Start Enable 1 Missing on ABB Drives: Causes and Fixes
If you searched for start enable 1 missing ABB, your drive is blocking the start because a permissive signal is absent. This guide shows what the message means on each ABB drive family, where to look, and how to clear it safely. You will also learn what to check when a VFD is not starting the motor and no fault shows.
On this page
- What “Start Enable 1 Missing” means on an ABB drive
- Start enable vs run enable vs STO vs start command: which one is blocking you?
- Find your drive family and message
- Fix start enable 1 missing ABB alarms on ACS355, ACS550 and ACH550 (alarm 2021)
- Fix enable start signal missing on ACS180, ACS380, ACS580 and ACS880
- ACS255 micro drive: no run, display shows InHibit
- Step-by-step check order when an ABB VFD won’t start the motor
- Safety: STO, restarts and bypassing enables
- Common mistakes behind start enable missing
- When to call for repair or help
- Frequently asked questions
- What does “Start enable 1 missing” mean on an ABB drive?
- How do I clear alarm 2021 Start Enable 1 Missing?
- What is the difference between start enable and run enable on ABB drives?
- How do I find out what is inhibiting an ABB drive from starting?
- Why does my ABB ACS255 show InHibit and not run?
- Why is my VFD not starting the motor with no fault showing?
What “Start Enable 1 Missing” means on an ABB drive
What does “Start enable 1 missing” mean?
It is a permissive signal. The drive has a start enable source configured, such as a digital input or the fieldbus control word. If that signal is absent, the drive refuses or inhibits a start command.

On the ACS355, ACS550 and ACH550, it appears as alarm 2021 START ENABLE 1 MISSING. Alarm 2022 is the Start Enable 2 equivalent. Newer drives use other names. The ACS180 shows warning AFEA, “Enable start signal missing”. On the ACS380 and ACS880, it shows as “Lost start enable”, which is bit 4 of parameter 06.18 Start inhibit status word.
This is a logic, wiring or parameter condition. The drive powers up fine but will not run. It is not normally a power section failure.
Is start enable missing a fault or a warning?
On the ACS355, ACS550 and ACH550, it is an alarm, so the drive does not trip. You see a start inhibit instead of a fault. On the ACS310 and ACS350, the manuals put START ENABLE 1 MISSING and START ENABLE 2 MISSING in the alarm words, not the fault word. They are alarms 2021 and 2022, shown as 0309 (Alarm Word 2) bit 4 and bit 5. On the ACS180, the status LED blinks green for a warning and stays steady red for a fault. When the start icon blinks on the panel, the drive received a start command but blocks it.
Start enable vs run enable vs STO vs start command: which one is blocking you?
What is the difference between start enable, run enable and STO?
These are separate signals with separate parameters. ABB notes that start enable differs from run enable. With start enable off, the drive inhibits a new start command. On the ACS380, turning it off while the drive runs does not stop the drive.
Run enable has its own source. On the ACS180, warning AFEB means run enable is missing, and parameter 20.12 Run enable 1 source sets it. STO, or Safe Torque Off, works as a hardware safety input. It is a different circuit from both enables.
Control location matters too. The panel Start key works only when the drive is under local control. If the drive is in remote, the start command must come from the selected external source.
| What you see | Likely signal | Where to look |
|---|---|---|
| Alarm 2021 | Start enable 1 | Parameter 1608 |
| Warning AFEA | Enable start signal | Parameter 20.19 |
| Warning AFEB | Run enable | Parameter 20.12 |
| InHibit on ACS255 | STO inputs | Terminals 12 and 13, plus DI1 |
| Start key does nothing | Control location | Local or remote setting |
Find your drive family and message
Which ABB drives show alarm 2021 and which show AFEA?
The same symptom has different names across families. Use this list to match yours.

- ACS355, ACS550, ACH550, ACQ550, ACS310, ACS350: alarm 2021 and parameter 1608. Parameter 1609 covers enable 2.
- ACS180, ACS380, ACS580, ACS880: enable start signal missing, parameter 20.19, and the start inhibit word 06.18.
- ACS255 micro drive: no start enable parameter in the same sense. Check DI1 (Stop/Run enable), the STO terminals 12 and 13, and the “InHibit” display.
Not every start enable 1 missing ABB message uses alarm 2021 or parameter 1608. Also, the AFEA and AFEB codes came from a third-party list, so confirm them in the ACS180 firmware manual (3AXD50000467860).
Are newer HVAC drives like the ACH580 and ACQ580 covered?
Yes, in most cases. The ACH580 and ACQ580 share the ACS580 platform, so look for the same style of message: an enable start signal missing condition. Check parameter 20.19 and the start inhibit word 06.18 first. The ACS310 is older and follows the 1608 and alarm 2021 pattern. Confirm the exact wording in the manual for your drive type.
Where do I find the ABB manual and parameter list?
Read the drive type code on the nameplate first. Then use the ABB document library to find the manual for that type. Our existing post on ABB drive type codes explains how to identify your family.
Each family has its own manual. The ACS550-01/U1 User’s Manual covers parameters 1608 and 1609 and alarms 2021 and 2022. The ACS180 Hardware manual covers STO and the panel status icons. Finally, the ACS255 micro drives user’s manual shows the STO terminals.
Fix start enable 1 missing ABB alarms on ACS355, ACS550 and ACH550 (alarm 2021)
How do I fix alarm 2021 start enable 1 missing?
First, read parameter 1608 to see which source the drive expects. Next, check the digital input configuration and the wiring to that terminal. If the source is COMM, check the fieldbus communication settings. Also, on the ACH550 and ACS550, one listed check is an encoder not in use while parameter 5002 ENCODER ENABLE reads 1 (ENABLED).
What does parameter 1608 do for start enable 1?
Parameter 1608 START ENABLE 1 selects the source of the start enable 1 signal. These are the options:
- 0 = NOT SEL: the drive starts without an external start enable signal. On the ACH550, the HVAC default macro wires DI3 as a safety interlock on 1608, so NOT SEL is not the default there. I found no page that states a NOT SEL default for the ACS550 or ACS355.
- DI1 and other inputs: that input must be active. The drive will not start until the signal returns.
- COMM: the fieldbus command word supplies the enable.
Parameter 1609 and alarm 2022 follow the same logic for Start Enable 2.
How do start enable and run enable differ on the ACS550 and ACH550?
These drives have a separate run enable, set by parameter 1601 RUN ENABLE. It has its own source, apart from 1608 and 1609. As on other ABB drives, start enable only inhibits a new start. Run enable is the signal that must stay present for the drive to run.
A damper interlock uses whichever enable your macro or installer wired for it. On the ACH550 HVAC default macro, that is DI3 on 1608. Read 1601 and 1608 to see which one points at the damper input.
What if the enable comes over fieldbus?
If the source is COMM, a building automation system or PLC must send the enable bit. The network link must also be healthy. So check the communication settings, then confirm the controller is actually writing that bit.
If you do not use the function, you can set 1608 to 0 (NOT SEL). Do that only after you confirm that no interlock or safety circuit relies on it.
Fix enable start signal missing on ACS180, ACS380, ACS580 and ACS880
What is parameter 20.19 for the enable start signal?
Parameter 20.19 selects the source for the start enable signal. On the ACS380 it is called Enable start signal. With the signal off, the drive inhibits any start command. Check the source it selects, then check the wiring or control word behind that source.

How do I read the start inhibit status word (06.18)?
Open parameter 06.18 Start inhibit status word. It shows what prevents the start. On the ACS380, the bits are:
- Bit 0 means not ready run.
- Control location changed is bit 1.
- SSW inhibit is bit 2.
- Lost start enable shows in bit 4.
- Finally, bit 5 means lost run enable.
The ACS880 list also includes bit 7 STO and bit 11 Emergency Stop Off1. That list is a third-party summary, so verify it in the ACS880 firmware manual. If bit 5 is set, check the source in 20.12 Run enable 1 source and its wiring.
Where do I view 06.18 and 20.19 on the panel or Drive composer?
On the panel, open the parameter menu, pick group 06, then select parameter 18. For 20.19, go to group 20 and select parameter 19. In Drive composer, open the parameter list or browser and find the same group and number. You can also add 06.18 to the monitor window to watch the bits change live. The menu names differ a little by panel type, so check your manual.
What does start inhibit mean, and how do I clear it?
Start inhibit means the drive is stopped and will not start. To start, remove the inhibiting signal and then cycle the start signal. In the manual, conditions with an asterisk need only the start command cycled. You must remove all others first.
The ACS580 manual also lists a start inhibit bit where 1 means start inhibited. Its default terminal layout shows DI1 as Stop (0)/Start (1), so a start input that stays on can look like a missing enable.
ACS255 micro drive: no run, display shows InHibit
Why does my ACS255 show InHibit?
InHibit means the STO inputs have no power. If the drive trips, it shows the trip instead. The STO function stays on, whatever the operating mode or parameter changes. No source shows a “start enable 1” parameter on this drive.
How do I wire the STO inputs?
The ACS255 needs external links to the STO inputs on terminals 12 and 13. Without a safety circuit, link terminal 1 to terminal 12 (STO+) and terminal 9 to terminal 13 (STO-). Then check DI1, shown as Stop/Run (Enable) in the wiring diagrams, and make sure it is closed.
The ACS255 Micro Series we sell falls in this family. It is NEMA 4X/IP66, and some versions add an integrated disconnect, speed pot and forward/reverse switch.
Step-by-step check order when an ABB VFD won’t start the motor
Why is my VFD not starting the motor when there is no fault?
The cause is usually an enable or inhibit condition. It may be a missing start or run enable, an open STO circuit, the wrong control location, or a start command you must cycle. Read the status or inhibit word before you replace hardware. Work in this order:

- Read the exact message: alarm 2021, AFEA, AFEB, InHibit, or none.
- Confirm the control location and that the start command comes from the right source.
- Find the enable source parameter and read the live input or status word.
- Measure at the terminal to verify the input sees the enable. Use the voltage level in the manual for that drive.
- Check both STO channels.
- Check parameters and the fieldbus control word if the source is COMM.
- Cycle the start command after you clear an inhibit, and reset any faults.
- Only then suspect hardware.
What voltage should I measure at the enable terminal?
Most ABB drives power their digital inputs from the drive’s own 24 V DC auxiliary supply, so a closed enable contact should read about 24 V DC at the input. STO inputs also use 24 V DC class signals. However, the exact on and off thresholds differ by drive, so take them from the manual’s specifications.
To test the enable step by step:
- Find the enable input in 1608 or 20.19 and note the terminal.
- Set your meter to DC volts and follow your lockout and safe work rules for live testing.
- Place one probe on the input terminal and the other on the matching common terminal.
- Close the enable contact, such as the damper switch or interlock, and read the meter.
- Open the contact and confirm the reading drops to near zero.
- Compare the reading with the drive’s digital input status. If the terminal shows 24 V DC but the drive shows the input off, suspect the drive.
Why does the drive start in Local but not in Remote?
In local, the panel Start key supplies the command. In remote, the command comes from the external source, and the enables must be present too. As a result, a drive can run from the panel while a missing enable or a wrong start source blocks remote starts. Also note that a changed control location sets bit 1 in 06.18.
Do I need to cycle the start command?
Often, yes. After you remove the inhibiting signal, cycle the start signal. Some conditions need only that, and you must clear others first.
How do 2-wire and 3-wire start modes affect a drive that will not restart?
A 2-wire start is level based. The drive runs while the start input stays on. A 3-wire start is edge based. It uses a pulse, so the drive needs a fresh pulse after an inhibit clears. In either case, a drive that stays stopped after the enable returns may be waiting for a new start edge.
On the ACS355, ACS550 and ACH550, parameter 1001 EXT1 COMMANDS sets the start method for external control location 1. On the ACS580 and ACS880, look in group 20 for the start trigger type, parameter 20.02. Check the manual for the ACS180 and ACS380.
Safety: STO, restarts and bypassing enables
Is it safe to clear start enable missing by setting NOT SEL or jumpering the enable?
Not without checking first. Installers often wire the enable to dampers, interlocks or a safety loop. Bridging it or setting 1608 to NOT SEL can remove protection for equipment or people. Confirm what the signal protects before you change anything. Also, lock out and tag out before you touch terminals.
Can an ABB drive restart by itself after STO is restored?
It can. The ACS180 manual warns that if both STO circuits close while a level-type start signal is active, the drive may start without a fresh start command. In addition, loss of only one STO signal always causes a fault, because the drive reads it as an STO wiring or hardware malfunction. After STO loss, the drive will not start until both signals return and you reset faults.
How are STO losses reported, and what does parameter 31.22 do?
On drives such as the ACS580, parameter 31.22 sets how the drive reports loss of the STO signals. Depending on the setting, and on whether the drive is running or stopped, it shows a fault, a warning, or no indication. Each family also has its own STO fault codes. Look them up in the manual for your drive, because I could not confirm the code meanings here.
Common mistakes behind start enable missing
What are the most common mistakes behind start enable missing?
- Treating start enable, run enable and STO as one signal.
- Pointing the source parameter at an input that is not wired, then forgetting the change.
- Forgetting the BAS or PLC bit when the source is COMM.
- Leaving a level-type start signal on and wondering why the drive will not start after you clear an inhibit.
- Replacing the drive before reading the inhibit status.
When to call for repair or help
When is start enable missing a hardware failure?
Suspect hardware when the enable measures correct at the terminal and the parameter points at it, yet the drive still reports it missing. Then the control board or I/O terminal may be at fault. Faults that return after reset, or hardware STO faults, also point to repair. In those cases, send the drive for repair or exchange.

How can I confirm a control board or I/O terminal failure?
Compare the terminal voltage with the drive’s digital input status. If the terminal reads 24 V DC but the drive shows the input as off, the input is reading wrong. Next, move the signal to a spare input, point the parameter at it, and test again. If the spare input works and the original does not, the I/O circuit is likely bad.
For repair or exchange, gather the full type code from the nameplate, the exact message, and your test results. Then contact Precision Electric, and we will go over repair and exchange options with you.
Where can I buy or replace an ABB ACS180 or ACS255?
Precision Electric sells the ABB ACS180 series, such as the ACS180-04S-02A4-2, and the ACS255 Micro Series in several voltage and enclosure options.
Frequently asked questions
What does “Start enable 1 missing” mean on an ABB drive?
The drive has a start enable source configured, such as a digital input or the fieldbus control word, and is not receiving that signal. So it blocks the start. On ACS355, ACS550 and ACH550 drives, it is alarm 2021, and parameter 1608 sets the source.
How do I clear alarm 2021 Start Enable 1 Missing?
Check parameter 1608 to see which source is selected. Then check the wiring and digital input configuration for that source, and the fieldbus settings if it is COMM. Set 1608 to 0 (NOT SEL) only if no external enable or interlock is needed.
What is the difference between start enable and run enable on ABB drives?
They are separate signals with separate parameters. With start enable off, the drive inhibits a new start command, and on the ACS380 turning it off while running does not stop the drive. Run enable has its own source parameter, 20.12 on the ACS180 and 1601 on the ACS550 and ACH550.
How do I find out what is inhibiting an ABB drive from starting?
On ACS380, ACS580 and ACS880 drives, read parameter 06.18 Start inhibit status word. Bit 4 is lost start enable and bit 5 is lost run enable. Some inhibits clear when you cycle the start command, while you must remove others first.
Why does my ABB ACS255 show InHibit and not run?
InHibit means the STO inputs have no power. Check the links or safety circuit on terminals 12 and 13, for example terminal 1 to 12 and terminal 9 to 13. Also check that DI1 (Stop/Run enable) is closed.
Why is my VFD not starting the motor with no fault showing?
Usually an enable or inhibit condition blocks the start. Look for a missing start or run enable, an open STO circuit, the wrong local or remote setting, or a start command that needs cycling. Read the status or inhibit word before you replace hardware.
Start enable 1 missing ABB messages are signal problems, so start with the message, find your drive family, and follow the enable back to its source. Read the inhibit word, check both enables and the STO circuit, and change nothing safety related without knowing what it protects. If the drive still will not run, contact Precision Electric for repair, a quote, or a replacement drive.