differ by revision.

| Item | Published value |
|---|---|
| Overload | 150% for 60 seconds as standard |
| Starting torque | Up to 200% from zero speed in open-loop vector |
| Motor control | Induction and PM motors; closed loop with an encoder |
| IP20 | Sizes 2 to 3 up to 15 HP / 11 kW; size 8 up to 300 HP / 250 kW |
| IP55 | Sizes 4 to 7 up to 200 HP / 160 kW |
| IP66 / NEMA 4X | Sizes 2 to 3 up to 10 HP / 7.5 kW, switched or non-switched; outdoor listed up to size 4 |
| Other features | Certified STO, simple PLC functions, operation down to -10 °C, made in the UK |
The top of the range is quoted as 350 HP in one place and 400 HP in the brochure. Because of this mismatch, the safest wording is 0.75 to 250 kW. Also, the outdoor IP66 version has a polycarbonate enclosure and conformally coated circuit boards as standard.
Does the P2 meet SIL 2 for STO?
Yes. The brochure says the Safe Torque Off function complies with EN62061 SIL level 2. In addition, Invertek’s support page lists SIL 2 STO certification, so download the certificate from there if your audit needs it.
Brake transistor: check your guide revision
The v3.02 guide says an internal brake transistor is fitted as standard on all models. However, the older v1.30 guide says it is standard on frame sizes 2 to 5 and optional on larger frames. Because of that, read your own revision before you plan on a brake resistor.
One more caution applies to the old version of this post. Do not assume every P2 has a particular EMC filter class. Likewise, do not assume Modbus RTU and CANopen come standard on every drive. Confirm both in the guide for your drive.
Installation and First Start-Up According to the Optidrive P2 Manual
How do I wire and start up an Optidrive P2 for the first time?
Mount the drive vertically on a flat, flame-resistant, vibration-free surface. Then follow the safety rules in the guide:
- Never connect mains power to output terminals U, V and W.
- Do not fit automatic switchgear between the drive and the motor.
- Tighten terminals to the stated torque.
- Do not run the drive with enclosure covers removed.
- Do not try to repair the drive. Contact your Invertek sales partner if you suspect a fault.
Before you touch any wiring, lock out and tag out the supply. NFPA 70E applies on US sites.
How long must I wait after removing power?
The DC bus capacitors hold a charge after you switch off the supply. Invertek’s guides tell you to wait at least 10 minutes before you remove covers or touch terminals. Check your guide for the figure that applies to your revision.
Also do not rely on time alone. After the wait, measure the DC bus voltage with a meter rated for the job, and only then start work.
What torque, cable size, fuse and earthing rules apply to my frame size?
These values change with frame size and rating, so do not copy them from another drive. The technical data and power wiring tables in your guide list the terminal torque, cable size and fuse rating for each model. Find your frame size on the label first, then read the row for your exact model.
For EMC, use screened motor cable and bond the screen to earth at both ends. In addition, keep motor cable away from control wiring, and make a solid earth connection on the drive.
Enable circuit and speed reference
The v1.30 Easy Start-Up page shows the hardware enable circuit. First, link terminal 1 to terminal 12 (STO+) and terminal 9 to terminal 13 (STO-). Then close the control switch between terminals 1 and 2 to enable the drive. As a result, a missing enable link is a common cause when a drive is enabled but will not run.
For a simple speed reference, wire a 1 kΩ to 10 kΩ potentiometer between terminals 5 and 7. Put the wiper on terminal 6. However, check these terminals in the current guide, since this example comes from v1.30.
Motor data and restart behavior
Before you run the drive, enter the motor nameplate data in the first parameter group. For example, P1-09 is motor rated frequency.
Also know how the drive restarts. After power-on or reset, it starts on its own if digital input 1 is closed, depending on the P2-36 setting (Start Mode Select / Automatic Restart). For safety, the guide warns you not to enable automatic fault reset where it could create a dangerous situation.
Finding Your Way Around the Parameters
How do I get to the extended parameters?
P2 parameters use group numbers. P1-xx is basic, P2-xx is extended, and P0-xx is read-only monitoring. You unlock extended access with the P2-40 access code, which defaults to 101. In the Advanced User Guide rev 1.10, P1-14 works the same way, and P2-40 accepts 0 to 9999.

The old post used P-04 and P-05 for acceleration and deceleration. It also spoke of “the initial 14 parameters.” However, those do not match the P2 documentation. So look up the exact ramp parameters in your current guide.
Useful read-only parameters
These P0 parameters help most when you diagnose a trip:
- Trip history log: P0-13 holds the last four faults
- Operating time: P0-31 shows total drive operating time
- Critical fault counters: P0-41 to P0-46 count over-current, over-voltage, under-voltage, over-temperature, brake transistor over-current and ambient over-temperature
- Pre-trip log: P0-36 or P0-37 stores data at 256 ms or 20 ms intervals, depending on the guide version
Use the pre-trip log to see what the drive measured just before it tripped. In addition, two other parameters are worth knowing. P2-25 is the fast-stop ramp time, and P2-18 set to 8 turns on hoist brake control.
Optidrive P2 Fault Codes: How the Drive Reports a Trip
How do Invertek Optidrive fault codes work?
The P2 has many protection features. When one activates, the drive trips and shows a fault message. The guide lists these in its Fault Messages section, which is 11.1 in the v3.0x guides (page 74 in v3.02, page 78 in v3.04).
Each trip has a short display mnemonic and a fault number. For example, P-LOSS is fault 14. The trip log and the high byte of the Modbus status word hold the number.
Also, a relay or digital output set to function 12 (Drive Tripped) goes to logic 1 when the drive trips. Function 1 (Drive Healthy) means no fault exists.
Always record the code first. Then read P0-13 and the pre-trip log before you reset, because a reset does not remove the cause.
What are the Optidrive P2 fault codes and what do they mean?
The table below lists the invertek optidrive fault codes confirmed in P2 sources. Display text can vary by revision, so check it against your guide.
| Code | Mnemonic | Meaning |
|---|---|---|
| 00 | no-Flt | No fault |
| 03 | (see guide) | Over-current trip on drive enable |
| 10 | P-dEF | Factory defaults loaded |
| 11 | E-trip | External trip |
| 12 | SC-ObS | Optibus comms loss; the guide also lists 12 as comms lost with a PC or remote keypad |
| 13 | FLt-dc | DC bus ripple too high |
| 14 | P-LOSS | Input phase loss |
| 15 | (see guide) | Instantaneous over-current on output; refers back to fault 3 |
| 17 | dAtA-F | Internal memory fault |
| 19 | dAtA-E | Internal memory fault |
| 21 | F-Ptc | Motor PTC thermistor trip |
| 22 | FAN-F | Cooling fan fault |
| 24 | O-torq | Maximum torque limit trip |
| 25 | (see guide) | Output torque too low; only with hoist brake control (P2-18 = 8) |
| 26 | Out-F | Drive output fault |
| 29 | Sto-F | Fault in a Safe Torque Off channel |
| 30, 34, 35 | Enc-05, Enc-06 for 34 and 35 | Encoder faults |
| 39 | Enc-10 | KTY trip |
| 40 | AtF-01 | Measured motor stator resistance varies between phases (auto-tune) |
| 50, 51, 52, 53 | SC-F01 to SC-F04 | Modbus, CANopen, Anybus and IO card comms loss |
| 61 | OF-02 | Option module in exceptional condition |
| 74 | PLC-05 | Table function block index overflow |
This list is not complete. Over-voltage, under-voltage, over-temperature, overload and brake faults, with their fault numbers, display codes and corrective actions, are in the Fault Messages section of your guide. Do not guess those mnemonics. In fact, the old post’s O-I, O-V and U-V labels are not confirmed for the P2, and sources show codes such as 03, 15, P-LOSS and OI-b for the family.
How do I reset a tripped Optidrive P2?
Reset only after you find and fix the cause. The guide gives three ways:
- Press the keypad Stop/Reset key.
- Remove power completely, then reapply it.
- If P1-13 is above 0, switch digital input 1 off and on again.
Over Modbus, set the reset bit in the command control word. Then clear the bit once the fault has cleared.
The drive can also auto-reset. It makes up to 5 restart attempts at 20 second intervals. However, you must power the drive down to clear that counter. If the last attempt fails, the drive needs a manual reset.
What does Sto-F mean and how do I clear Safe Torque Off?
Sto-F (code 29) means the drive found a fault in one of the two internal channels of the STO circuit. The guide’s corrective action is to contact your Invertek sales partner. So treat it as a repair issue, not a settings change.
Do not confuse it with a normal STO stop. To leave Safe Torque Off mode, reset any faults and re-energize the STO input. After all, a drive that is simply inhibited has not necessarily failed.
Before you send the drive back, check the STO wiring from the enable circuit above. Terminals 12 and 13 must be wired as shown in your guide, and the supply to them must be present. For the exact supply level, response time and proof-test interval, use the STO section of your guide and the SIL 2 certificate from Invertek.
Invertek Drives Troubleshooting: A Practical Workflow
What is the step-by-step approach?
Good invertek drives troubleshooting follows the same order each time. First, lock out and tag out, then work through these steps:

- Record the fault code and the P0-13 history.
- Compare the motor nameplate with the drive rating.
- Verify the input supply and all three phases.
- Inspect the enable and STO wiring.
- Test the motor and cable.
- Review ramps and limits.
- Decide whether the drive needs repair.
At each step, use the guide’s section for that code. It gives the cause and corrective action for the revision you hold, which a generic list cannot do.
What do I check when an Optidrive P2 trips on over-current?
Fault 03 happens when you enable the drive. It points to a short or ground fault in the output, wrong motor data or a failing output stage. Meanwhile, fault 15 is an instantaneous over-current on the output, and the guide refers you back to fault 3.
With power locked out, disconnect the motor. Then use a megohmmeter to test the motor and the cable. Next, check the motor data you entered. Finally, if the trip continues with the motor disconnected, suspect the drive and plan a repair.
Also keep the overload figures in mind. The internal motor overload protection is a current limit set at 150% of full-load current, and the drive allows 150% for 60 seconds.
How do I deal with over-voltage and braking trips?
Over-voltage on the DC bus usually comes from the load pushing energy back into the drive during deceleration. A longer deceleration ramp is one fix. A brake resistor is the other. Also check P2-25 if you use fast-stop, and read your guide for the exact ramp parameters.
Next, check the supply side. FLt-dc (13) means DC bus ripple is too high, and P-LOSS (14) means an input phase is gone. In that case, look at fuses, contactors and incoming phases.
The P2 has an internal brake transistor on the v3.02 guide, so you may only need an external resistor. However, confirm your revision first. The related CP2 guide lists OI-b and OL-br for the brake channel, so look for brake faults in your P2 guide’s list.
How do I choose and connect a brake resistor?
First, confirm that your drive has a brake transistor, as covered earlier. Then connect the resistor between the DC+ and BR terminals on the power terminal block. Do not connect it anywhere else.
Next, pick the resistor value from the brake resistor table for your frame size and voltage in the guide. Never use a resistance below the minimum listed there, because the brake transistor can fail. Also size the resistor power for how often and how hard you brake.
Why does my P2 show a Modbus, CANopen or analog input fault?
Faults 50, 51, 52 and 53 mean communication was lost. For Modbus (50), the drive trips if it gets no valid telegram within the watchdog time in P5-06. First, check that the master or PLC is running, then check the cables. For fault 53, check that the IO card is fully inserted.
The other P5 settings, such as address, baud rate and CANopen options, are in the fieldbus section of your guide. Set them to match the master, and set the watchdog time long enough for your network.
Analog inputs can trip too. If an input is set to 4-20 mA or 20-4 mA and the signal falls below 3 mA, the drive trips. However, depending on the setting, it may ramp to Preset Speed 8 (P2-08) instead. In either case, check the signal source and the wiring.
What do the motor PTC, fan and memory fault codes mean?
F-Ptc (21) means the motor PTC thermistor caused the trip. FAN-F (22) means the cooling fan failed. In that case, check the internal fan and replace it if needed.
dAtA-F (17) and dAtA-E (19) are internal memory faults. On fault 17, the parameters were not saved and the drive reloaded defaults. As a result, repeated memory faults are a repair case.
How do I load factory defaults, run auto-tune or set up a PM motor?
When the drive loads factory defaults, it shows P-dEF (fault 10). After that, re-enter your motor data and settings. Use your guide for the exact parameter that triggers the reset on your revision.
Auto-tune and PM motor set-up also depend on the revision. Read the motor control section of your guide, enter the nameplate data first, and run auto-tune with the motor disconnected from the load where the guide says so. If auto-tune trips with AtF-01 (fault 40), the measured stator resistance varies between phases, so check the motor and cable.
When to Stop Troubleshooting and Send the Drive for Repair
When should I stop and send the drive for repair?
The guide says not to attempt repair yourself. Contact your Invertek sales partner or a repair provider in these cases:
- Sto-F faults
- Repeated internal memory faults
- Output faults that persist with the motor disconnected
- Critical fault counters that keep rising
Before you call, collect the full model code, serial number and firmware version from the label. In addition, add the fault number, the P0-13 history and the pre-trip log. Also note the supply voltage, the motor nameplate and what the drive was doing at the trip.
Avoid these common mistakes: resetting again and again without finding the cause, using an old optidrive p2 manual revision, and enabling auto-reset on a hazardous machine. Also avoid swapping in a drive that does not match the voltage class and enclosure.
For routine care, keep the drive clean and dry. Then keep heatsink fins and fans clear, and check that terminals stay tight.
How do I find a service partner, and what warranty or lead time applies?
Start with the Invertek sales partner you bought the drive from, or ask Invertek for a partner near you. Precision Electric also repairs drives, so you can send us the label details and fault history.
Warranty terms and repair lead times depend on the drive, its age and the repair needed. For that reason, ask for them in writing when you request a quote.
Choosing a Replacement or Matching P2 Drive
How do I choose a matching or replacement Optidrive P2?
First match the voltage class and rating. Then match the enclosure, using the 42, 4N and 4A suffixes you learned above. For the safest match, use the part numbers on the label and in your guide.

Here are the P2 drives we list:
| Part number | HP | Input | Amps | Enclosure |
|---|---|---|---|---|
| ODP-2-42100-3HF42-MN | 10 | 208-240 V | 30 | IP20 |
| ODP-2-34100-3HF42-MN | 10 | 380-480 V | 18 | IP20 |
| ODP-2-36100-3H042-MN | 10 | 540-600 V | 12 | IP20 |
| ODP-2-42100-3HF4N-MN, ODP-2-42100-3HF4N-TN | 10 | 208-240 V | 30 | IP55 |
| ODP-2-42100-3HF4A-MN | 10 | 208-240 V | 30 | IP66 outdoor non-switched |
| ODP-2-34100-3HF4A-MN | 10 | 400-480 V | 18 | IP66 outdoor non-switched |
| ODP-2-36100-3H04A-MN | 10 | 540-600 V | 12 | IP66 outdoor non-switched |
| ODP-2-72100-3HF4N-MN, ODP-2-72100-3HF4N-TN | 100 | 208-240 V | 248 | IP55 |
| ODP-2-66100-3H04N-MN, ODP-2-66100-3H04N-TN | 100 | 540-600 V | 105 | IP55 |
Ask us if you are unsure which suffix fits your drive. We can match it to the label details you send.
Frequently asked questions
Where can I download the Optidrive P2 manual?
Invertek’s P2 documentation page lists the P2 User Guide as a PDF. It also lists Size 8 assembly instructions, CAD drawings, certificates and brochures. Then check the version number on the file against your drive. Elevator and Solar Pump P2 variants have their own guides.
What do Invertek Optidrive P2 fault codes look like?
Each trip shows a short mnemonic on the display, such as P-LOSS, F-Ptc, FAN-F or Sto-F. It also has a fault number, such as 14, 21, 22 or 29. The Fault Messages section of the P2 User Guide lists them with corrective actions. In addition, the drive stores the last four faults in P0-13.
How do I reset an Optidrive P2 trip?
Fix the cause first. Then press the keypad Stop/Reset key, remove power fully and reapply it, or, if P1-13 is above 0, switch digital input 1 off and on. Over Modbus, set the reset bit in the command control word and clear it afterwards.
What does the Sto-F fault on an Optidrive P2 mean?
Sto-F (code 29) means the drive found a fault in one of the two internal channels of the Safe Torque Off circuit. The guide’s corrective action is to contact your Invertek sales partner. So treat it as a repair issue, not a settings change.
Can I use one P2 manual for every P2 drive?
Not always. Older ODP-2 guides (rev 1.30) cover a narrower range and differ in details such as brake transistor fitment. Also, the Elevator and Solar Pump variants have their own guides. For that reason, match the guide revision to the label’s model code and firmware.
The right optidrive p2 manual, matched to your label, makes every later step faster, from wiring to reading a trip. Download it from Invertek, note the revision, and always record the fault code before you reset. If you need help with a tripped drive, a repair or a matching replacement, contact Precision Electric or browse our Optidrive P2 drives.